| Plan Review Stops For Permit 08060680 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-10-09 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2008-10-09 |
Time |
16:50 |
Rev Time |
2.00 |
| Received By |
amorse |
Date |
2008-10-09 |
Time |
15:55 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-09-13 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2008-09-13 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2008-09-13 |
Time |
09:42 |
Sent To |
PC |
|
| Notes |
| 2008-09-13 09:44:06 | | | | | | | DENIED | | | | | | THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE 1ST | | | REVIEW | | | | | | | | | 2) PLEASE SEE CHAPTER 6 FBC TO CORRECTLY DETERMINE THE | | | TYPE OF CONSTRUCTION | | | ******GENERALLY THE MIN REQUIRED TYPE WOULD BE USE TYPE | | | VB, THE TYPE CHOSEN IS FOR HEAVY TIMBER CONSTRUCTION | | | (IV)****** | | | 3) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | | PER 108.3 FBC* | | | | | | 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE, | | | AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE | | | INFORMATION. | | | | | | NEW REVIEW COMMENTS | | | | | | 1) PROVIDE PRODUCT APPROVAL FOE MULLIONS THAT WOULD BE | | | REQUIRED BETWEEN CASEMENT UNITS AND BETWEEN | | | CASEMENTS/FIXED IN MASTER BEDROOM. PLEASE SEE | | | MIAMI-DADE NOA #04-0603.04 | | | | | | 2) ONLY ONE SET OF NEW DRAWINGS WAS SUBMITTED PROVIDE 2 | | | COPIES OF ALL CONSTRUCTION DOCUMENTS. | | | | | | 3) THE STATEWIDE PRODUCT APPROVAL NUMBERS FOR ALL OF | | | THE YYK PRODUCTS ARE NO LONGER POSTED ON THE SITE AND | | | THE MIAMI-DADE REPORT FOR THE CASEMENTS HAS EXPIRED, | | | THERE ARE NEW STATE APPROVALS AVAILABLE ALTHOUGH WE NO | | | LONGER REQUIRE THEM AND THEIR ARE UPDATED MIAMI-DADE | | | NOA'S ALSO AVAILABLE. BEFORE PRINTING AND HAVING THEM | | | REVIEWED BY THE DESIGNER OF RECORD PLEASE BE SURE YOU | | | ONLY SUBMIT WHAT IS BEING USED, FOR EXAMPLE THE MASTER | | | BEDROOM WINDOW LOOKS LIKE CASEMENTS OVER FIXED BUT | | | DRAWING STATE CASEMENT OVER CASEMENT PLEASE CLARIFY AND | | | PROVIDE CORRECT PRODUCT APPROVALS. ALSO THE YYK UNIT | | | CAN BE INSTALLED AS ONE UNIT WITH INTEGRAL MULLION OR | | | IF USING OTHER MANUFACTURER SUCH AS NUAIR THEN MULLIONS | | | WOULD BE REQUIRED. | | | | | | 4) REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS | | | WITH REVISIONS AND INCLUDE 1 COPY OF THE MOST RESENT | | | OLD PAGES ONLY FOR REFERENCE. REMOVE ALL NON USED | | | PRODUCT APPROVAL FROM SUBMITTALS, WITH YYK CASEMENT AND | | | FIXED WINDOWS FOR MASTER WHERE IS THE NUAIR PRODUCT | | | BEING USED? | | | | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-07-04 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2008-07-04 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2008-07-04 |
Time |
14:04 |
Sent To |
PC |
|
| Notes |
| 2008-07-04 14:50:17 | | | | | | | DENIED | | | | | | 1) PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL | | | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 & 2007 | | | AMENDMENTS PER 106.1.1 FBC* | | | | | | 2) PLEASE SEE CHAPTER 6 FBC TO CORRECTLY DETERMINE THE | | | TYPE OF CONSTRUCTION | | | | | | 3) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | | PER 108.3 FBC* | | | | | | 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE, | | | AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE | | | INFORMATION. | | | | | | 5) THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF | | | EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE | | | SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES. | | | ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG | | | | | | 6) THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9B-72 | | | (PRODUCT APPROVALS) SHALL BE REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* | | | | | | 7) THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA | | | STATE PRODUCT APPROVAL SHEETS WHEN AVAILABLE. THEY CAN | | | BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG. WHEN | | | AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE | | | DENIED | | | | | | 8) NO PRODUCT APPROVALS WERE SUBMITTED FOR STORE FRONT | | | WINDOW/DOOR UNIT IN LIVINGROOM, CASEMENT/AWNING WINDOWS | | | UNDER FIXED WINDOW IN MASTER BEDROOM AND MULLIONS IF | | | REQUIRED | | | | | | 9) THE PRODUCT APPROVAL FOR THE YKK FIXED WINDOW IS | | | INCOMPLETE | | | | | | 10) NEW MASTER BEDROOM WINDOW DOES NOT MEET EMERGENCY | | | EGRESS REQUIREMENTS PER R310 FBC: MIN. NET CLEAR | | | OPENING OF 5 SQ.FT. ON GRADE FLOOR. MIN. NET CLEAR | | | OPENING ALL OTHER FLOORS OF 5.7 SQ.FT. IN BOTH CASES | | | THE MIN.NET CLEAR HEIGHT SHALL BE 24" AND THE NET CLEAR | | | WIDTH SHALL BE 20" | | | | | | 11) IF WOOD BUCKS ARE TO BE USED AN ATTACHMENT DETAIL | | | IS REQUIRED FOR THE TRANSFER OF APPLICABLE LOADS TO THE | | | BUILDING PER R613.6.1.1 FBC RES. | | | AS THE PRODUCT APPROVALS DO NOT SPECIFY ANY ATTACHMENT | | | METHOD | | | | | | 12) THE OPENING FOR THE WINDOW IN THE MASTER BEDROOM | | | HAS BEEN MADE SMALLER AND THE DOOR/WINDOW UNIT IN THE | | | LIVINGROOM IS LARGER, SUBMIT STRUCTURAL WALL CHANGES TO | | | ALLOW FOR THE ATTACHMENT OF THE NEW GLAZED UNITS | | | | | | 13) PROVIDE ATTACHMENT DETAILS FOR THE NEW ALUMINUM | | | TRELLIS AT EXISTING HOUSE AND TOP OF NEW SCREEN WALL | | | | | | 14) CLARIFY SCREEN FENCE HEIGHTS, LEGEND ON SHEET A1 | | | STATES PRIVACY WALL AT 5'-0" AND ELEVATIONS ON A3 SOUTH | | | ELEVATION IS 5'-10" AND NORTH ELEVATION IS 6'-0" THESE | | | ELEVATIONS ALSO STATE THE FRONT WALL AS NEW AND THE | | | REAR WALL AS FUTURE | | | | | | 15) PLEASE KEEP PERMIT APPLICATION AND DRAWING SCOPE OF | | | WORK THE SAME, REMOVE ALL FUTURE WORK FROM THE DRAWINGS | | | TO ALLEVIATE COMMENTS IN PLAN REVIEW, ALSO NOTE ZONING | | | COMMENTS ON THE LOCATION OF THE PROPOSED GENERATOR | | | | | | 16) PLEASE MAKE CORRECTIONS TO THE FOUNDATION PLANS, | | | PER 106.1.3 FBC* THE BUILDING OFFICIAL MAY ESTABLISH | | | THROUGH DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND | | | SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK" | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-10-06 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-10-06 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-10-06 |
Time |
16:01 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-07-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-07-22 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-07-21 |
Time |
16:28 |
Sent To |
M |
|
| Notes |
| 2008-07-22 08:38:38 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | THE FOLLOWING COMMENTS ARE FROM THE PREVIOUS REVIEW AND | | | HAD INCORRECT OR NO RESPONSE. | | | | | | 1} THE 250 MCM CONDUCTORS FEEDING THE 400 AMP MDP DO | | | NOT COMPLY WITH 310.15(B)(6), NEED TO BE A MINIMUM OF | | | 400 MCM FOR A 400 AMP SERVICE. NOTE: THE MAIN IS 200 | | | AMP AND THE NOTE ON THE CALCULATIONS INDICATE A 200 AMP | | | SERVICE. CORRELATE THE RISER.***THERE ARE 250 MCM | | | FEDING THE 200 AMP MAIN AND NOW 400 MCM FEEDING THE | | | "MDP" WHICH IS ALSO RATED AT 200 AMPS.THE 400 MCM | | | THOUGH NOT A VIOLATION, MUST BE INSTALLED IF THE | | | DESIGNER CHOOSES TO USE THEM. A REVISION WILL BE | | | REQUIRED TO CHANGE THE PLAN IN THE FUTURE. | | | | | | 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE | | | REVIEWED.WHERE IS THE MDP LOCATED ?*** STILL NOT SHOWN | | | ON THE PLAN. | | | | | | 9} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | | 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A) | | | (3).***ONLY ONE AHU IS SHOWN AND TWO COMPRESSERS.PLEASE | | | CLARIFY. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-06-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-26 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-26 |
Time |
08:23 |
Sent To |
P |
|
| Notes |
| 2008-06-26 09:33:48 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE 250 MCM CONDUCTORS FEEDING THE 400 AMP MDP DO | | | NOT COMPLY WITH 310.15(B)(6), NEED TO BE A MINIMUM OF | | | 400 MCM FOR A 400 AMP SERVICE. NOTE: THE MAIN IS 200 | | | AMP AND THE NOTE ON THE CALCULATIONS INDICATE A 200 AMP | | | SERVICE. CORRELATE THE RISER. | | | | | | 2} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH | | | 250.66.THE SERVICE CONDUCTORS DETERMINE THIS. SEE | | | ARTICLE. | | | | | | 3} A NOTE AT THE RISER INDICATES THE SERVICE IS LOCATED | | | ON THE GARAGE. THE PLAN SHOWS A METER AND DISCONNECTS | | | OUTSIDE THE KITCHEN WALL. | | | | | | 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE | | | REVIEWED.WHERE IS THE MDP LOCATED ? | | | | | | 5} INDICATE THE GENERATOR TO BE FUTURE ON THE RISER AS | | | A SEPARATE PERMIT IS REQUIRED WITH ALL SUPPORTING | | | DOCUMENTS FOR THAT PERMIT. | | | | | | 6} THERE APPEARS TO BE AN ELECTRICAL PANEL IN THE | | | STORAGE ROOM, LABEL SAME. SEE ARTICLES 408.17 AND | | | 240.24(D). | | | | | | 7} LABEL THE PANEL SCHEDULE INDICATING IF IT IS FOR MDP | | | OR PANEL "A". GIVE A PANEL SCHEDULE FOR ALL PANELS. | | | 408.4. | | | | | | 8} THE DISPOSAL AND MICROWAVE ON THE PANEL SCHEDULE ARE | | | NOT IN THE LOAD CALCULATIONS.220 | | | | | | 9} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | | 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A) | | | (3). | | | | | | 10} THERE WERE TWO SHEET A3 SUBMITTED. REMOVE THE SHEET | | | THAT IS NOT TO BE REVIEWED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-09-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-26 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-26 |
