Plan Review Details - Permit 08060566
Plan Review Stops For Permit 08060566
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-08 Cont ID  
Sent By mjacobs Date 2008-08-08 Time 15:29 Rev Time 0.00
Received By mjacobs Date 2008-08-08 Time 14:45 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-08 Cont ID  
Sent By mjacobs Date 2008-07-08 Time 09:59 Rev Time 0.00
Received By mjacobs Date 2008-07-08 Time 07:26 Sent To  
Notes
2008-07-08 09:59:18BUILDING PLAN REVIEW
 PERMIT: 08060566
 ADD: 529 S. FLAGLER DR. #31G
 CONT: BENCH MARK BUILDING DESIGN INC.
 TEL: (561)362
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 7-8-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 3)(CONDO CONSTRUCTION/RENOVATION)
 PER FLORIDA STATUTES, 481.229 EXEMPTIONS FROM
 ARCHITECTURAL LICENSURE ONLY APPLY TO 1FAMILY AND
 2FAMILY RESIDENCES (R3) NOT MULTI-FAMILY (R2) OR
 BUILDINGS OVER $25,000, THEREFORE, DRAWINGS ARE
 REQUIRED TO BE DRAWN BY A LICENSED DESIGN
 PROFESSIONAL.
  
 A DESIGN PROFESSIONAL THAT IS REGISTERED TO PRACTICE
 UNDER CHAPTER 481 OR 471 OF THE FLORIDA STATUTES SHALL
 AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND DATE TO SAID
 DRAWINGS AND SPECIFICATION PER 106.1 FBC 2004, THE
 EXEMPTION FROM LICENSURE UNDER 481.229 FLORIDA STATUTES
 DOES NOT EXEMPT THE DESIGNER RESPONSIBLE FOR THE
 DRAWINGS FROM SIGNING AND DATING SAID DRAWINGS.
  
 4)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC
 2004
  
 5)ADDITIONAL INFORMATION IS REQUIRED PER 106.1.2*.
 PROVIDE AN EXISTING FLOOR PLAN SHOWING THE EXISTING
 LAYOUT OF THE WALLS AND ROOMS. ON THIS PLAN YOU CAN
 SHOW WHAT WALLS OR SYSTEMS WILL BE DEMOLISH WITH THE
 AID OF A LEGEND INDICATING WHICH WALLS WILL REMAIN AND
 WHICH ONES WILL BE DEMOED. A PROPOSED FLOOR PLAN IS
 ALSO REQUIRED TO SHOW THE NEW LAYOUT OF THE STRUCTURE.
 THE DRAWINGS SHALL CLEARLY INDICATE WHICH WALLS ARE NEW
 AND THE ONES WHICH WALLS ARE EXISTING. AGAIN, A WALL
 LEGEND WILL HELP TO IDENTIFY THE NEW WALLS AND THE
 EXISTING WALLS. THE PROPOSED PLAN SHALL SHOW THE
 ADDITION OR RECONFIGURATION OF ANY SYSTEM. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS. 106.1.1. THE DRAWINGS NEED TO
 CLEARLY SHOW THE WORK TO BE CARRIED OUT FOR THIS
 PROJECT.
  
 6) NOTE: FBC (EXISTING) LEVEL 2 ALTERATION INCLUDE THE
 RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION
 OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION
 OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT.
  
 7)THE SUBMITTED DRAWINGS INDICATE THE OCCUPANCY TYPE
 AS TYPE 6 MULTI-STORY. THERE IS NO TYPE 6 OCCUPANCY
 PLEASE SEE FBC CHAPTER 3 FOR THE USE AND OCCUPANCY
 TYPES.THE DRAWINGS ALSO STATE THE MEAN ROOF HEIGHT IS
 ABOVE 60 FEET. THE PLANS NEED TO BE SPECIFIC WHEN
 STATING THE MEAN ROOF HEIGHT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-09-18 Cont ID  
Sent By btrobaug Date 2008-09-18 Time 14:42 Rev Time 0.00
Received By btrobaug Date 2008-09-18 Time 12:26 Sent To PC
Notes
2008-09-18 14:29:55 
  
  
 REVISION DENIED
  
 1} THE DESIGNER OF RECORD IS THE ONLY PERSON AUTHORIZED
 TO REVISE HIS/HER PLAN. TAKE ALL PROPOSED CHANGES TO
 THE DESIGNER TO BE REDRAWN.
 61G15-23.002 SEAL, SIGNATURE AND DATE SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND
 AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS,
 FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER?S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED OR
 ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED
 AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS,
 SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER.
  
 2} THIS WAS SUBMITTED AS A SUBMITTAL. ALL CHANGES TO
 THE PLANS THAT REQUIRE A REVIEW MUST BE SUBMITTED AS A
 REVISION AND THE APPROPRIATE FEES MUST BE PAID AT THE
 TIME OF SUBMITTAL OR THE REVIEW WILL NOT BE DONE. THE
 PLAN WILL BE PLACED FOR PICK UP UNTIL SUCH TIME AS FEES
 DETERMINED BY THE PERMIT SPECIALIST ARE PAID. 108.1
 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-07-28 Cont ID  
Sent By btrobaug Date 2008-07-28 Time 14:07 Rev Time 0.00
Received By btrobaug Date 2008-07-28 Time 13:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-24 Cont ID  
Sent By btrobaug Date 2008-06-24 Time 13:05 Rev Time 0.00
Received By btrobaug Date 2008-06-24 Time 11:33 Sent To  
Notes
2008-06-24 13:05:33 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 2} 210.12(B) DWELLING UNIT BEDROOMS ALL 120-VOLT,
 SINGLE PHASE, 15- AND 20-AMPERE BRANCH CIRCUITS
 SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT BEDROOMS
 SHALL BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT
 INTERRUPTER, COMBINATION TYPE INSTALLED TO PROVIDE
 PROTECTION OF THE BRANCH CIRCUIT. A NOTE ON THE PLAN
 WILL SUFFICE.
  
 3} THERE ARE RECEPTACLES SHOWN IN THE LIVING AND DINING
 ROOMS THAT APPEAR TO BE FLOOR RECEPTACLES. CLARIFY IF
 THESE ARE FLOOR OR WALL. IF FLOOR AN ENGINEERING REPORT
 WILL BE REQUIRED TO VERIFY THE STRUCTURAL INTEGRITY OF
 ANY CUTS IN THE FLOOR.
  
 4} SUBMIT A FIXTURE SCHEDULE INDICATING THE TYPE AND
 WATTAGES FOR THE NEW FIXTURES.106.1.1 FBC.
  
 NOTE PER 304.1SCOPE.
 LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF
 SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR
 WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM,
 OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. THE
 EXTENSION OF THE ELECTRICAL SYSTEM CONSTITUTED A LEVEL
 2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-08-04 Cont ID  
Sent By mawillia Date 2008-08-04 Time 16:32 Rev Time 0.00
Received By mawillia Date 2008-08-04 Time 16:23 Sent To  
Notes
2008-08-04 16:32:39*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED;SINGLE PLAN SHEET ONE OF ONE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-07-08 Cont ID  
Sent By mwennerg Date 2008-07-08 Time 15:53 Rev Time 0.00
Received By mwennerg Date 2008-07-08 Time 15:53 Sent To  
Notes
2008-07-08 15:56:54***DENIED***
  
 1) SEE OTHER REVIEW COMMENTS REGARDING FBC AND FORIDA
 STATUTES REQUIREMENTS FOR DRAWINGS.
  
 2) WILL WORK IMPACT EXISTING FIRE PROTECTION SYSTEMS?
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-08 Cont ID  
Sent By adarroug Date 2008-09-08 Time 15:57 Rev Time 0.00
Received By adarroug Date 2008-09-08 Time 15:57 Sent To E
Notes
2008-09-08 15:57:33TO "BTROBAUG" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-21 Cont ID  
Sent By adarroug Date 2008-07-21 Time 11:56 Rev Time 0.00
Received By adarroug Date 2008-07-21 Time 11:56 Sent To  
Notes
2008-07-28 08:55:26TO "BOB"#10
2008-07-21 11:56:34WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-08 Cont ID  
Sent By mwennerg Date 2008-07-08 Time 15:59 Rev Time 0.00
Received By mwennerg Date 2008-06-20 Time 09:49 Sent To  
Notes
2008-06-20 09:57:48TO "BOB"#7

Review Stop Z ZONING
Rev No 1 Status N Date 2008-06-24 Cont ID  
Sent By choops Date 2008-06-24 Time 14:32 Rev Time 0.00
Received By choops Date 2008-06-24 Time 14:32 Sent To  
Notes
2008-06-24 14:32:38*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.