Plan Review Details - Permit 08060702
Plan Review Stops For Permit 08060702
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2008-06-30 Cont ID  
Sent By lursu Date 2008-06-30 Time 14:19 Rev Time 0.00
Received By lursu Date 2008-06-30 Time 14:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-15 Cont ID  
Sent By mjacobs Date 2008-07-15 Time 07:57 Rev Time 0.00
Received By mjacobs Date 2008-07-15 Time 06:25 Sent To  
Notes
2008-07-15 07:57:52BUILDING PLAN REVIEW
 PERMIT: 08060702
 ADD: 7750 W. OKEECHOBEE BLVD #5
 CONT: SPANISH RIVER CONST. INC.
 TEL: (561)997-0045 X204
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 7-15-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5)FBC 11-7(2)(I) A PORTION OF THE MAIN COUNTER SHALL
 BE A MINIMUM OF36 INCHES IN LENGTH AND A MAXIMUM
 HEIGHT OF 36 INCHES.. PLEASE SHOW THE FRONT ELEVATION
 OF THE MAIN COUNTER MEETING THESE REQUIREMENTS.
  
 6)FIRE SPRINKLER PLANS REQUIRED TO SHOW THE NEW
 LOCATIONS OF THE SPRINKLER HEADS DUE TO THE NEW
 DEMISING WALL. THIS INFORMATION CAN BE SHOWN ON THE NEW
 CEILING PLAN. FBC* 106.3.5.1.1(5)
 7)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3*
  
 8)THE DESCRIPTION ON THE APPLICATION IS NOT CLEAR.
 THE APPLICATION NEEDS TO DESCRIBE THE PROJECT CLEARLY;
 IT SEEMS AS IF SOME OF THE INFORMATION IS CROSSED OUT.
 IF THE INFORMATION ON THE APPLICATION IS INCORRECT,
 DRAW A RED-LINE THROUGH THE SECTION WHICH WILL BE
 OMITTED FROM THE PROJECT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-07-03 Cont ID  
Sent By btrobaug Date 2008-07-03 Time 10:09 Rev Time 0.00
Received By btrobaug Date 2008-07-03 Time 09:09 Sent To  
Notes
2008-07-03 10:01:51 
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE.NOTE SAME ON THE PLAN.
  
 2} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER
 REQUIRED BY 61G15-23.002FLORIDA ADMINISTRATIVE CODE.
  
 3} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 4} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-09 Cont ID  
Sent By mwennerg Date 2008-07-09 Time 13:46 Rev Time 0.00
Received By mwennerg Date 2008-07-09 Time 13:46 Sent To  
Notes
2008-07-09 13:53:47***DENIED***
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
 PLEASE ADD TO PLANS.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY
 WITH NFPA 241. PLEASE ADD TO PLANS.
  
 3) SHOW THE LOCATION OF REQUIRED 2A-10B,C RATED FIRE
 EXTINGUISHER(S).
  
 4) SHEET 2 INDICATES EXISTING OR RELOCATED. PLEASE
 IDENTIFY WHAT EQUIPMENT THIS REFERS TO. NO LEGEND FOUND
 ON PLANS.
  
 5) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER REMODEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-07-15 Time   Rev Time 0.00
Received By adarroug Date 2008-06-25 Time 14:20 Sent To  
Notes
2008-06-26 14:03:41TO "BOB"#15
2008-06-25 14:21:19WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-06-26 Cont ID  
Sent By tgordon Date 2008-06-26 Time 16:26 Rev Time 0.15
Received By tgordon Date 2008-06-26 Time 16:26 Sent To  
Notes
2008-06-26 16:26:37NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-03 Cont ID  
Sent By mperson Date 2008-07-03 Time 08:00 Rev Time 0.00
Received By mperson Date 2008-07-03 Time 08:00 Sent To  
Notes
2008-07-03 08:13:43PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. THE SUBMITTED PLANS DO NOT MEET THE MINIMUM NUMBER
 OF REQUIRED PLUMBING FIXTURES FOR A BUSSINESS PER FBC-
 PLUMBING TABLE 403.1 BUSSINESS (B). A DRINKING FOUNTAIN
 IS REQUIRED AND IT SHALL BE COMPLIANT PER FBC- CHAPTER
 11, FLORIDA ACCESSIBILITY CODE PER THE FOLLOWING
 SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 2. PROVIDE A SANITARY AND WATER ISOMETRIC RISER
 DIAGRAM FOR THE REQUIRED DRINKING FOUNTAIN. PER (W.P.B.
 AS AMENDED) SECTION 106.3.5.1.3 PLUMBING
 (3)(4)(6)(13).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-06-26 Cont ID  
Sent By choops Date 2008-06-26 Time 14:54 Rev Time 0.00
Received By choops Date 2008-06-26 Time 14:54 Sent To  
Notes
2008-06-26 14:54:17*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.