Plan Review Details - Permit 08060706
Plan Review Stops For Permit 08060706
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-09-10 Cont ID  
Sent By jwitmer Date 2009-09-10 Time 12:54 Rev Time 0.50
Received By jwitmer Date 2009-09-10 Time 12:30 Sent To  
Notes
2009-09-10 12:58:03REVISIONS DATED: 8/28/09
 A101
 A102
 A103
 A201
 A501
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-09-10 Cont ID  
Sent By jwitmer Date 2009-09-10 Time 11:33 Rev Time 0.25
Received By jwitmer Date 2009-09-10 Time 11:33 Sent To  
Notes
2009-09-10 11:33:50ENGINEERING LETTER DATED 8/28/09

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-12-12 Cont ID  
Sent By mjacobs Date 2008-12-12 Time 08:24 Rev Time 0.00
Received By mjacobs Date 2008-12-12 Time 08:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-10-22 Cont ID  
Sent By jwitmer Date 2008-10-22 Time 09:43 Rev Time 1.55
Received By jwitmer Date 2008-10-22 Time 09:42 Sent To  
Notes
2008-10-22 09:45:16PLANS ARE CODE COMPLIANT, NEEDS A CONTRACTOR TO SIGN ON
 AND PERMIT APPLICATION AND ASSOCIATED FEES PAIDBEFORE
 PLANS CAN BE SHOW A PASSED REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-22 Cont ID  
Sent By jwitmer Date 2008-10-22 Time 08:25 Rev Time 1.77
Received By jwitmer Date 2008-10-22 Time 08:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-09-11 Cont ID  
Sent By jwitmer Date 2008-09-11 Time 10:29 Rev Time 2.22
Received By jwitmer Date 2008-09-11 Time 10:29 Sent To  
Notes
2008-09-11 11:30:11BUILDING PLAN REVIEW
 PERMIT: 08060706 PLAN REVIEW/MAJOR WORKING DRAWINGS
 ADD: 600 S. ROSEMARY AVE. PH 03
 CONT: BERGMEYER ASSOCIATES
 TEL: (617)695-7759
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 SEPT. 11,2008
  
 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B) NOT APPLICABLE.
  
 1C) PLEASE SEE COMMENT # 3 SITED CODE. 106.1.1* W.P.B.
 ADMINISTRATIVE CODE/2004 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E-G) COMPLIED.
  
 2) COMPLIED.
  
 3) 2ND REQUEST, AS STATED ABOVE 106.1.1 SUCH
 INFORMATION SHALL BE SPECIFIC TO THE TECNICAL CODE,
 CODE CAN NOT BE REPEATED AS SATISFYING THE CODE ISSUE.
 THIS IS MISSING WIND INFORMATION NEEDED TO BE ABLE TO
 COMPLETE THE REVIEW. TO DATE THE DESIGNER OF RECORD HAS
 NOT PROVIDED WIND INFORMATION NOR PRESSURES FOR
 COMPONENTS AND CLADDING. SHEET AD-101 INDICATES THE
 REMOVAL OF THE STOREFRONT SYSTEM AND A401 & A402
 INDICATE VARIOUS DETAILS OF THE NEW STOREFRONT SYSTEM
 BUT NO WIND DESIGN INFORMATION IS INDICATED WWITHIN THE
 PLANS: 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 4) 2ND REQUEST, SUBMITTED WERE TWO DIFERENT SETS
 OFPRODUCTS, (2) PGT PRODUCTS & (2) KAWNEER:
 PGT NOA 07-0817.04 SERIES "IR-500" ALUMINIUM GLAZING (W
 SOLUTIA/ DUPONT'S PVB) WINDOW WALL
 PGT NOA 06-0309.01 SERIES "IR-500" ALUMINIUM GLAZED (W/
 STORM GUARD) WINDOW WALL SYSTEM
  
 KAWNEER NOA 04-0123.01 SERIES "IR 500" GLAZED WALL
 -IMPACT NOTE THE MAXIMUM SPACING FOR GLAZED UNITS IS
 48" SEE SHEET 1OF 8.
 KAWNEER NOA 040123.02 SERIES 350 OUTSWING STOREFRONT
 DOOR W/IR 500 FRAMING SYSTEM
  
 PLEASE NOTE THAT ALSO SUBMITTED WAS A COVERSHEET FOR
 KAWNEER IR500/501 FRAMING AND SUPPOSED SHOP DRAWINGS
 THAT ARE ONLY ENLARGED TECHNICAL SHEETS FROM THE
 KAWNEER 07-0817.04 NOA.
 PLEASE REMOVE SETS OF PRODUCT APPROVALS NOT TO BE
 REVIEWED FOR CODE COMPLIANCE.
  
 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 4A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 4A)(1) STOREFRONT NOA SUBMITTED IS NOT ONE LISTED ON
 STATE WEB-SITE THER ARE 3 IR500 REPORTS LISTED.
 4A)(2) GLAZED EXTERIOR SWING DOORS
 4A)(3) MULLIONS-VERTICAL
  
 4B) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5) SHEET A402 DETAIL# 4 INDICATES AN EXTERIOR MALL
 WALKWAY, THIS IS THE EXTERIOR OFTHE BUILDING AND NOT
 LOCATED WITHIN A MALL, PLEASE INDICATE HOW THIS
 INSTALLATION WILL MAKE A WATERTIGHT SEAL.
 1403.2. WEATHER PROTECTION. EXTERIOR WALLS SHALL
 PROVIDE THE BUILDING WITH A WEATHER-RESISTANT EXTERIOR
 WALL ENVELOPE. THE EXTERIOR WALL ENVELOPE SHALL INCLUDE
 FLASHING, AS DESCRIBED IN SECTION 1405.3 .
 1405.3 FLASHING.
 FLASHING SHALL BE INSTALLED IN SUCH A MANNER SO AS TO
 PREVENT MOISTURE FROM ENTERING THE WALL OR TO REDIRECT
 IT TO THE EXTERIOR. FLASHING SHALL BE INSTALLED AT THE
 PERIMETERS OF EXTERIOR DOOR AND WINDOW ASSEMBLIES,
 PENETRATIONS AND TERMINATIONS OF EXTERIOR WALL
 ASSEMBLIES, EXTERIOR WALL INTERSECTIONS WITH ROOFS,
 CHIMNEYS, PORCHES, DECKS, BALCONIES AND SIMILAR
 PROJECTIONS AND AT BUILT-IN GUTTERS AND SIMILAR
 LOCATIONS WHERE MOISTURE COULD ENTER THE WALL. FLASHING
 WITH PROJECTING FLANGES SHALL BE INSTALLED ON BOTH
 SIDES AND THE ENDS OF COPINGS, UNDER SILLS AND
 CONTINUOUSLY ABOVE PROJECTING TRIM.
  
 6) 2ND REQUEST, SHEET A401DETAIL# 2 INDICATES A
 STOREFRONT FRAME, PLEASE PROVIDE A CUT SECTION THROUGH
 THE STOREFRONT FRAME AND DOOR FRAME, THIS IS WHERE IT
 WOULD APPEAR A VERTICAL MULLION WOULD BE REQUIRED,
 PLEASE PROVIDE ADDITIONAL INFORMATION HOW THE WIND
 LOADS WILL BE MET IN 1609.6.2.2. COMPONENTS AND
 CLADDING.
  
 7) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-08 Cont ID  
Sent By jwitmer Date 2008-07-08 Time 15:33 Rev Time 3.33
Received By jwitmer Date 2008-07-08 Time 15:33 Sent To  
Notes
2008-07-08 16:46:08BUILDING PLAN REVIEW
 PERMIT: 08060706 PLAN REVIEW/MAJOR WORKING DRAWINGS
 ADD: 600 S. ROSEMARY AVE. PH 03
 CONT: BERGMEYER ASSOCIATES
 TEL: (617)695-7759
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS, NOTE
 GOO1 CODE SUMMARYDOES NOT INDICATE THE 2007 SUPPLEMENTS
 NOR THE 2004 EXISTING BUILDING CODE.
  
 1F) PLANS FAIL TO INDICATE TO WHAT LEVEL ALTERATION THE
 DESIGNER AND OR OWNER HAVE ELECTED TO REMODEL OR
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO SECTION
 303, 304 AND 305 OF THIS CODE. SEE SECTION 301.5 /2004
 FBC EXISTING BUILDING CODE.
  
 SHEET G001 HEADING FIRE RESISTANCE SEPERATION, TENANT
 SEPERATION- INDICATES TABLE602, PLEASE CORRECT TO
 708.1( 5) WALLS SEPERATING INDIVIDUAL TENANT SPACES,
 708.3 FIRE-RESISTANCE RATING OF THE WALLS SHALL BE AT
 LEAST 1 HR.
  
 2) NOTE: SHEET A401 AND A402 INDICATE SIGNAGE AND
 AWNINGS. BOTH REQUIRE SEPERATE PERMITS, AND NOT COVERED
 UNDER THIS PERMIT. NOTE AWNINGS ARE TO MEET THE SHEET
 A402 DETAIL# 2 INDICATES A 7'-6" AWNING WITH A 8" DROP
 FRONT OR FINISHED HEIGHT OF 6'-10". SECTION 3105.1.1.1
 NO PART OF THE CLOTH DROP SHALL BE LESS THAN 7
 FEET.WIND DESIGNS MUST MEET ONE OF THE WIND SCENARIOS
 OF 3105.2.
  
 3) SHEET AD-101 INDICATES THE REMOVAL OF THE STOREFRONT
 SYSTEM AND A401 & A402 INDICATE VARIOUS DETAILS OF THE
 NEW STOREFRONT SYSTEM BUT NO WIND DESIGN INFORMATION IS
 INDICATED WWITHIN THE PLANS: 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3.
 WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 4) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 4A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 4A)(1) STOREFRONT NOA SUBMITTED IS NOT ONE LISTED ON
 STATE WEB-SITE THER ARE 3 IR500 REPORTS LISTED.
 4A)(2) GLAZED EXTERIOR SWING DOORS
 4A)(3) MULLIONS-VERTICAL
  
 4B) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4C) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) SHEET A402 DETAIL# 4 INDICATES AN EXTERIOR MALL
 WALKWAY, THIS IS THE EXTERIOR OFTHE BUILDING AND NOT
 LOCATED WITHIN A MALL, PLEASE INDICATE HOW THIS
 INSTALLATION WILL MAKE A WATERTIGHT SEAL.
 1403.2. WEATHER PROTECTION. EXTERIOR WALLS SHALL
 PROVIDE THE BUILDING WITH A WEATHER-RESISTANT EXTERIOR
 WALL ENVELOPE. THE EXTERIOR WALL ENVELOPE SHALL INCLUDE
 FLASHING, AS DESCRIBED IN SECTION 1405.3 .
 1405.3 FLASHING.
 FLASHING SHALL BE INSTALLED IN SUCH A MANNER SO AS TO
 PREVENT MOISTURE FROM ENTERING THE WALL OR TO REDIRECT
 IT TO THE EXTERIOR. FLASHING SHALL BE INSTALLED AT THE
 PERIMETERS OF EXTERIOR DOOR AND WINDOW ASSEMBLIES,
 PENETRATIONS AND TERMINATIONS OF EXTERIOR WALL
 ASSEMBLIES, EXTERIOR WALL INTERSECTIONS WITH ROOFS,
 CHIMNEYS, PORCHES, DECKS, BALCONIES AND SIMILAR
 PROJECTIONS AND AT BUILT-IN GUTTERS AND SIMILAR
 LOCATIONS WHERE MOISTURE COULD ENTER THE WALL. FLASHING
 WITH PROJECTING FLANGES SHALL BE INSTALLED ON BOTH
 SIDES AND THE ENDS OF COPINGS, UNDER SILLS AND
 CONTINUOUSLY ABOVE PROJECTING TRIM.
  
 6) SHEET A401DETAIL# 2 INDICATES A STOREFRONT FRAME,
 PLEASE PROVIDE A CUT SECTION THROUGH THE STOREFRONT
 FRAME AND DOOR FRAME, THIS IS WHERE IT WOULD APPEAR A
 VERTICAL MULLION WOULD BE REQUIRED, PLEASE PROVIDE
 ADDITIONAL INFORMATION HOW THE WIND LOADS WILL BE MET
 IN 1609.6.2.2. COMPONENTS AND CLADDING.
  
 7) SHEET A402 DETAIL# 4 INDICATES THE USE OF STEEL
 STUDS, THIS WALL IS AN EXTERIOR WALL REQUIRED TO RESIST
 WIND PRESSURE PLEASE PROVIDE THE DESIGN CRITERIA FOR
 THE BEARING STUDS, (WIND) SIZE OF STUD, GAUGE OF STUD,
 AND THE SPACING REQUIREMENTS. 2508 , GA-216 OR ASTM C
 1007.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2009-10-08 Cont ID  
Sent By dpalmer Date 2009-10-08 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2009-10-08 Time 19:11 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2009-09-24 Cont ID  
Sent By dpalmer Date 2009-09-24 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2009-09-24 Time 11:32 Sent To PC
Notes
2009-09-24 11:33:16** REDLINED PLANS **
  
  
  
 1) NOTE: PREVIOUS PLANS CONTAINED A 50AMP BREAKER FOR
 THE 30KVA TRANSFORMER WHICH WAS OK. THE REVIEW COMMENT
 HAD TO DO WITH THE INCORRECT CONDUCTOR SIZES.
 THE OVER CURRENT PROTECTION FOR THE SAME 30 KVA
 TRANSFORMER HAS NOW BEEN REVISED FROM THE PREVIOUS
 PLANS AND DOES NOT MEET 450.3B. THE MAXIMUM OCP FOR
 THIS SIZE TRANSFORMER IS 125%.
 THE 125% COMES OUT TO JUST OVER 45AMPS. HOWEVER IT IS
 PERMISSIBLE TO GO UP TO 50AMPS.
 A 45AMP OR 50AMP BREAKER IS PERMITTED HOWEVER 60AMP IS
 TOO HIGH.
 IF TRANSFORMER MEETS NOTE #3 ON TABLE THEN IT WOULD BE
 OK, HOWEVER THE TRANSFORMER ONSITE WOULD HAVE TO MEET
 *ALL* OF NOTE #3 OF 450.3B TABLE NOTES.
  
 ** PLANS MAY BE REVISED BY SUBMITTED A SMALLER VERSION
 OF THE PANEL SCHEDULE WITH THE CORRECT OCP AND
 CONDUCTORS ON 8 ?? BY 11 SHEETS. STILL REQUIRED TO
 CONTAIN TITLE BLOCKS, SIGNATURE, DATE AND SEAL PER FAC
 61G15-23.002, FS 471.025
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2009-09-11 Cont ID  
Sent By dpalmer Date 2009-09-11 Time 10:09 Rev Time 0.00
Received By dpalmer Date 2009-09-11 Time 10:09 Sent To  
Notes
2009-09-11 10:09:19** DENIED **
  
  
 1) NOTE: TRANSFORMER ON ORIGINAL PLANS STATED 15K AND
 REVISED IS NOW 30K.
 PLEASE COORDINATE RISER AND 277/480 PANEL. RISER
 INDICATES #6 CONDUCTORS TO TRANSFORMER HOWEVER PANEL
 SCHEDULE INDICATES #12. PER 240.21,240.4,310.16 #12 AWG
 IS NOT LARGE ENOUGH.
  
 2) NOTE: REVISION NOW HAS TRANSFORMER BEING RELOCATED.
 THE NEW LOCATION APPEARS TO SHOW THE TAPPED CONDUCTORS
 EXCEEDING THE LIMITS OF 240.21.
 THE TAPPED CONDUCTOR RULE IS 10FT OF CONDUCTORS. PLEASE
 REVISE BY ADDING A DISCONNECTING MEANS WITH OVER
 CURRENT PROTECTION, OR RELOCATE. IF ACTUAL TAPPED
 CONDUCTOR LENGTH IS 10FT OR LESS PROVIDE THIS ON PLANS.
 BASED ON SCALE OF PLANS THIS IS NOT POSSIBLE WITH THE
 LOCATION SHOWN.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-12-16 Cont ID  
Sent By dpalmer Date 2008-12-16 Time 15:32 Rev Time 0.00
Received By dpalmer Date 2008-12-16 Time 15:32 Sent To  
Notes
2008-12-17 16:06:55ELEC SHEET STAMPED BY VICKI FOR CARLOS BERNAL WITH
 RESPECT TO CITY PLACE STAMP.
2008-12-16 15:32:39** TEMPORARY FAILED **
  
 1) NOTE: NEW SHEET E-102 WAS NOT IN 2ND SET. INSERTED
 BY THIS OFFICE HOWEVER SHEET DID NOT CONTAIN CITY PLACE
 MANAGEMENT STAMP AS REQUIRED.
 IF OK WITH CITY PLACE UNSTAMPED COPY WILL GO OUT WITH
 CONTRACTORS FILE SET.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-10-28 Cont ID  
Sent By dpalmer Date 2008-10-28 Time 16:47 Rev Time 0.00
Received By dpalmer Date 2008-10-28 Time 16:47 Sent To PC
Notes
2008-10-28 16:48:01 
  
 ** DENIED REVIEW**
  
  
  
 1) NOTE: PLANS STILL ONLY SUBMITTED FOR PLAN REVIEW AND
 NOT FOR PERMIT APPLICATION.
  
 2) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1,
 .1.2 .
 ** PLEASE BE SURE TO LOOK AT SECTIONS NOTED ESPECIALLY
 FOR TRACK LIGHTING.
 PLEASE SEE THE LIGHTING SHALL BE BASED ON THE WATTAGE
 OF THE FIXTURES OR THE MINIMUM 30VA PER FT OF TRACK
 WHICH EVER IS GREATER.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-09-12 Cont ID  
Sent By dpalmer Date 2008-09-12 Time 16:39 Rev Time 0.00
Received By dpalmer Date 2008-09-12 Time 16:39 Sent To  
Notes
2008-09-12 16:39:47 
 ** DENIED 2ND REVIEW **
  
 1) NOTE: PLANS STILL ONLY SUBMITTED FOR PLAN REVIEW AND
 NOT FOR PERMIT APPLICATION.
  
 2) NOTE: PLEASE SEE FBC 13-415.2, 13-415.2.ABC.1.1,
 .1.2 . THE SUBMITTED METHOD*C* CALCULATIONS ARE NOT
 COMPLETE AND DO NOT COMPLY WITH THE CODE SECTIONS AS
 NOTED. THE TOTAL EFFECTIVE WATTAGE SHOWN AS 631 IS NOT
 POSSIBLE AS THE DISPLAY OR ACCENT LIGHTING IN THIS
 OCCUPANCY UNDER THE CONTROLS WHICH ARE SHOWN ARE NOT
 EXEMPT.
 PLEASE MEET PRESCRIPTIVE REQUIREMENTS. IT WAS NOTED IN
 NOTE #7 ON PREVIOUS REVIEW.
 ** PLEASE BE SURE TO LOOK AT SECTIONS NOTED ESPECIALLY
 FOR TRACK LIGHTING.
 ** BASED ON THE WATTAGE NUMBERS AT THIS TIME THE
 LIGHTING IS SHOWN AS THREE TIMES OVER THE ALLOWANCE AS
 METHOD *C*.
  
 3) NOTE: DOCUMENTS SUBMITTED WITH NOT SIGNED, DATED,
 SEALED OR CERTIFIED IN ANY MANOR. THIS WAS NOTE #2 ON
 PREVIOUS REVIEW.
  
 ** PREVIOUS REVIEW NOTE #2.
 PLEASE SEE THE CERTIFICATION SHEET SUBMITTED PAGE 3
 INDICATES A PERSON PREPARING DOCUMENTS OTHER THAN THE
 ENGINEER OF RECORD. THIS IS NOT PERMITTED. PLEASE BE
 SURE THE CERTIFICATION SHEET IS SIGNED, DATED AND
 SEALED.
 FBC 13-103.1, FAC 61G15-23.002, FS 471.025
  
 4) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** SAME AS PREVIOUS REVIEW. PLEASE SEE ELECTRICAL PLANS
 ONLY STATE TO COMPLY WITH CODES AND DO NOT LIST THE
 ABOVE AS NOTED.
 ** PLANS HAVE BEEN SUBMITTED FOR PLAN REVIEW ONLY AND
 HAVE NOT BEEN SUBMITTED FOR PERMIT APPLICATION.
  
  
 5) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FLORIDA STATUTES 481.219 FOR REQUIRED
 INFORMATION ON TITLE BLOCKS WHICH IS MISSING FROM ALL
 SHEETS FOR THE ARCHITECTURAL FIRM.
 MISSING PRINTED NAME.
 MISSING PRINTED LICENSE NUMBER
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADE
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
  
  
 6) NOTE: ** SAME AS PREVIOUS REVIEW**
 PLEASE SEE ELECTRICAL PLANS SEEMED TO BE SIGNED WITH AN
 INITIAL OF SOME KIND. IF THIS IS INDEED THE LEGAL
 SIGNATURE PLEASE PROVIDE A SIGNATURE VERIFICATION
 LETTER SIGNED, DATED, SEALED AND NOTARIZED. THIS WILL
 BE PLACED IN SIGNATURE FILE FOR FUTURE REFERENCE.
 FS 471.025
  
 7) NOTE: PLEASE SEE MISSING AUTOMATED LIGHTING CONTROLS
 PER 13-415.1.ABC.1.1, .1.2 AND.1.3 PLEASE PROVIDE MORE
 DETAIL ON THE SYSTEM, THE DEVICES, MAXIMUM TIMES, TIMED
 SCHEDULING, OVER RIDES ETC.
  
 9) NOTE: ** THIS IS THE SAME NOTE FROM PREVIOUS REVIEW
 IN FACT THE RISER WAS CHANGED TO NOW SHOW THE BREAKER
 IN PANEL *A* AS 60AMP MCB YET THE PANEL SCHEDULE STILL
 SHOWS 100AMPS. THIS DOES NOT MEET MINIMUM REQUIRED IN
 THE NEC.
 SECTIONS AS NOTED PREVIOUSLY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER SHOWS EXISTING #4 ON THE SECONDARY
 SIDE OF THE TRANSFORMER. PLEASE SEE 240.21, 310.16,
 240.4, AND 240.6 AS THIS SIZE CONDUCTOR DOES NOT MEET
 ANY OF THESE SECTIONS. THIS IS A FIRE AND LIFE SAFETY
 HAZARD AND EVEN IF EXISTS THE CONDUCTOR SIZE SHALL MEET
 THE MINIMUM FOR CODE COMPLIANCE.
 PLEASE ADJUST.
  
 10) NOTE: AS NOTED PREVIOUSLY PLEASE COMPLETE PANEL
 SCHEDULES WITH ALL CONDUCTORS AND OVER CURRENT
 PROTECTION.
 408.4, 310.16, 240.4, 450.3 ETC.
 FBC 106.1.1 FOR CLARITY AND 106.1.2 FOR ADDITIONAL
 INFORMATION
  
  
 ** PLEASE KNOW AS PLANS ARE NOT COMPLETE WITH
 INFORMATION ABOVE AT THIS TIME, WHEN PLANS COME BACK
 WITH THE INFORMATION NEW COMMENTS MAY BE PART OF THE
 REVIEW.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-17 Cont ID  
Sent By dpalmer Date 2008-07-17 Time 16:49 Rev Time 0.00
Received By dpalmer Date 2008-07-17 Time 16:49 Sent To  
Notes
2008-07-17 16:49:32** DENIED **
  
 ** PLANS HAVE BEEN SUBMITTED FOR PLAN REVIEW ONLY AND
 HAVE NOT BEEN SUBMITTED FOR PERMIT APPLICATION.
  
  
 1) NOTE: PLEASE SEE FBC 13-400.3.A, 13-400.3.B,
 13-400.3.C. THE VERSION REQUIRED AND AS ADOPTED PER
 SECTION GIVEN SHALL BE 2.5. PLEASE KNOW IT IS THE
 UNDERSTANDING OF THIS OFFICE THERE IS A PATCH AVAILABLE
 ON THE ENERGY GAUGE WEBSITE WHICH WILL PROVIDE THE 2.5
 VERSION AS REQUIRED.
  
  
 2) NOTE: PLEASE SEE THE CERTIFICATION SHEET SUBMITTED
 PAGE 3 INDICATES A PERSON PREPARING DOCUMENTS OTHER
 THAN THE ENGINEER OF RECORD. THIS IS NOT PERMITTED.
 PLEASE BE SURE THE CERTIFICATION SHEET IS SIGNED, DATED
 AND SEALED.
 FBC 13-103.1, FAC 61G15-23.002, FS 471.025
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 4) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FLORIDA STATUTES 481.219 FOR REQUIRED
 INFORMATION ON TITLE BLOCKS WHICH IS MISSING FROM ALL
 SHEETS FOR THE ARCHITECTURAL FIRM.
 MISSING PRINTED NAME.
 MISSING PRINTED LICENSE NUMBER
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADE
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
  
  
 5) NOTE: PLEASE SEE FAC 61G15-23.002 AND FS 471.023 FOR
 MISSING INFORMATION FROM THE TITLE BLOCKS FOR
 ENGINEERING FIRM.
 MISSING PRINTED NAME.
 MISSING PRINTED LICENSE NUMBER
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 6) NOTE: PLEASE SEE ELECTRICAL PLANS SEEMED TO BE
 SIGNED WITH AN INITIAL OF SOME KIND. IF THIS IS INDEED
 THE LEGAL SIGNATURE PLEASE PROVIDE A SIGNATURE
 VERIFICATION LETTER SIGNED, DATED, SEALED AND
 NOTARIZED. THIS WILL BE PLACED IN SIGNATURE FILE FOR
 FUTURE REFERENCE.
 FS 471.025
  
 7) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 ARE MISSING THE INPUT DATA REPORT. SEE PAGE 2 WHICH
 SPECIFICALLY STATES THE INPUT DATA REPORT MUST
 ACCOMPANY SUMMARY OF CALCULATIONS.
 PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3 FOR MISSING
 REQUIRED PERFORMANCE CALCULATIONS AND VERIFICATION TO
 BE SUBMITTED ON CALCULATIONS.
 PLEASE BE SURE TO SEE SECTIONS ABOVE IN SPECIFIC TO
 MINIMUM REQUIRED SHALL BE BASED ON FIXTURE NOT BULB
 WATTAGE.
 PLEASE BE SURE TO ALSO SEE THE SECTION ABOVE WITH
 RESPECT TO TRACK LIGHTING.
 ** IT IS IMPORTANT TO KNOW THE SUBMITTED CALCULATIONS
 INDICATE IN THE SUMMARY SHEETS THE TOTAL WATTAGE OF ALL
 LIGHTS IS 631.0 WATTS. THIS IS NOT POSSIBLE WHEN THE
 PLANS CONTAIN A MUCH GREATER AMOUNT.
 ** ONE TRACK LIGHT FIXTURE ALONE IS GREATER THAN THE
 TOTAL SHOWN.
  
 8) NOTE: PLEASE SEE MISSING AUTOMATED LIGHTING CONTROLS
 PER 13-415.1.ABC.1.1, .1.2 AND.1.3. THIS SPACE IS
 LOCATED IN A BUILDING GREATER THAN 5000 SQ FT AND
 AUTOMATED LIGHTING SHUT OFF IS REQUIRED UNDER THE
 FLORIDA ENERGY EFFICIENCY CODE.
 THE LIGHTING CONTROLS NOTED ON E103 DOES NOT PROVIDE
 OVER RIDES, TIMED SCHEDULING, OVER RIDE LOCATIONS,
 SEPARATE SPACE CONTROLS, DISPLAY/ACCENT LIGHTING
 CONTROLS. ETC
 PLEASE ALSO SEE 13-415.1.ABC.1.4 AS ONE OF TWO METHODS
 IS REQUIRED FOR CONTROL OF OUTSIDE LIGHTING.
 THE TIME CLOCK LISTED ON E104 DOES NOT PROVIDE MINIMUM
 FOR CODE.
  
 9) NOTE: PLEASE SEE RISER SHOWS EXISTING #4 ON THE
 SECONDARY SIDE OF THE TRANSFORMER. PLEASE SEE 240.21,
 310.16, 240.4, AND 240.6 AS THIS SIZE CONDUCTOR DOES
 NOT MEET ANY OF THESE SECTIONS. THIS IS A FIRE AND LIFE
 SAFETY HAZARD AND EVEN IF EXISTS THE CONDUCTOR SIZE
 SHALL MEET THE MINIMUM FOR CODE COMPLIANCE.
 PLEASE ADJUST.
  
 10) NOTE: PLEASE SEE 700.12F AS ALL EMERGENCY LIGHTING
 AND EXIT LIGHTING SHALL BE CIRCUITED TO THE LOCAL
 LIGHTING BRANCH CIRCUIT IN ANY ONE AREA. DOES MEET THE
 EXCEPTION IN THE NEC.
  
 11) NOTE: PLEASE SEE PANEL *B* WHICH ONLY LIST THE AHU.
 PLEASE COMPLETE WITH OVER CURRENT PROTECTION FOR ALL
 CIRCUITS.
 408.4, 310.16, 240.4, 450.3 ETC.
 FBC 106.1.1 FOR CLARITY AND 106.1.2 FOR ADDITIONAL
 INFORMATION
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR MINIMUM DESIGN THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-09-23 Cont ID  
Sent By mawillia Date 2009-09-23 Time 13:54 Rev Time 0.00
Received By mawillia Date 2009-09-23 Time 13:40 Sent To B
Notes
2009-09-23 13:54:17*****REVISION #4 & #5, APPROVED*****
  
  
 REVISED PLAN SHEETS A102, A201 AND E102 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-12-24 Cont ID  
Sent By mwennerg Date 2008-12-24 Time 10:35 Rev Time 0.00
Received By mwennerg Date 2008-12-24 Time 10:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-10-23 Cont ID  
Sent By mwennerg Date 2008-10-23 Time 15:25 Rev Time 0.00
Received By mwennerg Date 2008-10-23 Time 15:25 Sent To  
Notes
2008-10-23 15:26:10**DENIED***
  
 PLANS APPEAR TO BE FIRE CODE COMPLIANT BUT WILL REMAIN
 IN FAILED STATUS UNTIL APPLICATION HAS BEEN REVIEWED
 AND APPROVED FOR PERMIT.
  
  
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-09-16 Cont ID  
Sent By mwennerg Date 2008-09-16 Time 10:36 Rev Time 0.00
Received By mwennerg Date 2008-09-16 Time 10:36 Sent To  
Notes
2008-09-16 10:40:39***DENIED***
  
 PLANS APPEAR TO BE FIRE CODE COMPLIANT BUT WILL REMAIN
 IN FAILED STATUS UNTIL APPLICATION HAS BEEN REVIEWED
 AND APPROVED FOR PERMIT.
  
 1) PLEASE SEE OTHER REVIEW COMMENTS REGARDING FS AND
 FAC REQUIREMENTS FOR PLANS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-23 Cont ID  
Sent By mwennerg Date 2008-07-23 Time 14:51 Rev Time 0.00
Received By mwennerg Date 2008-07-23 Time 14:51 Sent To  
Notes
2008-07-23 15:08:20***DENIED***
  
 FOR PLAN REVIEW ONLY NOT FOR PERMIT
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003. PLEASE ADD TO
 CODE SECTION ON SHEET G-001.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241. PLEASE ADD TO CODE SECTION ON SHEET
 G-001.
  
 3) 2A-10B,C RATED FIRE EXTINGUISHER(S) REQUIRED WITH
 LOCATION(S) BEING ILLUSTRATED ON PLANS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER REMODEL.
  
 5) ADDRESS SUITE NUMBER SHALL MEET THE STANDARDS OF
 CITY OF WEST PALM BEACH FOR COMMERCIAL BUILDINGS. SUITE
 NUMBER SHALL BE PROVIDED AT THE REAR ENTRANCE FOR
 EMERGENCY UNIT IDENTIFICATION. SUITE NUMBERS TO BE A
 MINIMUM OF 3" IN HEIGHT AND CONTRASTING WITH
 BACKGROUND.
  
 6) NEW FIRE DAMPER INSTALLATIONS TO BE TESTED FOR
 CLOSURE IN ACCORDANCE WITH UL 555 AND APPROVED PRIOR TO
 FINAL INSPECTION.
  
 7) DUCT SMOKE DETECTORS SHALL BE LOCATED IN SUPPLY DUCT
 UNLESS BOTH SUPPLY AND RETURN DUCTS ARE REQUIRED. WHERE
 FIRE ALARM SYSTEM IS PROVIDED, DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 8) LOCKING ARRANGEMENTS SHALL MEET THE REQUIREMENTS OF
 NFPA 101, SEC. 7.2.1.5.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-10-05 Cont ID  
Sent By dpalmer Date 2009-10-05 Time 11:02 Rev Time 0.00
Received By dpalmer Date 2009-10-05 Time 11:02 Sent To E
Notes
2009-10-05 11:02:43TO DP'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-09-17 Cont ID  
Sent By lmartine Date 2009-09-16 Time 09:48 Rev Time 0.00
Received By lmartine Date 2009-09-16 Time 09:48 Sent To  
Notes
2009-09-17 09:49:04GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-09-03 Cont ID  
Sent By kstevens Date 2009-09-03 Time 11:15 Rev Time 0.00
Received By kstevens Date 2009-09-03 Time 11:15 Sent To  
Notes
2009-09-03 11:18:04SENT TO C-22.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-09-02 Cont ID  
Sent By kstevens Date 2009-09-02 Time 13:40 Rev Time 0.00
Received By kstevens Date 2009-09-02 Time 13:40 Sent To  
Notes
2009-09-02 13:43:12ENGINEERS LETTER SENT TO JWITMER.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-12-09 Cont ID  
Sent By adarroug Date 2008-12-09 Time 11:18 Rev Time 0.00
Received By adarroug Date 2008-12-09 Time 11:18 Sent To  
Notes
2008-12-09 11:19:58TO "COMM" BD#60
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status P Date 2008-11-18 Cont ID  
Sent By adarroug Date 2008-11-18 Time 09:22 Rev Time 0.00
Received By adarroug Date 2008-11-18 Time 09:22 Sent To  
Notes
2008-11-18 09:33:00TO "COMM" BD#56

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-08 Cont ID  
Sent By adarroug Date 2008-10-08 Time 09:29 Rev Time 0.00
Received By adarroug Date 2008-10-08 Time 09:29 Sent To  
Notes
2008-10-08 09:29:48TO "COMM" BD#45

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-27 Cont ID  
Sent By tgordon Date 2008-08-27 Time 15:45 Rev Time 0.00
Received By tgordon Date 2008-08-27 Time 15:45 Sent To  
Notes
2008-08-27 15:45:59TO "COMM" BD #54.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-23 Cont ID  
Sent By mwennerg Date 2008-07-23 Time 15:10 Rev Time 0.00
Received By mwennerg Date 2008-06-25 Time 16:52 Sent To  
Notes
2008-06-25 16:52:24TO "COMM" BD#10

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-09-15 Cont ID  
Sent By rregueir Date 2009-09-15 Time 10:42 Rev Time 0.00
Received By rregueir Date 2009-09-15 Time 10:42 Sent To  
Notes
2009-09-15 10:42:48REVISED M101, M102, M103 DELTA 4

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-01-11 Cont ID  
Sent By rregueir Date 2009-01-11 Time 12:02 Rev Time 0.00
Received By rregueir Date 2009-01-11 Time 11:56 Sent To PC
Notes
2009-01-11 12:03:05PLANS PREVIOUSLY REVIEWED AND PASSED BY TOM GORDON. WAS
 ONLY MISSING PERMIT APPLICATION, WHICH HAS NOW BEEN
 SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-10-09 Cont ID  
Sent By tgordon Date 2008-10-09 Time 10:29 Rev Time 0.45
Received By tgordon Date 2008-10-09 Time 10:23 Sent To  
Notes
2008-10-09 10:29:47PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 FOR PLAN REVIEW ONLY NOT FOR PERMIT
 *** DENIED ***
  
 1) MECHANICAL PLANS ARE O.K. AT THIS TIME, ALL THATS
 NEEDED IS TO HAVE YOUR CONTRACTOR APPLY FOR A PERMIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-09-10 Cont ID  
Sent By tgordon Date 2008-09-10 Time 09:24 Rev Time 0.40
Received By tgordon Date 2008-09-10 Time 09:24 Sent To  
Notes
2008-09-10 09:35:08PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 FOR PLAN REVIEW ONLY NOT FOR PERMIT.
 *** DENIED ***
  
 1) AS NOTED IN LAST REVIEW NOTE #2. THE ARCHITECTURE
 FIRM BAI ARCHITECTURE NEEDS THEIR FIRM LICENSE NUMBER
 AA26001474 IN THE TITLE BLOCK OF ALL THE PLAN PAGES,
 PER FAC 61G1-16.004, PLEASE CORRECT.
  
 NOTE; MECHANICAL PLANS EXCEPT FOR TITLE BLOCK ARE OK AT
 THIS TIME, PLANS CAN NOT PASS REVIEW UNTIL APPLYING FOR
 PERMIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-07-09 Cont ID  
Sent By tgordon Date 2008-07-09 Time 11:37 Rev Time 1.00
Received By tgordon Date 2008-07-09 Time 11:36 Sent To  
Notes
2008-07-09 11:53:22PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** FOR PLAN REVIEW ONLY NOT FOR PERMIT **
 *** DENIED ***
  
 1) INFORMATION MISSING FROM TITLE BLOCK.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT SEE
 FAC 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER. (MISSING)
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB
 ADDRESS" SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 3) PLAN M101 SYMBOL SCHEDULE IS MISSING THE SYMBOL FOR
 THE SMOKE DAMPER, PLEASE CORRECT AS THE PLAN SHOWS
 SMOKE DAMPERS ARE TO BE INSTALLED, PER 2004 FBC
 106.1.1.
  
 4) PLEASE ADD A SMOKE DAMPER DETAIL TO THE MECHANICAL
 PLANS, PER 2004 FBC/M 607.8.
  
 5) SHOW ON MECHANICAL PLAN HOW THE SMOKE DAMPERS ARE TO
 BE ACTUATED, PER 2004 FBC/M 607.3.2.1.
  
 6) NOTICE: SMOKE DAMPERS MAY NOT BE REQUIRED, SEE 2004
 FBC 710.7 AS AIR DUCTS ARE BEING INSTALLED AND NOT AIR
 TRANSFER OPENINGS. THIS DOES NOT PREVENT THE USE OF
 THEM, IF WANTED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-09-09 Cont ID  
Sent By kstevens Date 2009-09-09 Time 16:03 Rev Time 0.00
Received By kstevens Date 2009-09-09 Time 16:03 Sent To  
Notes
2009-09-09 16:03:37REVISION OK -- SHT M-102.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-12-18 Cont ID  
Sent By kstevens Date 2008-12-18 Time 12:00 Rev Time 0.00
Received By kstevens Date 2008-12-18 Time 12:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-10-16 Cont ID  
Sent By mperson Date 2008-10-16 Time 08:58 Rev Time 1.00
Received By mperson Date 2008-10-16 Time 08:58 Sent To  
Notes
2008-10-16 09:05:24PLUMBING PLAN REVIEW:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 NOTE: FOR PLAN REVIEW ONLY, NOT FOR PERMIT.
 *** DENIED ***
  
 1. NOTE: PLUMBING PLANS ARE COMPLIANT AT THIS TIME,
 HOWEVER WILL REMAIN IN A FAILED STATUS UNTIL A
 CONTRACTOR HAS APPLIED FOR A PERMIT.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-09-04 Cont ID  
Sent By kstevens Date 2008-09-04 Time 10:34 Rev Time 0.00
Received By kstevens Date 2008-09-04 Time 10:34 Sent To  
Notes
2008-09-04 10:52:08DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 2. INFORMATION MISSING FROM TITLE BLOCK.
 SEE FAC 61G1-16.004 PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE
 BLOCK WHICH MUST INCLUDE
 - STATE THE FIRM NAME, ADDRESS & TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS
  
 NOTE: PLANS MISSING PRINTED NAME, PRINTED LICENSE
 NUMBER, AND CERTIFICATE OF AUTHORIZATION NUMBER.
 ****RESPONSE NOTED, BUT THE CERTIFICATE OF
 AUTHORIZATION IS NOT SHOWN IN THE TITLE BLOCK OF THE
 ARCHITECT. THIS IS REQUIRED ON ALL SHEETS WITH BAI
 ARCHITECTURE INC TITLE BLOCK ON IT. (SEE ATTACHED
 SHEET).
  
 4. SHEET A201 DETAILS 8 & 9 INTERIOR TOILET ROOM
 ELEVATIONS: PLEASE PROVIDE THE FOLLOWING REQUIRED
 INFORMATION PER FBC-CHAPTER 11, FLORIDA ACCESSIBILITY
 CODE.
  
 A} WATER CLOSET= CLEARLY INDICATE THE HEIGHT OF THE
 WATER CLOSET 17"-19". PER SECTION 11-4.16.3.
 B} LAVATORY= CLEARLY PROVIDE A CLEARANCE OF AT LEAST 29
 INCHES ABOVE THE FINNISH FLOOR TO THE BOTTOM OF THE
 APRON. KNEE AND TOE CLEARANCE SHALL COMLY WITH FIGURE
 31. PER SECTION 11-4.19.2.
 ****RESPONSE NOTED, BUT NO CLEARANCE IS INDICATED FOR
 THE LAV.
  
 5. SHEET M102 WATER RISER DIAGRAM: PER FBC-PLUMBING
 SECTION 604.9 WATER HAMMER. WATER HAMER ARRESTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURE'S
 SPECIFICATIONS. MANUFACTURE'S SPECIFICATIONS FOR BOTH
 MODELS PPP AND SIOUX CHIEF STATE THAT WATER HAMMER
 ARRESTORS SHALL BE PLACED AS NEAR TO THE SOURCE OF THE
 SHOCK AS POSSIBLE. PLEASE LOCATE WATER HAMMER ARRESTORS
 CLOSE TO FIXTURE.
 ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTOR IS
 SHOWN LOCATED IN THE CEILING. PLEASE LOCATE THE
 ARRESTOR NEXT TO THE FIXTURE. PDI-WH 201.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-18 Cont ID  
Sent By mperson Date 2008-07-18 Time 11:52 Rev Time 0.00
Received By mperson Date 2008-07-18 Time 11:52 Sent To  
Notes
2008-07-18 12:00:11PLUMBING PLAN REVIEW:
 DENIED:
  
 **FOR PLAN REVIEW ONLY NOT FOR PERMT**
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1.INFORMATION MISSING FROM TITLE BLOCK.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2. INFORMATION MISSING FROM TITLE BLOCK.
 SEE FAC 61G1-16.004 PLANS PREPARED BY A REGISTERED
 ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE
 NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL
 -
 INCLUDE THE PRINTED NAME OF THE ARCHITECT
 SEALING THE
 PLANS
 NOTE: MISSING PRINTED NAME, PRINTED LICENSE NUMBER,
 AND CERTIFICATE OF AUTHORIZATION NUMBER.
  
 3. SHEET GOO1 PLUMBING FACILITIES: INDICATES BOTTLED
 WATER PROVIDED INSTEAD OF THE REQUIRED DRINKING
 FOUNTAIN. PER FBC- PLUMBING SECTION 410.1 BOTTLED WATER
 DISPENSERS SHALL BE PERMITTED TO BE SUBSTITUTED FOR NOT
 MORE THAN 50 PERCENT OF THE REQUIRED DRINKING
 FOUNTAINS. PER FBC- PLUMBING TABLE 401.3 WITH AN
 OCCUPANCY OF MERCANTILE (M) DRINKING FOUNTAIN
 REQUIREMENTS ARE 1 PER 1000. PLEASE INDICATE THE
 REQUIRED DRINKING FOUNTAIN ON THE RESUBMITTED SHEET
 A101 CONSTRUCTION FLOOR PLAN, SHEET M102 PLUMBING PLAN,
 SANITARY AND WATER RISER DIAGRAMS.
 NOTE: THE DRINKING FOUNTAIN IS REQUIRED TO BE
 ACCESSIBLE AND COMPLIANT WITH FBC- CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE THE FOLLOWING SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
  
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
  
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN
 3" OF THE FRONT OF FOUNTAIN.
  
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
  
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE. (CLEARLY INDICATE THE REQUIRED CLEAR FLOOR SPACE
 ON SHEET A101 CONSTRUCTION FLOOR PLAN.
  
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 4. SHEET A201 DETAIL 8 & 9 INTERIOR TOILET ROOM
 ELEVATIONS: PLEASE PROVIDE THE FOLLOWING REQUIRED
 INFORMATION PER FBC- CHAPTER 11, FLORIDA ACCESSIBILITY
 CODE.
  
 A} WATER CLOSET= CLEARLY INDICATE THE HEIGHT OF THE
 WATER CLOSET 17"-19". PER SECTION 11-4.16.3.
 B} LAVATORY= CLEARLY PROVIDE A CLEARANCE OF AT LEAST
 29 INCHES ABOVE THE FINNISH FLOOR TO THE BOTTOM OF THE
 APRON. KNEE AND TOE CLEARANCE SHALL COMPLY WITH FIGURE
 31. PER SECTION 11-4.19.2.
  
 5. SHEET M102 WATER RISER DIAGRAM: PER FBC- PLUMBING
 SECTION 604.9 WATER HAMMER. WATER-HAMMER ARRESTORS
 SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S SPECIFICATIONS. MANUFACTURER'S
 SPECIFICATIONS FRO BOTH MODELS PPP AND SIOUX CHIEF
 STATE THAT WATER-HAMMER ARRESTORS SHALL BE PLACED AS
 NEAR TO THE SOURCE OF SHOCK AS POSSIBLE. PLEASE LOCATE
 WATER-HAMMER ARRESTORS CLOSE TO FIXTURE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-11-19 Cont ID  
Sent By eschneid Date 2008-11-19 Time 11:29 Rev Time 0.00
Received By eschneid Date 2008-11-19 Time 11:18 Sent To  
Notes
2008-11-19 11:29:31SIGNS AND AWNINGS REQUIRE SEPARATE PERMIT APPROVAL.

Review Stop Z ZONING
Rev No 3 Status F Date 2008-10-16 Cont ID  
Sent By eschneid Date 2008-10-16 Time 14:35 Rev Time 0.00
Received By eschneid Date 2008-10-16 Time 14:35 Sent To  
Notes
2008-10-16 14:37:50PLAN REVIEW FAIL
  
 PLANS OK FOR ZONING AS SHOWN ONCE THIS IS A BUILDING
 PERMIT.
  
 NOTE THAT SIGNS REQUIRE A SEPARATE PERMIT.
  
 ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-09-02 Cont ID  
Sent By eschneid Date 2008-09-02 Time 09:56 Rev Time 0.00
Received By eschneid Date 2008-09-02 Time 09:56 Sent To  
Notes
2008-09-02 09:59:00FAILED - PLAN REVIEW FAIL.
  
 NOTE: ALL SIGNS WILL REQUIRE A SEPARATE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-27 Cont ID  
Sent By choops Date 2008-06-27 Time 16:37 Rev Time 0.00
Received By choops Date 2008-06-27 Time 16:37 Sent To  
Notes
2008-06-27 16:39:02***FAILED***
  
 1)SIGNS AND AWNINGS SHALL BE APPROVED UNDER SEPARATE
 PERMIT.
  
  
 QUESTIONS/COMMENTS, CONTACT ERIC SCHNEIDER,
 (561)822-1435


Account Summary | Usage Policy | Privacy Policy