Plan Review Details - Permit 08060631
Plan Review Stops For Permit 08060631
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-12 Cont ID  
Sent By amorse Date 2008-08-12 Time 16:14 Rev Time 0.00
Received By amorse Date 2008-08-12 Time 16:14 Sent To E
Notes
2008-08-12 16:15:09 
  
 SENT TO ELECTRICAL ON 8/12/08

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-09 Cont ID  
Sent By amorse Date 2008-08-09 Time 12:32 Rev Time 0.00
Received By amorse Date 2008-08-09 Time 12:32 Sent To PC
Notes
2008-08-09 12:48:32 
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM THE
 FIRST REVIEW
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $ 71.01 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 NEW COMMENTS
  
 1)PER 106.1 OF THE CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1, FBC 2 OR MORE SETS OF ALL CONSTRUCTION
 DOCUMENTS ARE REQUIRED TO BE SUBMITTED WITH THE PERMIT
 APPLICATION. ONLY ONE SET OF PLANS WERE SUBMITTED.
  
 2)ENGINEERED TRUSS DRAWINGS ARE REQUIRED TO BE
 SUBMITTED OR GIVEN TO SITE INSPECTOR PRIOR TO SETTING
 TRUSSES.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-04 Cont ID  
Sent By amorse Date 2008-07-04 Time 10:44 Rev Time 0.00
Received By amorse Date 2008-07-04 Time 10:44 Sent To PC
Notes
2008-07-04 11:41:48 
  
 DENIED
  
 1)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR
 SETBACKS, PLEASE NOTE THE EXISTING SURVEY FRONT SETBACK
 DISTANCE, THE PROPOSED NEW PORCH WOULD ENCROACH INTO
 REQUIRED 25'-0" SETBACK. PLEASE SEE ZONING COMMENTS
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
 THE VALUE SHALL INCLUDE ALL COSTS SUCH AS PERMITS,
 DRAWINGS AND ACTUAL CONSTRUCTION COSTS
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 4)EXTERIOR KNEE WALL DOES NOT SPECIFY SHEATHING
 AND/OR WEATHER RESISTANT SHEATHING PAPER
  
 5)SUBMIT A COPY OF THE RECORDED NOTICE OF
 COMMENCEMENT TO THE CONSTRUCTION SERVICES DEPARTMENT
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-08-15 Cont ID  
Sent By btrobaug Date 2008-08-15 Time 12:01 Rev Time 0.00
Received By btrobaug Date 2008-08-15 Time 11:52 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-08-06 Cont ID  
Sent By btrobaug Date 2008-08-06 Time 13:38 Rev Time 0.00
Received By btrobaug Date 2008-08-05 Time 14:41 Sent To B
Notes
2008-08-06 13:38:50 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 SECTION 106
 CONSTRUCTION DOCUMENTS
 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS,
 SPECIAL INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS,
 AND OTHER DATA SHALL BE SUBMITTED IN ONE TWO OR MORE
 SETS WITH EACH APPLICATION FOR A PERMIT.***ONLY ONE SET
 OF 1.2, 2.2 AND E-1 WERE SUBMITTED
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-06-25 Cont ID  
Sent By btrobaug Date 2008-06-25 Time 15:04 Rev Time 0.00
Received By btrobaug Date 2008-06-25 Time 15:01 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-29 Cont ID  
Sent By adarroug Date 2008-07-29 Time 14:26 Rev Time 0.00
Received By adarroug Date 2008-07-29 Time 14:26 Sent To E
Notes
2008-07-29 14:26:50TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-07-04 Time   Rev Time 0.00
Received By adarroug Date 2008-06-23 Time 15:12 Sent To  
Notes
2008-06-23 15:14:10TO "SFR" "Z"

Review Stop Z ZONING
Rev No 2 Status P Date 2008-08-03 Cont ID  
Sent By mcruz Date 2008-08-03 Time 10:49 Rev Time 0.00
Received By mcruz Date 2008-08-03 Time 10:48 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-24 Cont ID  
Sent By choops Date 2008-06-24 Time 11:36 Rev Time 0.00
Received By choops Date 2008-06-24 Time 11:36 Sent To E
Notes
2008-06-24 11:40:33***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF THE PROVIDED SURVEY.
  
 2)INDICATE SETBACK DIMENSIONS FROM THE PROPOSED
 ADDITION TO ALL ADJACENT PROPERTY LINES.
  
 NOTE:MINIMUM REQUIRED FRONT SETBACK = 25',
 NOTE:OVERHANGS MAY PROJECT NO MORE THAN 3' INTO A
 REQUIRED SETBACK.
  
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
 [email protected]
  
  
  
  
 SENT TO "E" - SF RACK