Time |
15:24 |
Sent To |
Z |
|
| Notes |
| 2008-09-26 15:25:39 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-08-28 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-08-28 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
tgordon |
Date |
2008-08-28 |
Time |
13:54 |
Sent To |
Z |
|
| Notes |
| 2008-08-28 13:55:26 | TO "ZONING"BOX. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-07-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-18 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-18 |
Time |
14:10 |
Sent To |
E |
|
| Notes |
| 2008-07-18 14:11:37 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-07-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-10 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-10 |
Time |
15:12 |
Sent To |
Z |
|
| Notes |
| 2008-07-10 15:13:35 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2008-07-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-25 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2008-06-25 10:57:01 | TO "SFR" "Z" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2008-10-08 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-10-08 |
Time |
09:25 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-10-08 |
Time |
09:25 |
Sent To |
P |
|
| Notes |
| 2008-10-08 09:26:27 | NO MECHANICAL PLANS SUBMITTED, AND NO | | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | | THIS TIME. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-07-22 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-07-22 |
Time |
10:32 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-07-22 |
Time |
10:32 |
Sent To |
P |
|
| Notes |
| 2008-07-22 10:47:47 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | | | | 1) AS NOTED IN LAST REVIEW 6-25-08. PLAN A1 NEW FLOOR | | | PLAN SHOWS A GAS WATER HEATER (APPEARS TO BE A | | | TANKLESS) IN THE NEW STORAGE ROOM. THIS APPEARS TO BE A | | | CONFINED SPACE, PLEASE SUBMIT MANUFACTURER'S | | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR GAS | | | WATER HEATER AND STATE WERE IT'S GETTING THE COMBUSTION | | | AIR FROM, IF NOT A GAS WATER HEATER CORRECT PLANS PAGES | | | A1 AND A2, PER 2004 FBC/R G2407.1. | | | | | | 2) AS NOTED IN LAST REVIEW 6-25-08. PLAN A1 NEW FLOOR | | | PLAN SHOWS THE AIR HANDLER BEING RELOCATED TO THE NEW | | | A/C CLOSET, PLEASE SUBMIT A MECHANICAL PLAN SHOWING THE | | | SUPPLY AND RETURN AIR DUCTS THAT ARE BEING ALTERED, PER | | | 2004 FBC/R M1601.1. | | | | | | 3) AS NOTED IN LAST REVIEW 6-25-08. PLAN A2 ELECTRICAL | | | PLAN IS LABELING THE A/C CONDENSER UNITS AS A.H.U. (AIR | | | HANDLER UNIT), PLEASE CORRECT PER 2004 FBC/R, CH. 13 | | | ANDFBC 106.1.1. | | | | | | 4) PLAN A1 AND A2 SHOW A A/C CONDENSER UNIT LABELED | | | FUTURE AHU, PLEASE REMOVE FROM PLANS OR SHOW THE | | | COMPLETE SYSTEM IT IS GOING TO, PER 2004 WPB AMEND. | | | 106.3.5.4 (10). | | | | | | 5) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, SEE F.B.C. 106.1.1. | | | | | | 6) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR | | | TIMES THE FEE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-06-25 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-06-25 |
Time |
14:29 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2008-06-25 |
Time |
14:29 |
Sent To |
E |
|
| Notes |
| 2008-06-25 14:56:13 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLEASE SUBMIT A MECHANICAL (A/C) PLAN, PER 2004 WPB | | | AMEND. 106.3.5.4 (10). | | | | | | 2) PLAN A1 NEW FLOOR PLAN SHOWS A GAS WATER HEATER | | | (APPEARS TO BE A TANKLESS) IN THE NEW STORAGE ROOM. | | | THIS APPEARS TO BE A CONFINED SPACE, PLEASE SUBMIT | | | MANUFACTURER'S SPECIFICATION'S AND INSTALLATION | | | INSTRUCTIONS FOR GAS WATER HEATER AND STATE WERE IT'S | | | GETTING THE COMBUSTION AIR FROM, PER 2004 FBC/R | | | G2407.1. | | | | | | 3) PLAN A1 NEW FLOOR PLAN SHOWS THE AIR HANDLER BEING | | | RELOCATED TO THE NEW A/C CLOSET, PLEASE SHOW ON THE NEW | | | MECHANICAL PLAN BEING SUBMITTED THE SUPPLY AND RETURN | | | AIR DUCTS, PER 2004 FBC/R M1601.1. | | | | | | 4) PLAN A2 TOTAL BUILDING LOAD CALCULATIONS STATES THE | | | CLOTHES DRYER IS GAS, THE ELECTRICAL PLAN SHOWS A 220V | | | OUTLET FOR IT. PLEASE CLARIFY ON THE PLANS IF THE | | | CLOTHES DRYER IS GAS OR ELECTRIC, PER 2004 FBC/R | | | G2407.1 AND FBC 106.1.1. | | | | | | 5) PLAN A2 ELECTRICAL PLAN IS LABELING THE A/C | | | CONDENSER UNITS AS A.H.U. (AIR HANDLER UNIT), PLEASE | | | CORRECT PER 2004 FBC/R, CH. 13 ANDFBC 106.1.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-10-08 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-10-08 |
Time |
11:20 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2008-10-08 |
Time |
11:20 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-07-28 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-07-28 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-07-28 |
Time |
10:08 |
Sent To |
B |
|
| Notes |
| 2008-07-28 11:31:47 | PLUMBING PLAN REVIEW: | | | DENIED **2ND TIME: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE | | | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW | | | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW | | | COMMENTS. | | | NOTE: THERE WERE NO COMMET RESPONSES FROM THE DESIGNER | | | AND NONE OF THE PREVIOUS PLUMBING REVIEW COMMENTS WERE | | | ADDRESSED | | | | | | 1. SHEET A3 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT | | | REFLECT THE FLOOR PLAN OF SHEET A1 AND IS NOT CODE | | | COMPLIANT PER FBC- PLUMBING THE FOLLOWING SECTIONS. | | | | | | A} BATHTUB MISSING FROM RISER DIAGRAM. PER SECTIONS | | | 401.1 AND 701.1 SCOPE. | | | | | | B} BOTH SINKS IN THE KITCHEN REQUIRE VENTS. PER | | | SECTION 901.2.1 VENTING REQUIRED. | | | | | | C} SINK IN THE LAUNDRY REQUIRES A VENT. PER 901.2.1 | | | VENTING REQUIRED. | | | | | | D} THE WASHING MACHINE IS DESIGNED WITH A PROHIBITED | | | "S" TRAP. PER SECTION 1002.3 PROHIBITED TRAPS (5). THE | | | WASHING MACHINE REQUIRES A VENT. PER SECTION 901.2.1 | | | VENTING REQUIRED. | | | NOTE: PLEASE DESIGN THE WASHING MACHINE PER THE | | | FOLLOWING. | | | | | | SECTION 406.3 WASTE CONNECTIONS.THE TRAP AND FIXTURE | | | DRAIN FOR AN AUTOMATIC CLOTHES | | | WASHER SHALL BE A MINIMUM OF 2 INCHES | | | (51MM) IN DIAMETER. THE AUTOMATIC | | | CLOTHES WASHER FIXTURE DRAIN SHALL | | | CONNECT TO A BRANCH DRAIN OR DRAINAGE | | | STACK A MINIMUM OF 3 INCHES (76MM) IN | | | DIAMETER. | | | | | | SECTION 802.4 STANDPIPES.STANDPIPES SHALL BE | | | INDIVIDUALLY TRAPPED. STANDPIPES SHALL | | | EXTEND A MINIMUM OF 18 INCHES (457MM) | | | AND A MAXIMUM OF 42 INCHES (1066MM) | | | ABOVE THE TRAP WEIR. ACCESS SHALL BE | | | PROVIDED TO ALL STANDPIPES AND DRAINS | | | FOR RODDING. | | | NOTE: CLEARLY INDICATE THE REQUIRED STANDPIPE FOR THE | | | WASHING MACHINE. | | | | | | SECTION 708.7 MINIMUM SIZE. CLEANOUTS SHALL BE THE | | | SAME NOMINAL SIZE AS THE PIPE THEY SERVE UP TO 4 INCHES | | | (102MM) | | | NOTE: WASHING MACHINE CLEANOUT SHALL BE 3". | | | | | | SECTION 708.9 ACCESS. ACCESS SHALL BE | | | PROVIDED TO ALL CLEANOUTS. | | | NOTE: WASHING MACHINE CLEANOUT SHALL BE LOCATED AT 4' | | | A.F.F. | | | | | | E} "OK" COMMENT ADDRESSED. | | | | | | 2. SHEET A1 NEW FLOOR PLAN INDCATES ICE. IS THIS AN | | | ICE MAKER? NOTE: THE ICE MAKER MAY REQUIRE A DRAIN PIPE | | | FROM THE SANITARY SYSTEM. PLEASE SUBMIT TWO COPIES OF | | | ICE MAKER MANUFACTURE SHEETS AND DESIGN SANITARY SYSTEM | | | ACCORDINGLY IF A DRAIN IS REQUIRED. PER FBC- PLUMBING | | | SECTION 701.1 SCOPE. WHERE A TRAP SEAL IS SUBJECT TO | | | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE | | | INSTALLED. PER FBC- PLUMBING SECTION 1002.4 TRAP | | | SEALS. | | | | | | **THE FOLLOWING ARE NEW COMMENTS | | | | | | 3. SHEET A1 SCOPE OF WORK INDICATES IN THE GUEST | | | BEDROOM (NEW MASTER CLOSET) ADD DRAINS AND CAP FOR | | | SINKS (FUTURE APPLICATION) AND ADD WC WASTE LINE AND | | | CAP (FUTURE USE). THESE FUTURE FIXTURES AND LAYOUT MUST | | | BE INDICATED ON THE PROPOSED NEW FLOOR PLAN AND THE | | | SANITARY WASTE, VENTS, TRAPS AND CLEANOUTS WITH SIZES | | | MUST BE CLEALY INDICATED ON THE SANITARY RISER DIAGRAM | | | FOR THESE FUTURE FIXTURES ON SHEET A3. PER (W.P.B. AS | | | AMENDED) SECTION 106.3.5.4(9) PLUMBING AND FBC-2004 | | | PLUMBING SECTION 701.1, AND SECTION 901.1 SCOPE. | | | | | | 4. SHEET A1 INDICATES GAS APPLIANCES (GAS W.H.& GAS | | | RANGE): PLEASE KNOW THAT A GAS PERMIT IS REQUIRED FOR | | | THIS WORK. A LICENSED GAS OR PLUMBING CONTRACTOR SHALL | | | SUBMIT PLANS WITH PERMIT APPLICATION. ALL GAS | | | INSPECTIONS ARE TO BE COMPLETE BEFORE THE FINAL | | | INSPECTION. | | | | | | 5. SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR | | | TIMES THE FEE. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-07-02 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-07-02 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-07-02 |
Time |
10:05 |
Sent To |
B |
|
| Notes |
| 2008-07-02 10:35:39 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | 1. SHEET A3 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT | | | REFLECT THE FLOOR PLAN OF SHEET A1 AND IS NOT CODE | | | COMPLIANT PER FBC- PLUMBING THE FOLLOWING SECTIONS. | | | | | | A} BATHTUB MISSING FROM RISER DIAGRAM. PER SECTIONS | | | 401.1 AND 701.1 SCOPE. | | | | | | B} BOTH SINKS IN THE KITCHEN REQUIRE VENTS. PER | | | SECTION 901.2.1 VENTING REQUIRED. | | | | | | C} SINK IN THE LAUNDRY REQUIRES A VENT. PER 901.2.1 | | | VENTING REQUIRED. | | | | | | D} THE WASHING MACHINE IS DESIGNED WITH A PROHIBITED | | | "S" TRAP. PER SECTION 1002.3 PROHIBITED TRAPS (5). THE | | | WASHING MACHINE REQUIRES A VENT. PER SECTION 901.2.1 | | | VENTING REQUIRED. | | | NOTE: PLEASE DESIGN THE WASHING MACHINE PER THE | | | FOLLOWING. | | | | | | SECTION 406.3 WASTE CONNECTIONS.THE TRAP AND FIXTURE | | | DRAIN FOR AN AUTOMATIC CLOTHES | | | WASHER SHALL BE A MINIMUM OF 2 INCHES | | | (51MM) IN DIAMETER. THE AUTOMATIC | | | CLOTHES WASHER FIXTURE DRAIN SHALL | | | CONNECT TO A BRANCH DRAIN OR DRAINAGE | | | STACK A MINIMUM OF 3 INCHES (76MM) IN | | | DIAMETER. | | | | | | SECTION 802.4 STANDPIPES.STANDPIPES SHALL BE | | | INDIVIDUALLY TRAPPED. STANDPIPES SHALL | | | EXTEND A MINIMUM OF 18 INCHES (457MM) | | | AND A MAXIMUM OF 42 INCHES (1066MM) | | | ABOVE THE TRAP WEIR. ACCESS SHALL BE | | | PROVIDED TO ALL STANDPIPES AND DRAINS | | | FOR RODDING. | | | NOTE: CLEARLY INDICATE THE REQUIRED STANDPIPE FOR THE | | | WASHING MACHINE. | | | | | | SECTION 708.7 MINIMUM SIZE. CLEANOUTS SHALL | | | BE THE SAME NOMINAL SIZE AS THE PIPE | | | THEY SERVE UP TO 4 INCHES (102MM) | | | NOTE: WASHING MACHINE CLEANOUT SHALL BE 3". | | | | | | SECTION 708.9 ACCESS. ACCESS SHALL BE | | | PROVIDED TO ALL CLEANOUTS. | | | NOTE: WASHING MACHINE CLEANOUT SHALL BE LOCATED AT 4' | | | A.F.F. | | | | | | E} CLEARLY INDICATE THE CLEANOUT AT THE JUNCTION OF | | | THE BUILDING DRAIN AND BUILDING SEWER AS BEING A | | | TWO-WAY CLEANOUT. PER SECTION 708.3.5. | | | | | | NOTE: PLEASE REFERENCE THE SANITARY ISOMETRIC EXAMPLE | | | THAT REFLECTS THE FLOOR PLAN AND IS CODE COMPLIANT | | | ATTACHED TO THESE PLUMBING COMMENTS FOR REFERENCE TO | | | ASSIST IN THE RESUBMITTAL. | | | | | | 2. SHEET A1 NEW FLOOR PLAN INDCATES ICE. IS THIS AN | | | ICE MAKER? NOTE: THE ICE MAKER MAY REQUIRE A DRAIN PIPE | | | FROM THE SANITARY SYSTEM. PLEASE SUBMIT TWO COPIES OF | | | ICE MAKER MANUFACTURE SHEETS AND DESIGN SANITARY SYSTEM | | | ACCORDINGLY IF A DRAIN IS REQUIRED. PER FBC- PLUMBING | | | SECTION 701.1 SCOPE. WHERE A TRAP SEAL IS SUBJECT TO | | | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE | | | INSTALLED. PER FBC- PLUMBING SECTION 1002.4 TRAP | | | SEALS. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-10-02 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2008-10-02 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2008-10-02 |
Time |
17:05 |
Sent To |
I |
|
| Notes |
| 2008-10-02 17:05:57 | PER ERIC SCHNEIDER, PRINCIPAL PLANNER. | | | | | | PLEASE NOTE THE FUTURE PRIVACY WALL SURROUNDING THE A/C | | | UNITS AND OTHER MECHANICAL EQUIPMENTS SHALL BE APPROVED | | | ON A SEPARATE PERMIT. | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-07-17 |
|
|
Cont ID |
|
| Sent By |
adavila |
