| 2008-06-27 13:36:03 | RESIDENTIAL (R3)SHUTTERS INSTALLATION BUILDING REVIEW |
| | CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- PROVIDE 2 COPIES OF EVERYTHING: PRODUCT APPROVALS |
| | FOR STORM PANELS,ACCORDION SHUTTERS AND KEY PLANS AS |
| | REQUIRED BY SEC. 106.1 CITY AMENDMENTS TO FBC 2004. |
| | ONLY ONE COPY WAS SUBMITTED. |
| | |
| | 2- PROVIDE COMPLETE PRODUCT APPROVAL FOR THE ACCORDION |
| | SHUTTERS. MISSING THE COVER PAGES OF FLORIDAPRODUCT |
| | APPROVAL.GO TO WWW.FLORIDABUILDING.ORG AND DOWNLOAD |
| | FLORIDA PRODUCT APPROVAL THAT CORRESPONDS TO DRAWINGS |
| | SUBMITTED. |
| | |
| | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE SUBMITTED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 4-A) PROVIDE COMPLETE INSTALLATION SCHEDULE(NOTE: |
| | PLEASE,IDENTIFY WHICH OPENING IS GOING TO HAVE STORM |
| | PANELSOR ACCORDION SHUTTERS)AS REQUIRED BY CITY'S |
| | IMPLEMENTATION STANDARD FOR WIND-BORNE DEBRIS IMPACT |
| | PROTECTION.SEE ATTACHED SAMPLE.ANOTHER METHOD MAY |
| | BE USED, BUT ALL THE INFORMATION SHOWN ON THE ATTACHED |
| | SAMPLE SHALL BE PROVIDED. |
| | |
| | B) CLEARLY MARK ON SHUTTER DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS TO BE USED (EG: WALL MOUNTED OR |
| | BUILT OUT MOUNT) AND SPECIFIC ANCHOR TYPE AND SPACING |
| | TO BE USED ACCORDING TO THE OPENING DESIGN PRESSURES, |
| | PANEL SPAN, EDGE DISTANCE, CONNECTION TYPE AND |
| | STRUCTURE TO BE ATTACHED TO (CONCRETE OR CONCRETE |
| | BLOCK, WOOD).SEC. 106.1.2 CITY AMENDMENTS TO VERIFY |
| | COMPLIANCE WITH PRODUCT APPROVAL INSTALLATION AND |
| | DESIGN PRESSURES OF SEC. R301. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |