| 2008-07-07 09:46:11 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. THE SUBMITTED PRODUCT APPROVALS FOR THE SUNSTAR |
| | SOLAR COLLECTOR, HELIOCOL ARE EXPIRED AS OF 9/12/97. AN |
| | ONLINE SEARCH OF SAID PRODUCT APPROVALS BY THIS PLANS |
| | EXAMINER CAME UP WITH "THERE ARE NO RECORDS THAT MATCH |
| | THE SEARCH CRITERIA". PLEASE SUBMIT TWO COPIES OF |
| | UPDATED PRODUCT APPROVALS. |
| | |
| | 2. SHEET S-1, THE ENGINEERED ANCHORING OF THE "SUN |
| | STAR" COLLECTORS IS EXPIRED. SHEET S-1 INDICATES PER |
| | 2001 FLORIDA BUILDING CODE. THE CORRECT CODE CYCLE IS |
| | 2004 FLORIDA BUILDING CODES WITH 2007 REVISIONS. PLEASE |
| | PROVIDE TWO COPIES OF UPDATED ENGINEERED ANCHORING |
| | DETAILS WITH THE CORRECT CODE CYCLES AND COMPLIANT TO |
| | MEET THE 140 MPH WIND LOAD PER FBC-2004 BUILDING |
| | CHAPTER 16, SECTION 1603.1.4 WIND DESIGN DATA AND |
| | SECTION 1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT |
| | AND SLIDING.. |
| | |
| | 3. SHEET S-1 ALSO INDICATES A PHOTO COPY OF THE |
| | ENGINEER'S SEAL, DATE AND SIGNATURE. PER |
| | FAC-61G15-23.002 SEAL SIGNATURE AND DATE SHALL BE |
| | AFFIXED: EACH SHEET OF PLANS AND PRINTS WHICH MUST BE |
| | SEALED UNDER PROVISIONS OF CHAPTER 471 SHALL BE SEALED, |
| | SIGNED AND DATED BY THE PROFESSIONAL ENGINEER IN |
| | RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. |
| | IF |
| | PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING |
| | BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME |
| | LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND |
| | CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGNEERING |
| | BUSINESS ON EACH SHEET. |
| | |
| | 4. THE SUBMITTED "GOOGLE 2008 TELE ATLAS" OF 3800 |
| | WASHINGTON ROAD, PORTOFINO SOUTH WITH THE SOLAR |
| | COLLECTORS INDICATED ON THE ROOF NEEDS MORE |
| | INFORMATION. PLEASE PROVIDE A SCHEDULE WITH THE PIPE |
| | SIZES, THE EXACT NUMBER OF SOLAR COLLECTORS, OR CLEARLY |
| | IDENTIFY THE COLLECTORS AND PIPE SIZES ON THE DRAWING. |
| | PER FBC-2004 MECHANICAL SECTION 1401.1 SCOPE. |
| | |
| | 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, |
| | THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, |
| | SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA |
| | STATUTES 481 AND 471 RESPECTIVELY. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |