Plan Review Details - Permit 08060598
Plan Review Stops For Permit 08060598
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-07 Cont ID  
Sent By mjacobs Date 2008-08-07 Time 10:26 Rev Time 0.00
Received By mjacobs Date 2008-08-07 Time 10:26 Sent To PC
Notes
2008-08-07 10:27:05PROCESS PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-01 Cont ID  
Sent By mjacobs Date 2008-08-01 Time 07:07 Rev Time 0.00
Received By mjacobs Date 2008-07-31 Time 15:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-30 Cont ID  
Sent By mjacobs Date 2008-06-27 Time 14:51 Rev Time 0.00
Received By mjacobs Date 2008-06-26 Time 15:25 Sent To  
Notes
2008-06-27 09:04:23BUILDING PLAN REVIEW
 PERMIT: 08060598
 ADD: 580 VILLAGE BLVD. #315
 CONT: RYBEK CONSTRUCTION INC.
 TEL: (561)798-5122
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 6-27-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 3)THE OCCUPANCY TYPE INDICATED ON THE PLANS IS
 BUSINESS/ ORDINARY HAZARD. THE OF TYPES OF HAZARDOUS
 GROUPS MENTION IN THE FBC 2004 SECTION 306 ARE F-1
 MODERATE-HAZARD/ F-2 LOW-HAZARD AND F-3 WHICH IS A
 SPECIAL PURPOSE FACTORY INDUSTRIAL OCCUPANCY. THEN
 THERE IS THE HIGH HAZARD IN SECTION 307. ONE OF THE
 ABOVE MENTION GROUPS SHALL BE CHOSEN INSTEAD OF
 ORDINARY HAZARD. IF THIS IS BUSINESS ONLY, REMOVE THE
 ORDINARY HAZARD FROM THE DRAWINGS.
  
 4)FBC 106.3.5.1.1(5) FIRE SPRINKLER PLANS REQUIRED TO
 SHOW THE LAYOUT OF THE SPRINKLER HEADS IN RELATION THE
 RENOVATION. THE LAYOUT OF THE SPRINKLER HEADS MAY BE
 SHOWN ON THE REFLECTED CEILING PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-07-22 Cont ID  
Sent By btrobaug Date 2008-07-22 Time 16:00 Rev Time 0.00
Received By btrobaug Date 2008-07-22 Time 15:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-06-23 Cont ID  
Sent By btrobaug Date 2008-06-23 Time 15:39 Rev Time 0.00
Received By btrobaug Date 2008-06-23 Time 15:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-08-01 Cont ID  
Sent By mwennerg Date 2008-08-01 Time 10:54 Rev Time 0.00
Received By mwennerg Date 2008-08-01 Time 10:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-30 Cont ID  
Sent By mwennerg Date 2008-06-30 Time 15:01 Rev Time 0.00
Received By mwennerg Date 2008-06-30 Time 15:01 Sent To  
Notes
2008-06-30 15:08:21***DENIED***
  
 1) PLEASE SEE BUILDING COMMENT #4 REGARDING FIRE
 SPRINKLER LAYOUT. ADDITIONALLY, SEPARATE SHOP DRAWINGS
 AND PERMIT REQUIRED FOR FIRE SPRINKLER REMODEL PRIOR TO
 WORK.
  
 2) IF BUILDING HAS EXISTING FIRE ALARM SYSTEM, A STROBE
 IS REQUIRED IN CONFERENCE ROOM.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-17 Cont ID  
Sent By adarroug Date 2008-07-17 Time 11:05 Rev Time 0.00
Received By adarroug Date 2008-07-17 Time 11:05 Sent To  
Notes
2008-07-17 11:09:21TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-30 Cont ID  
Sent By mwennerg Date 2008-06-30 Time 15:13 Rev Time 0.00
Received By mwennerg Date 2008-06-20 Time 16:37 Sent To  
Notes
2008-06-20 16:38:15TO "BOB"#3

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-07-21 Cont ID  
Sent By tgordon Date 2008-07-21 Time 09:30 Rev Time 0.40
Received By tgordon Date 2008-07-21 Time 09:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-24 Cont ID  
Sent By tgordon Date 2008-06-24 Time 10:54 Rev Time 0.45
Received By tgordon Date 2008-06-24 Time 10:54 Sent To  
Notes
2008-06-24 10:57:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PROVIDE FOR RETURN AIR TO THE FOLLOWING OFFICES #2,
 3, 4, AND 5. PER 2004 FBC/M 601.4.
  
 2) SHOW THE CFM'S AT THE TWO NEW SUPPLY AIR GRILLS, PER
 2004 FBC 106.3.5.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-06-24 Cont ID  
Sent By choops Date 2008-06-24 Time 14:33 Rev Time 0.00
Received By choops Date 2008-06-24 Time 14:33 Sent To  
Notes
2008-06-24 14:33:43*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.