Plan Review Details - Permit 08060680
Plan Review Stops For Permit 08060680
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-09 Cont ID  
Sent By amorse Date 2008-10-09 Time 16:50 Rev Time 2.00
Received By amorse Date 2008-10-09 Time 15:55 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-09-13 Cont ID  
Sent By amorse Date 2008-09-13 Time 09:42 Rev Time 0.00
Received By amorse Date 2008-09-13 Time 09:42 Sent To PC
Notes
2008-09-13 09:44:06 
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE 1ST
 REVIEW
  
  
 2) PLEASE SEE CHAPTER 6 FBC TO CORRECTLY DETERMINE THE
 TYPE OF CONSTRUCTION
 ******GENERALLY THE MIN REQUIRED TYPE WOULD BE USE TYPE
 VB, THE TYPE CHOSEN IS FOR HEAVY TIMBER CONSTRUCTION
 (IV)******
 3) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 NEW REVIEW COMMENTS
  
 1) PROVIDE PRODUCT APPROVAL FOE MULLIONS THAT WOULD BE
 REQUIRED BETWEEN CASEMENT UNITS AND BETWEEN
 CASEMENTS/FIXED IN MASTER BEDROOM. PLEASE SEE
 MIAMI-DADE NOA #04-0603.04
  
 2) ONLY ONE SET OF NEW DRAWINGS WAS SUBMITTED PROVIDE 2
 COPIES OF ALL CONSTRUCTION DOCUMENTS.
  
 3) THE STATEWIDE PRODUCT APPROVAL NUMBERS FOR ALL OF
 THE YYK PRODUCTS ARE NO LONGER POSTED ON THE SITE AND
 THE MIAMI-DADE REPORT FOR THE CASEMENTS HAS EXPIRED,
 THERE ARE NEW STATE APPROVALS AVAILABLE ALTHOUGH WE NO
 LONGER REQUIRE THEM AND THEIR ARE UPDATED MIAMI-DADE
 NOA'S ALSO AVAILABLE. BEFORE PRINTING AND HAVING THEM
 REVIEWED BY THE DESIGNER OF RECORD PLEASE BE SURE YOU
 ONLY SUBMIT WHAT IS BEING USED, FOR EXAMPLE THE MASTER
 BEDROOM WINDOW LOOKS LIKE CASEMENTS OVER FIXED BUT
 DRAWING STATE CASEMENT OVER CASEMENT PLEASE CLARIFY AND
 PROVIDE CORRECT PRODUCT APPROVALS. ALSO THE YYK UNIT
 CAN BE INSTALLED AS ONE UNIT WITH INTEGRAL MULLION OR
 IF USING OTHER MANUFACTURER SUCH AS NUAIR THEN MULLIONS
 WOULD BE REQUIRED.
  
 4) REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 WITH REVISIONS AND INCLUDE 1 COPY OF THE MOST RESENT
 OLD PAGES ONLY FOR REFERENCE. REMOVE ALL NON USED
 PRODUCT APPROVAL FROM SUBMITTALS, WITH YYK CASEMENT AND
 FIXED WINDOWS FOR MASTER WHERE IS THE NUAIR PRODUCT
 BEING USED?
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-04 Cont ID  
Sent By amorse Date 2008-07-04 Time 14:04 Rev Time 0.00
Received By amorse Date 2008-07-04 Time 14:04 Sent To PC
Notes
2008-07-04 14:50:17 
  
 DENIED
  
 1) PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 & 2007
 AMENDMENTS PER 106.1.1 FBC*
  
 2) PLEASE SEE CHAPTER 6 FBC TO CORRECTLY DETERMINE THE
 TYPE OF CONSTRUCTION
  
 3) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 5) THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 6) THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9B-72
 (PRODUCT APPROVALS) SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 7) THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL SHEETS WHEN AVAILABLE. THEY CAN
 BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG. WHEN
 AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
  
 8) NO PRODUCT APPROVALS WERE SUBMITTED FOR STORE FRONT
 WINDOW/DOOR UNIT IN LIVINGROOM, CASEMENT/AWNING WINDOWS
 UNDER FIXED WINDOW IN MASTER BEDROOM AND MULLIONS IF
 REQUIRED
  
 9) THE PRODUCT APPROVAL FOR THE YKK FIXED WINDOW IS
 INCOMPLETE
  
 10) NEW MASTER BEDROOM WINDOW DOES NOT MEET EMERGENCY
 EGRESS REQUIREMENTS PER R310 FBC: MIN. NET CLEAR
 OPENING OF 5 SQ.FT. ON GRADE FLOOR. MIN. NET CLEAR
 OPENING ALL OTHER FLOORS OF 5.7 SQ.FT. IN BOTH CASES
 THE MIN.NET CLEAR HEIGHT SHALL BE 24" AND THE NET CLEAR
 WIDTH SHALL BE 20"
  
 11) IF WOOD BUCKS ARE TO BE USED AN ATTACHMENT DETAIL
 IS REQUIRED FOR THE TRANSFER OF APPLICABLE LOADS TO THE
 BUILDING PER R613.6.1.1 FBC RES.
 AS THE PRODUCT APPROVALS DO NOT SPECIFY ANY ATTACHMENT
 METHOD
  
 12) THE OPENING FOR THE WINDOW IN THE MASTER BEDROOM
 HAS BEEN MADE SMALLER AND THE DOOR/WINDOW UNIT IN THE
 LIVINGROOM IS LARGER, SUBMIT STRUCTURAL WALL CHANGES TO
 ALLOW FOR THE ATTACHMENT OF THE NEW GLAZED UNITS
  
 13) PROVIDE ATTACHMENT DETAILS FOR THE NEW ALUMINUM
 TRELLIS AT EXISTING HOUSE AND TOP OF NEW SCREEN WALL
  
 14) CLARIFY SCREEN FENCE HEIGHTS, LEGEND ON SHEET A1
 STATES PRIVACY WALL AT 5'-0" AND ELEVATIONS ON A3 SOUTH
 ELEVATION IS 5'-10" AND NORTH ELEVATION IS 6'-0" THESE
 ELEVATIONS ALSO STATE THE FRONT WALL AS NEW AND THE
 REAR WALL AS FUTURE
  
 15) PLEASE KEEP PERMIT APPLICATION AND DRAWING SCOPE OF
 WORK THE SAME, REMOVE ALL FUTURE WORK FROM THE DRAWINGS
 TO ALLEVIATE COMMENTS IN PLAN REVIEW, ALSO NOTE ZONING
 COMMENTS ON THE LOCATION OF THE PROPOSED GENERATOR
  
 16) PLEASE MAKE CORRECTIONS TO THE FOUNDATION PLANS,
 PER 106.1.3 FBC* THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK"
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-10-06 Cont ID  
Sent By btrobaug Date 2008-10-06 Time 16:39 Rev Time 0.00
Received By btrobaug Date 2008-10-06 Time 16:01 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-07-22 Cont ID  
Sent By btrobaug Date 2008-07-22 Time 08:38 Rev Time 0.00
Received By btrobaug Date 2008-07-21 Time 16:28 Sent To M
Notes
2008-07-22 08:38:38 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THE FOLLOWING COMMENTS ARE FROM THE PREVIOUS REVIEW AND
 HAD INCORRECT OR NO RESPONSE.
  
 1} THE 250 MCM CONDUCTORS FEEDING THE 400 AMP MDP DO
 NOT COMPLY WITH 310.15(B)(6), NEED TO BE A MINIMUM OF
 400 MCM FOR A 400 AMP SERVICE. NOTE: THE MAIN IS 200
 AMP AND THE NOTE ON THE CALCULATIONS INDICATE A 200 AMP
 SERVICE. CORRELATE THE RISER.***THERE ARE 250 MCM
 FEDING THE 200 AMP MAIN AND NOW 400 MCM FEEDING THE
 "MDP" WHICH IS ALSO RATED AT 200 AMPS.THE 400 MCM
 THOUGH NOT A VIOLATION, MUST BE INSTALLED IF THE
 DESIGNER CHOOSES TO USE THEM. A REVISION WILL BE
 REQUIRED TO CHANGE THE PLAN IN THE FUTURE.
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE
 REVIEWED.WHERE IS THE MDP LOCATED ?*** STILL NOT SHOWN
 ON THE PLAN.
  
 9} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A)
 (3).***ONLY ONE AHU IS SHOWN AND TWO COMPRESSERS.PLEASE
 CLARIFY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-26 Cont ID  
Sent By btrobaug Date 2008-06-26 Time 10:44 Rev Time 0.00
Received By btrobaug Date 2008-06-26 Time 08:23 Sent To P
Notes
2008-06-26 09:33:48 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE 250 MCM CONDUCTORS FEEDING THE 400 AMP MDP DO
 NOT COMPLY WITH 310.15(B)(6), NEED TO BE A MINIMUM OF
 400 MCM FOR A 400 AMP SERVICE. NOTE: THE MAIN IS 200
 AMP AND THE NOTE ON THE CALCULATIONS INDICATE A 200 AMP
 SERVICE. CORRELATE THE RISER.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66.THE SERVICE CONDUCTORS DETERMINE THIS. SEE
 ARTICLE.
  
 3} A NOTE AT THE RISER INDICATES THE SERVICE IS LOCATED
 ON THE GARAGE. THE PLAN SHOWS A METER AND DISCONNECTS
 OUTSIDE THE KITCHEN WALL.
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE
 REVIEWED.WHERE IS THE MDP LOCATED ?
  
 5} INDICATE THE GENERATOR TO BE FUTURE ON THE RISER AS
 A SEPARATE PERMIT IS REQUIRED WITH ALL SUPPORTING
 DOCUMENTS FOR THAT PERMIT.
  
 6} THERE APPEARS TO BE AN ELECTRICAL PANEL IN THE
 STORAGE ROOM, LABEL SAME. SEE ARTICLES 408.17 AND
 240.24(D).
  
 7} LABEL THE PANEL SCHEDULE INDICATING IF IT IS FOR MDP
 OR PANEL "A". GIVE A PANEL SCHEDULE FOR ALL PANELS.
 408.4.
  
 8} THE DISPOSAL AND MICROWAVE ON THE PANEL SCHEDULE ARE
 NOT IN THE LOAD CALCULATIONS.220
  
 9} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A)
 (3).
  
 10} THERE WERE TWO SHEET A3 SUBMITTED. REMOVE THE SHEET
 THAT IS NOT TO BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-26 Cont ID  
Sent By adarroug Date 2008-09-26 Time 15:24 Rev Time 0.00
Received By adarroug Date 2008-09-26 Time 15:24 Sent To Z
Notes
2008-09-26 15:25:39TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-08-28 Cont ID  
Sent By tgordon Date 2008-08-28 Time 13:54 Rev Time 0.00
Received By tgordon Date 2008-08-28 Time 13:54 Sent To Z
Notes
2008-08-28 13:55:26TO "ZONING"BOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-18 Cont ID  
Sent By adarroug Date 2008-07-18 Time 14:10 Rev Time 0.00
Received By adarroug Date 2008-07-18 Time 14:10 Sent To E
Notes
2008-07-18 14:11:37TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-10 Cont ID  
Sent By adarroug Date 2008-07-10 Time 15:12 Rev Time 0.00
Received By adarroug Date 2008-07-10 Time 15:12 Sent To Z
Notes
2008-07-10 15:13:35TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-07-04 Time   Rev Time 0.00
Received By adarroug Date 2008-06-25 Time 10:54 Sent To  
Notes
2008-06-25 10:57:01TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2008-10-08 Cont ID  
Sent By tgordon Date 2008-10-08 Time 09:25 Rev Time 0.30
Received By tgordon Date 2008-10-08 Time 09:25 Sent To P
Notes
2008-10-08 09:26:27NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-07-22 Cont ID  
Sent By tgordon Date 2008-07-22 Time 10:32 Rev Time 0.30
Received By tgordon Date 2008-07-22 Time 10:32 Sent To P
Notes
2008-07-22 10:47:47PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) AS NOTED IN LAST REVIEW 6-25-08. PLAN A1 NEW FLOOR
 PLAN SHOWS A GAS WATER HEATER (APPEARS TO BE A
 TANKLESS) IN THE NEW STORAGE ROOM. THIS APPEARS TO BE A
 CONFINED SPACE, PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR GAS
 WATER HEATER AND STATE WERE IT'S GETTING THE COMBUSTION
 AIR FROM, IF NOT A GAS WATER HEATER CORRECT PLANS PAGES
 A1 AND A2, PER 2004 FBC/R G2407.1.
  
 2) AS NOTED IN LAST REVIEW 6-25-08. PLAN A1 NEW FLOOR
 PLAN SHOWS THE AIR HANDLER BEING RELOCATED TO THE NEW
 A/C CLOSET, PLEASE SUBMIT A MECHANICAL PLAN SHOWING THE
 SUPPLY AND RETURN AIR DUCTS THAT ARE BEING ALTERED, PER
 2004 FBC/R M1601.1.
  
 3) AS NOTED IN LAST REVIEW 6-25-08. PLAN A2 ELECTRICAL
 PLAN IS LABELING THE A/C CONDENSER UNITS AS A.H.U. (AIR
 HANDLER UNIT), PLEASE CORRECT PER 2004 FBC/R, CH. 13
 ANDFBC 106.1.1.
  
 4) PLAN A1 AND A2 SHOW A A/C CONDENSER UNIT LABELED
 FUTURE AHU, PLEASE REMOVE FROM PLANS OR SHOW THE
 COMPLETE SYSTEM IT IS GOING TO, PER 2004 WPB AMEND.
 106.3.5.4 (10).
  
 5) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, SEE F.B.C. 106.1.1.
  
 6) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-25 Cont ID  
Sent By tgordon Date 2008-06-25 Time 14:29 Rev Time 0.45
Received By tgordon Date 2008-06-25 Time 14:29 Sent To E
Notes
2008-06-25 14:56:13PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT A MECHANICAL (A/C) PLAN, PER 2004 WPB
 AMEND. 106.3.5.4 (10).
  
 2) PLAN A1 NEW FLOOR PLAN SHOWS A GAS WATER HEATER
 (APPEARS TO BE A TANKLESS) IN THE NEW STORAGE ROOM.
 THIS APPEARS TO BE A CONFINED SPACE, PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR GAS WATER HEATER AND STATE WERE IT'S
 GETTING THE COMBUSTION AIR FROM, PER 2004 FBC/R
 G2407.1.
  
 3) PLAN A1 NEW FLOOR PLAN SHOWS THE AIR HANDLER BEING
 RELOCATED TO THE NEW A/C CLOSET, PLEASE SHOW ON THE NEW
 MECHANICAL PLAN BEING SUBMITTED THE SUPPLY AND RETURN
 AIR DUCTS, PER 2004 FBC/R M1601.1.
  
 4) PLAN A2 TOTAL BUILDING LOAD CALCULATIONS STATES THE
 CLOTHES DRYER IS GAS, THE ELECTRICAL PLAN SHOWS A 220V
 OUTLET FOR IT. PLEASE CLARIFY ON THE PLANS IF THE
 CLOTHES DRYER IS GAS OR ELECTRIC, PER 2004 FBC/R
 G2407.1 AND FBC 106.1.1.
  
 5) PLAN A2 ELECTRICAL PLAN IS LABELING THE A/C
 CONDENSER UNITS AS A.H.U. (AIR HANDLER UNIT), PLEASE
 CORRECT PER 2004 FBC/R, CH. 13 ANDFBC 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-10-08 Cont ID  
Sent By mperson Date 2008-10-08 Time 11:20 Rev Time 0.45
Received By mperson Date 2008-10-08 Time 11:20 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-07-28 Cont ID  
Sent By mperson Date 2008-07-28 Time 10:08 Rev Time 0.00
Received By mperson Date 2008-07-28 Time 10:08 Sent To B
Notes
2008-07-28 11:31:47PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
 NOTE: THERE WERE NO COMMET RESPONSES FROM THE DESIGNER
 AND NONE OF THE PREVIOUS PLUMBING REVIEW COMMENTS WERE
 ADDRESSED
  
 1. SHEET A3 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN OF SHEET A1 AND IS NOT CODE
 COMPLIANT PER FBC- PLUMBING THE FOLLOWING SECTIONS.
  
 A} BATHTUB MISSING FROM RISER DIAGRAM. PER SECTIONS
 401.1 AND 701.1 SCOPE.
  
 B} BOTH SINKS IN THE KITCHEN REQUIRE VENTS. PER
 SECTION 901.2.1 VENTING REQUIRED.
  
 C} SINK IN THE LAUNDRY REQUIRES A VENT. PER 901.2.1
 VENTING REQUIRED.
  
 D} THE WASHING MACHINE IS DESIGNED WITH A PROHIBITED
 "S" TRAP. PER SECTION 1002.3 PROHIBITED TRAPS (5). THE
 WASHING MACHINE REQUIRES A VENT. PER SECTION 901.2.1
 VENTING REQUIRED.
 NOTE: PLEASE DESIGN THE WASHING MACHINE PER THE
 FOLLOWING.
  
 SECTION 406.3 WASTE CONNECTIONS.THE TRAP AND FIXTURE
 DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 SECTION 802.4 STANDPIPES.STANDPIPES SHALL BE
 INDIVIDUALLY TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 NOTE: CLEARLY INDICATE THE REQUIRED STANDPIPE FOR THE
 WASHING MACHINE.
  
 SECTION 708.7 MINIMUM SIZE. CLEANOUTS SHALL BE THE
 SAME NOMINAL SIZE AS THE PIPE THEY SERVE UP TO 4 INCHES
 (102MM)
 NOTE: WASHING MACHINE CLEANOUT SHALL BE 3".
  
 SECTION 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: WASHING MACHINE CLEANOUT SHALL BE LOCATED AT 4'
 A.F.F.
  
 E} "OK" COMMENT ADDRESSED.
  
 2. SHEET A1 NEW FLOOR PLAN INDCATES ICE. IS THIS AN
 ICE MAKER? NOTE: THE ICE MAKER MAY REQUIRE A DRAIN PIPE
 FROM THE SANITARY SYSTEM. PLEASE SUBMIT TWO COPIES OF
 ICE MAKER MANUFACTURE SHEETS AND DESIGN SANITARY SYSTEM
 ACCORDINGLY IF A DRAIN IS REQUIRED. PER FBC- PLUMBING
 SECTION 701.1 SCOPE. WHERE A TRAP SEAL IS SUBJECT TO
 LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. PER FBC- PLUMBING SECTION 1002.4 TRAP
 SEALS.
  
 **THE FOLLOWING ARE NEW COMMENTS
  
 3. SHEET A1 SCOPE OF WORK INDICATES IN THE GUEST
 BEDROOM (NEW MASTER CLOSET) ADD DRAINS AND CAP FOR
 SINKS (FUTURE APPLICATION) AND ADD WC WASTE LINE AND
 CAP (FUTURE USE). THESE FUTURE FIXTURES AND LAYOUT MUST
 BE INDICATED ON THE PROPOSED NEW FLOOR PLAN AND THE
 SANITARY WASTE, VENTS, TRAPS AND CLEANOUTS WITH SIZES
 MUST BE CLEALY INDICATED ON THE SANITARY RISER DIAGRAM
 FOR THESE FUTURE FIXTURES ON SHEET A3. PER (W.P.B. AS
 AMENDED) SECTION 106.3.5.4(9) PLUMBING AND FBC-2004
 PLUMBING SECTION 701.1, AND SECTION 901.1 SCOPE.
  
 4. SHEET A1 INDICATES GAS APPLIANCES (GAS W.H.& GAS
 RANGE): PLEASE KNOW THAT A GAS PERMIT IS REQUIRED FOR
 THIS WORK. A LICENSED GAS OR PLUMBING CONTRACTOR SHALL
 SUBMIT PLANS WITH PERMIT APPLICATION. ALL GAS
 INSPECTIONS ARE TO BE COMPLETE BEFORE THE FINAL
 INSPECTION.
  
 5. SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR
 TIMES THE FEE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-02 Cont ID  
Sent By mperson Date 2008-07-02 Time 10:05 Rev Time 0.00
Received By mperson Date 2008-07-02 Time 10:05 Sent To B
Notes
2008-07-02 10:35:39PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. SHEET A3 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN OF SHEET A1 AND IS NOT CODE
 COMPLIANT PER FBC- PLUMBING THE FOLLOWING SECTIONS.
  
 A} BATHTUB MISSING FROM RISER DIAGRAM. PER SECTIONS
 401.1 AND 701.1 SCOPE.
  
 B} BOTH SINKS IN THE KITCHEN REQUIRE VENTS. PER
 SECTION 901.2.1 VENTING REQUIRED.
  
 C} SINK IN THE LAUNDRY REQUIRES A VENT. PER 901.2.1
 VENTING REQUIRED.
  
 D} THE WASHING MACHINE IS DESIGNED WITH A PROHIBITED
 "S" TRAP. PER SECTION 1002.3 PROHIBITED TRAPS (5). THE
 WASHING MACHINE REQUIRES A VENT. PER SECTION 901.2.1
 VENTING REQUIRED.
 NOTE: PLEASE DESIGN THE WASHING MACHINE PER THE
 FOLLOWING.
  
 SECTION 406.3 WASTE CONNECTIONS.THE TRAP AND FIXTURE
 DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 SECTION 802.4 STANDPIPES.STANDPIPES SHALL BE
 INDIVIDUALLY TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 NOTE: CLEARLY INDICATE THE REQUIRED STANDPIPE FOR THE
 WASHING MACHINE.
  
 SECTION 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: WASHING MACHINE CLEANOUT SHALL BE 3".
  
 SECTION 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: WASHING MACHINE CLEANOUT SHALL BE LOCATED AT 4'
 A.F.F.
  
 E} CLEARLY INDICATE THE CLEANOUT AT THE JUNCTION OF
 THE BUILDING DRAIN AND BUILDING SEWER AS BEING A
 TWO-WAY CLEANOUT. PER SECTION 708.3.5.
  
 NOTE: PLEASE REFERENCE THE SANITARY ISOMETRIC EXAMPLE
 THAT REFLECTS THE FLOOR PLAN AND IS CODE COMPLIANT
 ATTACHED TO THESE PLUMBING COMMENTS FOR REFERENCE TO
 ASSIST IN THE RESUBMITTAL.
  
 2. SHEET A1 NEW FLOOR PLAN INDCATES ICE. IS THIS AN
 ICE MAKER? NOTE: THE ICE MAKER MAY REQUIRE A DRAIN PIPE
 FROM THE SANITARY SYSTEM. PLEASE SUBMIT TWO COPIES OF
 ICE MAKER MANUFACTURE SHEETS AND DESIGN SANITARY SYSTEM
 ACCORDINGLY IF A DRAIN IS REQUIRED. PER FBC- PLUMBING
 SECTION 701.1 SCOPE. WHERE A TRAP SEAL IS SUBJECT TO
 LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. PER FBC- PLUMBING SECTION 1002.4 TRAP
 SEALS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-10-02 Cont ID  
Sent By adavila Date 2008-10-02 Time 17:05 Rev Time 0.00
Received By adavila Date 2008-10-02 Time 17:05 Sent To I
Notes
2008-10-02 17:05:57PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 PLEASE NOTE THE FUTURE PRIVACY WALL SURROUNDING THE A/C
 UNITS AND OTHER MECHANICAL EQUIPMENTS SHALL BE APPROVED
 ON A SEPARATE PERMIT.
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2008-07-17 Cont ID  
Sent By adavila Date 2008-07-17 Time 09:11 Rev Time 0.00
Received By adavila Date 2008-07-17 Time 09:11 Sent To  
Notes
2008-07-17 09:12:15PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. THE SITE PLAN AND SURVEY DO NOT MATCH.ALL PLANS
 SHALL SHOW SAME CONDITIONS.PLEASE REVISE.
  
 2. REPEAT COMMENT - INDICATE SETBACK DIMENSIONS FROM
 THE PROPOSED FRONT TRELLIS/WALL STRUCTURE TO ALL
 ADJACENT PROPERTY LINES.
 A. SETBACK DIMENSIONS WERE NOT PROVIDED FROM THE SIDE
 PROPERTY LINES TO THE FURTHEST PROJECTION POINT OF THE
 STRUCTURE.PROVIDE THESE DIMENSIONS
  
 3. IDENTIFY THE ROUND OBJECT NEXT TO THE POOL
 EQUIPMENT.
  
 4. PLEASE STATE WHETHER THE POOL EQUIPMENT AND THE
 ROUND OBJECT MENTIONED IN COMMENT NO. 3 ABOVE ARE
 EXISTING OR PROPOSED.THESE ARE NOT SHOWN ON THE
 SURVEY.IF PROPOSED, PROVIDE SETBACK DIMENSIONS FROM
 THE PROPERTY LINES SHOWING COMPLIANCE WITH SECTION
 94-305(B)(4) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS).
  
 5. FUTURE PRIVACY WALL SURROUNDING THE A/C UNITS AND
 OTHER MECHANICAL EQUIPMENTS SHALL BE APPROVED ON A
 SEPARATE PERMIT.
  
 6. PROVIDE OVERHANG DIMENSIONS OF THE TRELLIS.PLEASE
 NOTE THAT OVERHANGS SHALL NOT PROJECT MORE THAN 3 FEET
 INTO ANY SETBACK PER SECTION 94-305(B)(2) OF THE
 ZLDRS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-25 Cont ID  
Sent By choops Date 2008-06-25 Time 13:39 Rev Time 0.00
Received By choops Date 2008-06-25 Time 13:39 Sent To E
Notes
2008-06-25 13:46:28***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM THE PROPOSED
 FRONT TRELLIS/WALL STRUCTURE TO ALL ADJACENT PROPERTY
 LINES.
  
 2)CLARIFY SCOPE OF WORK.SOME DETAILS INDICATE THE
 EASTERN PRIVACY WALL IS FUTURE WORK, OTHERS (SOUTH
 ELEVATIONS ON SHEET A3) SHOW THE WALL AS "NEW WALL". IS
 THIS STRUCTURE TO BE INCLUDED IN THIS SCOPE OF WORK OR
 NOT?IF INCLUDED, INDICATE THE DIMENSION FROM THE
 PROPERTY LINE AT WHICH THE WALL EXCEEDS 6 FEET IN
 HEIGHT.
 NOTE:WALLS/FENCES SHALL NOT EXCEED 6' IN HEIGHT
 WITHIN THE REQUIRED SIDE/REAR SETBACK.
 NOTE:THE HEIGHT DIMENSIONS OF THIS WALL STRUCTURE DO
 NOT MATCH BETWEEN NORTH AND SOUTH ELEVATIONS.
  
 3)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL ADJACENT PROPERTY LINES.AS PER
 SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.
  
 NOTE:ANY MECHANICAL EQUIPMENT ("FUTURE GENERATOR") IS
 REQUIRED TO BE SETBACK A MINIMUM OF 5.1 FEET FROM THE
 EASTERN SIDE PROPERTY LINE PURSUANT TO THE
 AFOREMENTIONED CODE SECTION.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
 [email protected]
  
  
  
  
 SENT TO "E" - SF RACK