Date |
2008-07-17 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
adavila |
Date |
2008-07-17 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2008-07-17 09:12:15 | PLANNING AND ZONING DEPARTMENT | | | | | | ***FAILED*** | | | | | | 1. THE SITE PLAN AND SURVEY DO NOT MATCH.ALL PLANS | | | SHALL SHOW SAME CONDITIONS.PLEASE REVISE. | | | | | | 2. REPEAT COMMENT - INDICATE SETBACK DIMENSIONS FROM | | | THE PROPOSED FRONT TRELLIS/WALL STRUCTURE TO ALL | | | ADJACENT PROPERTY LINES. | | | A. SETBACK DIMENSIONS WERE NOT PROVIDED FROM THE SIDE | | | PROPERTY LINES TO THE FURTHEST PROJECTION POINT OF THE | | | STRUCTURE.PROVIDE THESE DIMENSIONS | | | | | | 3. IDENTIFY THE ROUND OBJECT NEXT TO THE POOL | | | EQUIPMENT. | | | | | | 4. PLEASE STATE WHETHER THE POOL EQUIPMENT AND THE | | | ROUND OBJECT MENTIONED IN COMMENT NO. 3 ABOVE ARE | | | EXISTING OR PROPOSED.THESE ARE NOT SHOWN ON THE | | | SURVEY.IF PROPOSED, PROVIDE SETBACK DIMENSIONS FROM | | | THE PROPERTY LINES SHOWING COMPLIANCE WITH SECTION | | | 94-305(B)(4) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDRS). | | | | | | 5. FUTURE PRIVACY WALL SURROUNDING THE A/C UNITS AND | | | OTHER MECHANICAL EQUIPMENTS SHALL BE APPROVED ON A | | | SEPARATE PERMIT. | | | | | | 6. PROVIDE OVERHANG DIMENSIONS OF THE TRELLIS.PLEASE | | | NOTE THAT OVERHANGS SHALL NOT PROJECT MORE THAN 3 FEET | | | INTO ANY SETBACK PER SECTION 94-305(B)(2) OF THE | | | ZLDRS. | | | | | | COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC | | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-06-25 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-06-25 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-06-25 |
Time |
13:39 |
Sent To |
E |
|
| Notes |
| 2008-06-25 13:46:28 | ***FAILED*** | | | | | | | | | 1)INDICATE SETBACK DIMENSIONS FROM THE PROPOSED | | | FRONT TRELLIS/WALL STRUCTURE TO ALL ADJACENT PROPERTY | | | LINES. | | | | | | 2)CLARIFY SCOPE OF WORK.SOME DETAILS INDICATE THE | | | EASTERN PRIVACY WALL IS FUTURE WORK, OTHERS (SOUTH | | | ELEVATIONS ON SHEET A3) SHOW THE WALL AS "NEW WALL". IS | | | THIS STRUCTURE TO BE INCLUDED IN THIS SCOPE OF WORK OR | | | NOT?IF INCLUDED, INDICATE THE DIMENSION FROM THE | | | PROPERTY LINE AT WHICH THE WALL EXCEEDS 6 FEET IN | | | HEIGHT. | | | NOTE:WALLS/FENCES SHALL NOT EXCEED 6' IN HEIGHT | | | WITHIN THE REQUIRED SIDE/REAR SETBACK. | | | NOTE:THE HEIGHT DIMENSIONS OF THIS WALL STRUCTURE DO | | | NOT MATCH BETWEEN NORTH AND SOUTH ELEVATIONS. | | | | | | 3)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C | | | EQUIPMENT TO ALL ADJACENT PROPERTY LINES.AS PER | | | SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT | | | MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED | | | SETBACK. | | | | | | NOTE:ANY MECHANICAL EQUIPMENT ("FUTURE GENERATOR") IS | | | REQUIRED TO BE SETBACK A MINIMUM OF 5.1 FEET FROM THE | | | EASTERN SIDE PROPERTY LINE PURSUANT TO THE | | | AFOREMENTIONED CODE SECTION. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 | | | [email protected] | | | | | | | | | | | | | | | SENT TO "E" - SF RACK |
|
|