Plan Review Details - Permit 08060908
Plan Review Stops For Permit 08060908
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-07-23 Cont ID  
Sent By jgomez Date 2008-07-23 Time 14:33 Rev Time 0.00
Received By jgomez Date 2008-07-23 Time 14:33 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-07-21 Cont ID  
Sent By jgomez Date 2008-07-21 Time 14:34 Rev Time 0.00
Received By jgomez Date 2008-07-21 Time 12:34 Sent To PC
Notes
2008-07-21 14:51:08RESIDENTIAL (R3)SHUTTERS, BUILDING REVIEWTHIRD
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-INFORMATION SUBMITTED ON OCEAN SHUTTERS LETTER HEAD
 CALLS FOR OPENING #6 TO HAVE HEADER.INSTALLATION
 SCHEDULE DOESN'T REFLECT THIS. REVISE CONNECTION TYPE
 AND ANCHOR SPACING AS REQUIRED.(REPEAT COMMENT).
  
 2- DESIGN PRESSURES SHOWN ON INSTALLATION SCHEDULE ARE
 DIFFERENT FROM THOSE DESIGN PRESSURES SHOWNON THE
 WIND LOADS CALCULATIONS AND DESIGN PRESSURES
 HIGHLIGHTED ONSHUTTERSPAGE 5 OF 5. COORDINATE
 INFORMATION AS REQUIRED WITH EACH OPENING AND REVISE AS
 REQUIRED TO MATCH.REVISE ANCHOR SPACING AS REQUIRED.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 * NOTE: THIS MAY BE PROVIDED AT TIME OF PERMIT PICK
 UP.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-07-15 Cont ID  
Sent By jgomez Date 2008-07-15 Time 16:14 Rev Time 0.00
Received By jgomez Date 2008-07-15 Time 16:14 Sent To PC
Notes
2008-07-15 16:35:25RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEWSECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- INSTALLATION SCHEDULESUBMITTED DOESN'T REFLECT
 INFORMATIONMARKED ON THE PRODUCT APPROVAL DRAWINGS.
 EG:"U" HEADER IS MARKED WITH #16. THERE IS NOT #16 ON
 INSTALLATION SCHEDULE.ALSO, THERE ARE NOT STUD ANGLES
 SHOWN ON THE MOUNTING CONDITIONS AND IN THE
 INSTALLATION SCHEDULE. AND,DRAWINGS ARE MARKED WITH
 THE INSTALLATION SCHEDULE FOR CONCRETE, WHILE
 INSTALLATION SCHEDULE CALLS FOR CONCRETE BLOCK. REVISE
 AS REQUIRED.
  
  
 2- INFORMATION SUBMITTED ON OCEAN SHUTTERSLETTER HEAD
 CALLS FOR OPENINGS # 5 AND #6 TO HAVE TRACK AND HEADER
 RESPECTIVELY.INSTALLATION SCHEDULE DOESN'T REFLECT
 THIS.REVISE CONNECTION TYPEAND ANCHOR SPACING AS
 REQUIRED.
  
 3-ANCHOR SCHEDULE MARKED ON SHEET 4 OF 5 OF STORM
 SHUTTERS IS FOR CONCRETE SUBSTRATE INSTALLATION ONLY.
 PROVIDE DOCUMENTATION THAT SHOWS THAT EXISTING
 SUBSTRATE IS 3,000/3,140 PSI AT TOP AND BOTTOM OF STORM
 SHUTTERS INSTALLATIONS.OTHERWISE, TABLE FOR HOLLOW
 CONCRETE BLOCK SHALL BE USED OR SITE SPECIFIC
 ENGINEERING WILL BE REQUIRED. (TYPICALLY, WINDOW
 SILLS ARE NOT POURED OR PRECAST SILLS, BUT FILLED
 CONCRETE BLOCK. THAT'S WHYSITE SPECIFIC PROOF IS
 REQUIRED TO USE THE CONCRETE TABLE).SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH
 THE PROPOSED INSTALLATION AND DESIGN PRESSURES OF SEC.
 R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW.UPDATE VALUATIONAS REQUIRED BY SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004. (REPEAT COMMENT).
  
 5- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE. (REPEAT COMMENT).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-01 Cont ID  
Sent By jgomez Date 2008-07-01 Time 11:21 Rev Time 0.00
Received By jgomez Date 2008-07-01 Time 11:09 Sent To PC
Notes
2008-07-01 11:45:38RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEWCHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE A COMPLETE INSTALLATION SCHEDULE(SEE
 ATTACHED SAMPLE).OR PROVIDE ANYOTHER FORMAT THAT
 WILL PROVIDE ALL THE INFORMATION REQUIREDON THE
 ATTACHED SAMPLE AS REQUIRED BYCITY IMPLEMENTATION
 STANDARD FOR WIND-BORNE DEBRIS IMPACT PROTECTION.SEE
 ATTACHED COPY.
  
 2-ANCHOR SCHEDULE MARKED ON SHEET 4 OF 5 OF STORM
 SHUTTERS IS FOR CONCRETE SUBSTRATE INSTALLATION ONLY.
 PROVIDE DOCUMENTATION THAT SHOWS THAT EXISTING
 SUBSTRATE IS 3,000/3,140 PSI AT TOP AND BOTTOM OF STORM
 SHUTTERS INSTALLATIONS.OTHERWISE, TABLE FOR HOLLOW
 CONCRETE BLOCK SHALL BE USED OR SITE SPECIFIC
 ENGINEERING WILL BE REQUIRED. (TYPICALLY, WINDOW
 SILLS ARE NOT POURED OR PRECAST SILLS, BUT FILLED
 CONCRETE BLOCK. THAT'S WHYSITE SPECIFIC PROOF IS
 REQUIRED TO USE THE CONCRETE TABLE).SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH
 THE PROPOSED INSTALLATION AND DESIGN PRESSURES OF SEC.
 R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. UPDATE VALUATIONAS REQUIRED BY SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004.
  
 4- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-10 Cont ID  
Sent By adarroug Date 2008-07-10 Time 09:16 Rev Time 0.00
Received By adarroug Date 2008-07-10 Time 09:14 Sent To B
Notes
2008-07-10 09:14:47TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-01 Cont ID  
Sent By jgomez Date 2008-07-01 Time 11:49 Rev Time 0.00
Received By jgomez Date 2008-07-01 Time 11:09 Sent To  
Notes
***NONE***