Plan Review Details - Permit 08060580
Plan Review Stops For Permit 08060580
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-08-13 Cont ID  
Sent By mperson Date 2008-08-13 Time 11:33 Rev Time 0.00
Received By mperson Date 2008-08-13 Time 11:33 Sent To PC
Notes
2008-08-13 11:35:20REVISION: "OK" CHANGED PIPE SIZE FROM 1" TO 1-1/4" AND
 INCREASED VALUE.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-07-03 Cont ID  
Sent By mperson Date 2008-07-03 Time 14:52 Rev Time 0.00
Received By mperson Date 2008-07-03 Time 14:52 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-06-23 Cont ID  
Sent By mperson Date 2008-06-23 Time 08:09 Rev Time 0.00
Received By mperson Date 2008-06-23 Time 08:08 Sent To I
Notes
2008-06-23 08:39:17GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 NOTE: SUBMITTED DRAWING IS NOT INDICATING
 CORROSPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER-2004 FBC FUEL
 GAS SECTION 401.1 SCOPE.
 NOTE: SUBMITTED DRAWING DOES NOT INDICATE ANY PIPING
 MATERIALS BEING INSTALLED.
  
 3. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 BEING USED ON THE DRAWINGS. PER FBC-2004 FUEL GAS
 SECTION 401.1 SCOPE.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #1.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: A PERMIT INFORMATION SEARCH OF SAID ADDRESS DOES
 NOT INDICATE AN APPROVED POOL PERMIT WITH A POOL
 HEATER. PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS
 FOR THE PROPOSED POOL HEATER CLEARLY INDICATING THE
 MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LAORATORY.
  
 6. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 7. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW.
 THE VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE
 TOTAL COST OF LABOR AND MATERIALS. VALUATION REFERENCES
 MAY INCLUDE THE LATEST PUBLISHED DATA OF A NATIONAL
 CONSTRUCTION COST ANALYSIS (MARSHALL-SWIFT, MEANS,
 ECT...) ADJUST THE VALUE AT THE PERMIT CLERK'S DESK AND
 PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING OR
 PROVIDE A COPY OF THE SIGNED CONRACT BY BOTH PARTIES
 (CONTRACTOR AND CUSTOMER) TO VERIFY THE PERMIT
 APPLICATION VALUE. PER (W.P.B. AS AMENDED) SECTION
 108.3 BUILDING PERMIT VALUATION.
 PER MARSHALL AND SWIFT A 400,000 BTU HEATER IS AROUND
 $3000.00.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-12 Cont ID  
Sent By adarroug Date 2008-08-12 Time 16:02 Rev Time 0.00
Received By adarroug Date 2008-08-12 Time 16:02 Sent To G
Notes
2008-08-12 16:03:46TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-03 Cont ID  
Sent By adarroug Date 2008-07-03 Time 09:21 Rev Time 0.00
Received By adarroug Date 2008-07-03 Time 09:21 Sent To G
Notes
2008-07-03 09:21:25TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-23 Cont ID  
Sent By mperson Date 2008-06-23 Time 08:39 Rev Time 0.00
Received By mperson Date 2008-06-20 Time 16:48 Sent To PC
Notes
***NONE***