| 2008-07-15 16:35:25 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEWSECOND |
| | CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- INSTALLATION SCHEDULESUBMITTED DOESN'T REFLECT |
| | INFORMATIONMARKED ON THE PRODUCT APPROVAL DRAWINGS. |
| | EG:"U" HEADER IS MARKED WITH #16. THERE IS NOT #16 ON |
| | INSTALLATION SCHEDULE.ALSO, THERE ARE NOT STUD ANGLES |
| | SHOWN ON THE MOUNTING CONDITIONS AND IN THE |
| | INSTALLATION SCHEDULE. AND,DRAWINGS ARE MARKED WITH |
| | THE INSTALLATION SCHEDULE FOR CONCRETE, WHILE |
| | INSTALLATION SCHEDULE CALLS FOR CONCRETE BLOCK. REVISE |
| | AS REQUIRED. |
| | |
| | |
| | 2- INFORMATION SUBMITTED ON OCEAN SHUTTERSLETTER HEAD |
| | CALLS FOR OPENINGS # 5 AND #6 TO HAVE TRACK AND HEADER |
| | RESPECTIVELY.INSTALLATION SCHEDULE DOESN'T REFLECT |
| | THIS.REVISE CONNECTION TYPEAND ANCHOR SPACING AS |
| | REQUIRED. |
| | |
| | 3-ANCHOR SCHEDULE MARKED ON SHEET 4 OF 5 OF STORM |
| | SHUTTERS IS FOR CONCRETE SUBSTRATE INSTALLATION ONLY. |
| | PROVIDE DOCUMENTATION THAT SHOWS THAT EXISTING |
| | SUBSTRATE IS 3,000/3,140 PSI AT TOP AND BOTTOM OF STORM |
| | SHUTTERS INSTALLATIONS.OTHERWISE, TABLE FOR HOLLOW |
| | CONCRETE BLOCK SHALL BE USED OR SITE SPECIFIC |
| | ENGINEERING WILL BE REQUIRED. (TYPICALLY, WINDOW |
| | SILLS ARE NOT POURED OR PRECAST SILLS, BUT FILLED |
| | CONCRETE BLOCK. THAT'S WHYSITE SPECIFIC PROOF IS |
| | REQUIRED TO USE THE CONCRETE TABLE).SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH |
| | THE PROPOSED INSTALLATION AND DESIGN PRESSURES OF SEC. |
| | R301 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW.UPDATE VALUATIONAS REQUIRED BY SEC. 108.3 CITY |
| | AMENDMENTS TO FBC 2004. (REPEAT COMMENT). |
| | |
| | 5- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. (REPEAT COMMENT). |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |