Plan Review Details - Permit 08060891
Plan Review Stops For Permit 08060891
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-25 Cont ID  
Sent By mjacobs Date 2008-07-25 Time 14:07 Rev Time 0.00
Received By mjacobs Date 2008-07-25 Time 11:06 Sent To  
Notes
2008-07-25 14:07:43BUILDING PLAN REVIEW
 PERMIT: 08060891
 ADD: ?
 CONT: ALL - STATE TECHNICAL SOLUTIONS
 TEL: (954)474-4172
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)AS STATED BEFORE, THE ADDRESS ON THE APPLICATION
 AND PLANS DO NOT MATCH. FOR INSPECTION AND RECORD
 PURPOSES THE CORRECT ADDRESS FOR THE PROJECT INDICATED
 ON THE SUBMITTED APPLICATION SHALL MATCH THE ADDRESS ON
 THE PLANS.THE ADDRESS ON THE APPLICATION IS 7515 S.
 DIXIE HWY AND THE PLANS SHOW 7915 S. DIXIE HWY, SO
 WHICH ONE IS THE CORRECT ADDRESS? CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED.
 106.1.1
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-24 Cont ID  
Sent By btrobaug Date 2008-07-24 Time 15:39 Rev Time 0.00
Received By btrobaug Date 2008-07-24 Time 11:38 Sent To  
Notes
2008-07-24 15:16:58 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, NFPA 110-2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 1} 700.12 (B)(2) INTERNAL COMBUSTION AS PRIME MOVERS
 WHERE INTERNAL COMBUSTION ENGINES ARE USED AS THE PRIME
 MOVER, AN ON-SITE FUEL SUPPLY SHALL BE PROVIDED WITH AN
 ON-PREMISE FUEL SUPPLY SUFFICIENT FOR NOT LESS THAN 2
 HOURS' FULL-DEMAND OPERATION OF THE SYSTEM. WHERE POWER
 IS NEEDED FOR THE OPERATION OF THE FUEL TRANSFER PUMPS
 TO DELIVER FUEL TO A GENERATOR SET DAY TANK, THIS PUMP
 SHALL BE CONNECTED TO THE EMERGENCY POWER SYSTEM.
 700.12 (B)(3) DUAL SUPPLIES PRIME MOVERS SHALL NOT BE
 SOLELY DEPENDENT ON A PUBLIC UTILITY GAS SYSTEM FOR
 THEIR FUEL SUPPLY OR MUNICIPAL WATER SUPPLY FOR THEIR
 COOLING SYSTEMS. MEANS SHALL BE PROVIDED FOR
 AUTOMATICALLY TRANSFERRING FROM ONE FUEL SUPPLY TO
 ANOTHER WHERE DUAL FUEL SUPPLIES ARE USED. THE PROPOSED
 NATURAL GAS GENERATOR DOES NOT COMPLY WITH THESE
 ARTICLES.
  
 2} PANEL E-4 AND PANEL E-1FED FROM MDP1, SHEET E-1,
 WERE ORIGINALLY FED FROM THE REQUIRED EMERGENCY SYSTEM
 AND NOW ARE FED FROM THE OPTIONAL SYSTEMS. PROVIDE
 PANEL SCHEDULES FOR THESE PANELS INDICATING THERE ARE
 NO LIFE SAFETY CIRCUITS BEING FED FROM THE OPTIONAL
 GENERATOR.
  
 3} SHEET E-1 PANEL "EDP". THE #2/0 CONDUCTORS FEEDING
 "PLL" HAVE AN OCP OF 200 AMPS WHICH IS IN VIOLATION OF
 310.16 AND NONCOMPLIANT WITH ARTICLE 240.4(B)(2), WHICH
 INDICATES A 175 AMP OCPFOR THOSE CONDUCTORS.
  
 4} PROVIDE PANEL SCHEDULES FOR NEW PANELS "CL", "EM"
 AND "PLL". PER 408.4 AND 106.3.5.1.2 FBC AS AMENDED.
  
 5} THE ADDRESS ON THE PLAN AND THE APPLICATION DO NOT
 CORRELATE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-30 Cont ID  
Sent By mwennerg Date 2008-07-30 Time 14:19 Rev Time 0.00
Received By mwennerg Date 2008-07-30 Time 14:19 Sent To  
Notes
2008-07-30 14:26:58***DENIED***
  
 1) ADDRESS ON PLANS DO NOT CORRELATE WITH PERMIT
 APPLICATION.
  
 2) CLEARLY INDICATE SOUCE OF FUEL AS PLANS, MORE
 SPECIFICALLY SHEET E-1 SEEMS TO SUGGEST (2) SEPARATE
 GENERATORS AND PERMIT APPLICATION MENTIONS (1).
  
 3) IN ADDITION TO ALL OTHER APPLICABLE CODES, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 4) CLEARLY INDICATE THE LOCATION OF EXHAUST TERMINUS
 RELATIVE TO BUILDING OPENINGS AND MEANS OF EGRESS.
  
 5) INDICATE WHAT SPECIFIC BUILDING AND LIFE SAFETY
 EQUIPMENT WOULD BE POWERED BY GENERATOR(S) SHOULD IT
 BECOME NECESSARY AS A RESULT OF POWER LOSS.
  
 6) IN ADDITION TO NFPA 704 PLACARDING, NO SMOKING SIGNS
 ARE REQUIRED IN AREA OF FUEL SOURCE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2008-07-02 Cont ID  
Sent By tgordon Date 2008-07-02 Time 15:36 Rev Time 0.10
Received By tgordon Date 2008-07-02 Time 15:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-07-07 Cont ID  
Sent By mperson Date 2008-07-07 Time 16:10 Rev Time 0.00
Received By mperson Date 2008-07-07 Time 16:10 Sent To  
Notes
2008-07-07 16:39:40GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. SHEETS E-1, E-3, AND E-6 ARE INDICATING AN 85KW
 NATURAL GAS EMERGENCY GENERATOR, HOWEVER THERE IS NO
 ISOMETRIC NATURAL GAS RISER DIAGRAM SUBMITTED OR GAS
 PERMIT APPLICATION THAT HAS BEEN APPLIED FOR.
  
 CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL
 GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL GEN/COM
 INSPECTION.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 NOTE: THE FOLLOWING INFORMATION IS REQUIRED ON THE
 NATURAL GAS ISOMETRIC RISER DIAGRAM PER THE CITY OF
 WEST PALM BEACH GAS PERMIT APPLICATION REQUIREMENTS:
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS. PER
 FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE.
  
 3. CLEARLY SHOW THE TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH NUMBER OF
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE
 BEING USED. PER FBC-2004 FUEL GAS CODE SECTION 401.1
 SCOPE.
  
 4. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL).
 PER FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE.
  
 5. INDICATE THE BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2004
 FUEL GAS CODE SECTIONS 401.8 THRU 402.6.1 AND TABLES
 402.4(1) THRU 402.4(33).
  
 6. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SECTION 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 THE FBC-2004 FUEL GAS CODE SECTION 402.2.
 NOTE: IF THE NATURAL GAS SYSTEM DELIVERY PRESSURE IS 2
 PSI PLEASE SUBMIT TWO COPIES OF MANUFACTURE SHEETS FOR
 THE MP REGULATOR CLEARLY INDICATING ITS MAKE, MODEL
 NUMBER, BTU LOAD CAPACITY, AND A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY.
  
 10. NOTE: ALL PLANS (NATURAL GAS ISOMETRIC RISER
 DIAGRAM), SPECIFICATIONS, AND ACCOMPANYING DATA BEING
 FILED FOR PUBLIC RECORD SHALL CONTAIN THE PRINTED NAME
 OF THE RESPONSIBLE PERSON WITH THE ORIGINAL SIGNATURE
 AND DATE ON SUCH INFORMATION. PER SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-30 Cont ID  
Sent By mwennerg Date 2008-07-30 Time 14:28 Rev Time 0.00
Received By mwennerg Date 2008-07-01 Time 11:30 Sent To  
Notes
2008-07-01 11:30:55TO "COMM" BD#8

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-07-02 Cont ID  
Sent By tgordon Date 2008-07-02 Time 15:36 Rev Time 0.30
Received By tgordon Date 2008-07-02 Time 15:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-07-14 Cont ID  
Sent By kdfreema Date 2008-07-14 Time 08:18 Rev Time 0.00
Received By kdfreema Date 2008-07-14 Time 08:18 Sent To  
Notes
2008-07-14 08:19:06***FAILED***
  
 1. THE PROPOSED 8 FOOT SCREEN WALL IS OF INSUFFICIENT
 HEIGHT TO SCREEN THE GENERATOR. INCREASE THE HEIGHT OF
 THE PROPOSED SCREEN WALL TO 13 FEET.
  
 2. SHRUBS AND HEDGES PLANTED AT TWO FOOT INTERVALS MUST
 BE PLANTED AROUND THE EXTERIOR OF THE PROPOSED
 ENCLOSURE. ENSURE THAT THE PLACEMENT OF LANDSCAPING IS
 COORDINANTED WITH THE PLACEMENT OF THE PROPOSED
 GUARDRAILS.
  
 3. PLEASE SHOW THE PROPOSED GENERATOR IN THE CONTEXT OF
 ITS SURROUNDINGS. PLEASE SHOW THE EXISTING PARKING
 SPACES WHICH ARE TO REMAIN INCLUDING THOSE ON THE WEST
 SIDE OF THE DRIVE AISLE. MAKE SURE DIMENSIONS ARE
 PROVIDED SHOWING THE WIDTH OF THE DRIVE AISLE AS WELL
 AS THE PARKING SPACES.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR [email protected] WITH QUESTIONS.