Plan Review Details - Permit 08060892
Plan Review Stops For Permit 08060892
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-16 Cont ID  
Sent By jwitmer Date 2008-07-16 Time 15:34 Rev Time 4.44
Received By jwitmer Date 2008-07-16 Time 15:34 Sent To  
Notes
2008-07-16 15:58:30BUILDING PLAN REVIEW
 PERMIT: 08060892
 ADD: 2497 OKEECHOBEE BLVD
 CONT: WARWICK CONSTRUCTION
 TEL: (832)448-7000
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION. IT APPEARS
 TO BE A OLD SET OF PLANS WITHIN THE PLAN DOCUMENT,
 PLEASE REMOVE ALL OLD SHEETS AND HAVE THE CURRENT SET
 OF DOCUMENTS STAPLED TOGETHER.
  
 1B) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) SHEET A0-0 CODE INFORMATION:
  
 2A) BUILDING TYPE IS INDICATED AS 2C PLEASE SEE
 BUILDING TYPE II HAS ONLY AN A OR B DESIGNATION. TABLE
 601 AND SECTION 603.
  
 2B) BUILDING DESCRIPTION# 8 INDICATES A STOREFRONT
 RENOVATION WHILE NOTES WITHIN THE DOCUMENT INDICATE TO
 REWORK THE EXISTING DOORS, DESCREPANCY PLEASE CORRECT.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 2C) BUILDING DESCRIPTION NOTE# 10 ALSO INDICATES ENERGY
 CALCULATION ARE ATTACHED, THERE ARE NO ENERGY
 CALCULATIONS WITHIN THE PERMIT PACKAGE.
  
 3) PHILLIPS PARTNERSHIP IS MISSING THEIR CERTIFICATE OF
 AUTHORIZATION.481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ARCHITECT PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.ADD THE NUMBER TO EACH
 SHEET.
 THIS MAY BE ADDED BY HAND.
  
 4) MISSING THE ARCHITECTS SIGNATURE AND SEAL.
 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE
 NUMBER
 XX - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 XX - STATE DATE PREPARED
 XX - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEALED
 INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-18 Cont ID  
Sent By dpalmer Date 2008-07-18 Time 11:40 Rev Time 0.00
Received By dpalmer Date 2008-07-18 Time 11:40 Sent To  
Notes
2008-07-18 11:41:06** DENIED **
  
 1) NOTE: PLEASE SEE PLANS BEING SUBMITTED FOR EXPIRED
 PERMIT ARE ALL PHOTO-COPIES OF SIGNED AND SEALED PLANS
 WHICH IS NOT PERMITTED UNDER FS 481.221, 471.025, FAC
 61G15-23.002 ETC
  
 2) NOTE: PLEASE BE SURE ALL ELECTRICAL IS THAT OF THE
 PERMITTED SET OF PLANS WITH ANY CHANGES. PLANS
 SUBMITTED ARE NOT THE SAME.
 THE PLANS SUBMITTED ARE NOT THE PLANS STAMPED WHEN
 ISSUED FOR PERMIT. IN FACT THERE WERE SEVERAL CODE
 REVIEWS BEFORE THIS PERMIT WAS ISSUED. THE PLANS
 SUBMITTED HAD AT A MINIMUM OF THREE ELECTRICAL
 REVISIONS BEFORE ISSUANCE.
 PLEASE SEE 2005 NFPA-70, 2003 NFPA-101, 2004 FBC W/2006
 REVISION ETC
 FBC 106.1 FOR MINIMUM INFORMATION REQUIRED.
  
 3) NOTE: PLANS NEED TO COMPLY WITH THE FLORIDA ENERGY
 CODE.
 FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2 AND .1.3,
 13-415.2, 13-415.2.ABC.1.1,.1.2
 PLEASE SUBMIT THE COMPLETED FLA COM CALCULATIONS. THE
 INPUT DATA REPORT REQUIRED IS MISSING FROM PLANS AND
 PACKAGE. THIS INFORMATION NEEDS TO BE SHOWN.
  
 3) NOTE: PLEASE SEE THE PLANS AND TITLE BLOCKS ARE
 MISSING REQUIRED INFORMATION PER FAC 61G15-23.002 AND
 FS 471.023 FOR ENGINEERING FIRM.
 PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS PER FAC
 61G1-16.004, FS 481.219 FOR ARCHITECTURAL FIRM.
  
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-24 Cont ID  
Sent By mawillia Date 2008-07-24 Time 12:51 Rev Time 0.00
Received By mawillia Date 2008-07-24 Time 11:42 Sent To  
Notes
2008-07-24 12:51:18*****DENIED*****
  
  
 1. THE SUBMITTED PLANS SHALL BE SIGNED AND SEALED.
  
 2. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED IN ADDITION TO THE 2004 FLORIDA FIRE
 PREVENTION CODE
  
 3. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4. THE REMOVAL AND (OR) THE REPLACEMENT OF BUILDING
 MATERIALS & SUPPLIES SHALL NOT HINDER OR INTERFERE WITH
 EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING FIRE LANES) .
  
 5. ON SHEET A0-0, THE PROJECT TEAM INFORMATION IS
 INCORRECT. PLEASE BE ADVISED THAT AHJ FOR THE JOB SITE
 IS THE CITY OF WEST PALM BEACH. AMEND BUILDING
 DEPARTMENT AND FIRE DEPARTMENT INFORMATION.
  
 6. SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE EXTERIOR
 ELEVATION WHICH FRONTS OKEECHOBEE BOULEVARD. AS PER
 WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN
 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE.
  
 7. SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN THE TERMS OF CLASS A, CLASS B, OR CLASS
 C.
  
 8. PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCES
 TO THE EXITS, EXIT LIGHTS, EMERGENCY LIGHTS, FIRE
 EXTINGUISHERS, AND ANY OTHER PERTINENT LIFE SAFETY
 FEATURES.
  
 9. PROVIDE A LAYOUT FOR THE SPRINKLER HEADS AND A
 LAYOUT FOR THE FIRE ALARM DEVICES FOR THIS FLOOR PLAN.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WIOLLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-24 Cont ID  
Sent By mawillia Date 2008-07-24 Time 11:43 Rev Time 0.00
Received By mawillia Date 2008-07-01 Time 14:37 Sent To  
Notes
2008-07-01 14:38:06TO "COMM" BD#35

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-07-15 Cont ID  
Sent By rregueir Date 2008-07-15 Time 13:12 Rev Time 0.00
Received By rregueir Date 2008-07-15 Time 13:09 Sent To  
Notes
2008-07-15 13:12:52THERE ARE NO MECHANICAL ADDITIONS OR MODIFICATIONS
 ASSOCIATED WITH THIS SCOPE OF WORK.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-21 Cont ID  
Sent By kstevens Date 2008-07-21 Time 15:10 Rev Time 0.00
Received By kstevens Date 2008-07-21 Time 15:10 Sent To  
Notes
2008-07-21 15:33:22DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS SUBMITTED SHALL BE SIGNED, SEALED & DATED
 AND HAVE ALL THE INFORMATION IN THE TITLE BLOCK AS
 REQUIRED BY SECTION 106.1, FAC 61G1-16.001,
 61G1-16.002, 61G1-16.003 & 61G1-16.004,
 61G15-23.002(1)(2) AS WELL AS FS 481.219, 481.2055,&
 471.025.
  
 2. SUBMIT ONLY SHEETS THAT WILL BE REVIEWED AND
 STAMPED. REMOVE ALL OTHER SHEETS. SECTION 106.1.3.
  
 3. THE REVISIONS INDICATED ON THE SET OF PLANS
 PREVIOUSLY REVIEWED AND STAMPED FOR CONSTRUCTION HAVE
 MORE INFORMATION AND REVISION NUMBERS THAT THE SHEETS
 SUBMITTED FOR THIS PERMIT. (EXAMPLE SHT A0-0 SUBMITTED
 WITH REVISION #1 ONLY. SHT A0-0 STAMPED FOR PREVIOUS
 PERMIT NUMBER 07040301 HAS REVISIONS NUMBERED 1, 2 &
 3). THE PLANS ARE NOT CODE COMPLIANT AS SUBMITTED.
  
 4. ALL SHEETS WITH THE ARCHITECTURAL TITLE BLOCK
 REQUIRE THE BUSINESS LICENSE NUMBER, THE PHONE NUMBER,
 THE SIGNATURE & THE PRINTED NAME OF THE ARCHITECT AT A
 MINIMUM PER FAC 61G1-16.004(1)(2)(5)(6) & FS 481.219,
 481.2055.
  
 5. SHT A0-1 ROOM FINISH SCHEDULE. THE TOILET ROOM WALL
 FINISHES, PER SECTION 1210.2 REQUIRE ALL WALLS WITHIN 2
 FEET OF URINALS & WATER CLOSETS SHALL HAVE A "SMOOTH,
 HARD, NONABSORBENT SURFACE". PAINTED WALLS DO NOT
 COMPLY WITH THE "HARD" PORTION OF THE REQUIREMENT.
 PLEASE SHOW COMPLIANCE.
  
 6. SHTS A1-1, A1-3 & A2-0. SHT A1-1 SHOWS A SINK IN THE
 STOCK ROOM THAT IS NOT INDICATED ON SHTS A1-3 OR A2-0.
 IS THE SINK EXISTING & WILL IT BE DEMO'D? PLEASE
 CLARIFY. IF THE SINK WILL BE DEMO'D, DEAD ENDS ARE
 PROHIBITED PER SECTION 704.5. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-07-09 Cont ID  
Sent By lfranco Date 2008-07-09 Time 17:36 Rev Time 0.00
Received By lfranco Date 2008-07-09 Time 17:36 Sent To  
Notes
2008-07-09 17:39:26PLANNING AND ZONING:NO REVIEW REQUIRED.
  
 1. HOWEVER, IF A NEW SIGN FOR "OLD NAVY" IS PROPOSED, A
 REVIEW BY THE PLANNING AND ZONING DEPARTMENT WILL BE
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 OFFICE: (561) 822-1443