| 2008-07-16 11:51:56 | BUILDING PLAN REVIEW |
| | PERMIT: 08060789 |
| | ADD: 400 N. FLAGLER DR. #2102 |
| | CONT: A.D. SABA ENTERPRISES |
| | TEL: (561)969-2920 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 3)THE DESIGN PROFESSIONAL SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE TO THE DRAWINGS PER |
| | FLORIDA STATUTES 481.221(1) |
| | |
| | 4)AN ENGINEER SHALL PROVIDE THE CALCULATION FOR THE |
| | DESIGN PRESSURE OF THE NEW DOOR DUE TO THE FACT THAT |
| | THE BUILDING IS OVER 60 FEET. ON THE PRODUCT APPROVAL; |
| | CIRCLE OR HI-LIGHT ALL INFORMATION PERTAINING TO THE |
| | DOOR INCLUDING THE WIDTH OF THE PANELS AND THE DOOR |
| | HEIGHT. DESIGN PRESSURES FOR BUILDINGS OVER 60FEET ARE |
| | REQUIRED TO BE DESIGNED USING ASCE7, FBC1609.1.1 AND |
| | MUST BE DONE BY AN ENGINEER. DOCUMENTS PREPARED BY AN |
| | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| | SIGNED SEALED ORIGINALS FAC61G15-23.002. |
| | |
| | 5)1714.5.1 THE DESIGN PRESSURE FOR WINDOW AND DOOR |
| | ASSEMBLIES SHALL BE CALCULATED IN ACCORDANCE WITH |
| | COMPONENTS AND CLADDING WIND LOAD IN FBC 1609 |
| | |
| | 6)INDICATE HOW THE NEW DOOR WILL BE ATTACHED TO THE |
| | STRUCTURE OF THE BUILDING. DOOR AND WINDOW BUCKS SHALL |
| | EXTEND BEYOND THE INTERIOR FACE OF THE FRAME SUCH THAT |
| | FULL SUPPORT OF THE FRAME IS PROVIDED. WHERE THE WOOD |
| | BUCK THICKNESS IS 1 ? INCHES OR GREATER, THE BUCK SHALL |
| | BE SECURELY FASTENED TO TRANSFER LOAD TO THE MASONRY, |
| | CONCRETE OR THE OTHER STRUCTURAL SUBSTRATE AND THE BUCK |
| | SHALL EXTEND BEYOND THE INTERIOR FACE OF THE DOOR |
| | FRAME. PROVIDE THE NEW DOOR BUCK DETAIL. FBC |
| | 1714.5.4.2. |
| | |
| | 7)IS THE PATIO FLOOR AND THE EXISTING BEDROOM FLOOR |
| | ON THE SAME LEVEL? IF NOT, WILL THE CONTRACTOR BUILD UP |
| | THE PATIO FLOOR TO MAKE IT EVEN WITH THE EXISTING |
| | BEDROOM FLOOR? IF THIS IS THE CASE INDICATE AND SHOW |
| | WHAT MATERIALS WILL BE USED TO ACHIEVE A LEVEL FLOOR. |
| | PROVIDE DETAIL DRAWINGS TO SHOW COMPLIANCE. ADDITIONAL |
| | INFORMATION IS REQUIRED 106.1.2* |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| | |