| 2008-07-09 10:29:22 | ** DENIEDREVIEW ** |
| | |
| | 1) NOTE: PLEASE ADJUST PLANS AND CORRELATE ALL |
| | ELECTRICAL ITEMS ON THE ELECTRICAL RISER WITH THE |
| | EQUIPMENT SCHEDULE, CONDUCTOR SCHEDULE AND PANEL |
| | SCHEDULE WITH LOADS. |
| | SOME EXAMPLES OF THESE ITEMS WILL BE LISTED AS A |
| | BENEFIT AND MAY NOT BE ALL ITEMS WHICH DO NOT |
| | CORRELATE. |
| | |
| | FOR EXAMPLE: |
| | EQUIPMENT #10 ON THE LEGEND INDICATES A POOL/SPA LIGHT |
| | YET PLEASE SEE THE RISER WHICH SHOWS ONE OF THE PUMPS |
| | WITH THIS SAME NUMBER 10. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE CIRCLE #3 WHICH IS LISTED ON LEGEND AS A |
| | PUMP YET THE RISER DO NOT INDICATE THIS SAME #3. IN |
| | FACT SOME PUMPS LISTED ARE NOT SHOWN. |
| | |
| | 2) NOTE: PLEASE INDICATE THE SIZE OF THE FEEDERS AND |
| | AMPACITY OF THE FEED TO THE NEW POOL EQUIPMENT PANEL |
| | SHOWN. AS PERMIT FOR BASE BUILDING HAS NOT BEEN ISSUED |
| | INCLUSIVE OF INTERIOR BUILD OUT WORK THERE ARE NO |
| | RECORD PLANS WHICH SHOW THESE ITEMS. |
| | 220, 408, 215.5, 310.16 ETC |
| | FBC 106.1.1 FOR CLARITY AND ADDITIONAL INFORMATION. |
| | |
| | 3) NOTE: PLEASE SHOW THE COMPLETE GROUNDING SYSTEM FOR |
| | THE EQUALPOTENTIAL BONDING. THE COVER SHEET SHOWS A |
| | LINE AND MENTIONS *GROUND PER CODE* HOWEVER YOU MAY NOT |
| | QUOTE THE CODE OR PARTS OF THE CODE IN LIEU OF ACTUAL |
| | DESIGN. |
| | 680.26 |
| | NEC 2005, |
| | FBC 106.1.1, 106.1.2, 106.5 FOR ADDITIONAL INFORMATION, |
| | CLARITY AND INFORMATION ON RECORD PLANS. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |