Plan Review Details - Permit 08060552
Plan Review Stops For Permit 08060552
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-20 Cont ID  
Sent By shill Date 2008-10-20 Time 14:49 Rev Time 0.00
Received By shill Date 2008-10-20 Time 14:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-10-02 Cont ID  
Sent By shill Date 2008-10-02 Time 11:51 Rev Time 0.00
Received By shill Date 2008-10-02 Time 11:51 Sent To  
Notes
2008-10-02 11:56:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. ONE SET OF THE ELEVATION PLAN WHICH SPECIFIES DESIGN
 PRESSURES WAS A PHOTOCOPY. DOCUMENTS PREPARED BY AN
 ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. FS481.
  
 2. THE ARCHITECT HAS SPECIFIED DESIGN PRESSURE OF
 -47.34, BUT ANCHORING FOR 47.2 HAS BEEN USED. PLEASE
 REVISE; A DESIGN PRESSURE OF -47.34 EXCEEDS 47.2 AND
 THEREFORE THE ANCHORING FOR -77PSF SHOULD BE USED.
  
 3. THE INSTALLATION SCHEDULE STAES THAT THE SUBSTRATE
 IS "CEMENT". THIS SHOULD STATE EITHER "CONCRETE" OR
 "BLOCK". IF THIS IS BLOCK, PLEASE USE THE CHART ON PAGE
 8 OF THE ACCORDION PRODUCT APPROVAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-01 Cont ID  
Sent By shill Date 2008-07-01 Time 10:54 Rev Time 0.00
Received By shill Date 2008-07-01 Time 10:54 Sent To  
Notes
2008-07-01 11:06:02****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471.ONE PHOTOCOPY OF THE WIND LOAD CHART
 (ENGINEERING EXPRESS) WAS SUBMITTED.HOWEVER, IT IS
 NOT CLEAR WHY THIS WAS SUBMITTED AS THE ARCHITECT
 SPECIFIED WIND LOADS.ENGINEERING IS NOT REQUIRED FOR
 BUILDINGS UNDER 60' AS THE BUILDING CODE SPECIFIES WIND
 PRESSURES.PLEASE EITHER REMOVE THE WIND LOAD CHARTS
 (ENGINEERING EXPRESS) OR PROVIDE ANOTHER ORIGINAL.
  
 2.TWO COMPLETE ORIGINAL COLLATED SETS OF PERMIT
 DOCUMENTS REQUIRED.ONLY ONE INSTALLATION SCHEDULE WAS
 SUBMITTED, AND ONE SET OF ENGINEERING WAS A PHOTOCOPY
 (SEE ITEM1).DUE TO WORKLOAD, I AM UNABLE TO MAKE
 PHOTOCOPIES FOR CONTRACTORS.
  
 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72.THIS WAS NOT SUBMITTED FOR THE ROLL UP
 SHUTTERS.
  
 4.THE SPAN SHOULD BE ONE NUMBER, NOT TWO.FOR
 ACCORDIONS THIS WILL CORRELATE WITH THE BLADE LENGTH.
 FOR ROLL UP SHUTTERS, IT WILL BE THE HORIZONTAL
 DIMENSION.
  
 5.THE SHUTTER CONNECTION MOUNTING TYPE SHOULD
 CORRELATE WITH THE ANCHOR CHART ON THE PRODUCT
 APPROVAL.FOR THE ACCORDIONS, YOU'VE MARKED C2.
 PLEASE REVISE THE INSTALLATION SCHEDULE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-10 Cont ID  
Sent By adarroug Date 2008-10-10 Time 11:09 Rev Time 0.00
Received By adarroug Date 2008-10-10 Time 11:09 Sent To B
Notes
2008-10-10 11:10:11TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-29 Cont ID  
Sent By adarroug Date 2008-09-29 Time 10:46 Rev Time 0.00
Received By adarroug Date 2008-09-29 Time 10:46 Sent To B
Notes
2008-09-29 10:47:10TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-01 Cont ID  
Sent By shill Date 2008-07-01 Time 11:06 Rev Time 0.00
Received By shill Date 2008-06-20 Time 09:16 Sent To  
Notes
2008-06-20 09:16:52TO "MISC" BOX#1