| 2008-07-03 10:37:18 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW |
| | CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1-SHEET A1-0: |
| | A) REVISE TYPE OF OCCUPANCY. THIS IS NOT OCCUPANCY |
| | GROUP R2, BUT R3. REVISE AS REQUIRED. |
| | |
| | B) DESIGN PRESSURES SHOWN ON DESIGN CRITERIA DON'T |
| | MATCH DESIGN PRESSURES SHOWN ON DOORS AND WINDOWS |
| | SCHEDULES. REVISE AS REQUIRED. |
| | |
| | C) WALL TYPE LEGEND: REVISE STUCCO THICKNESS. MIN. |
| | 7/8" STUCCO IS REQUIRED. SEC. R703.6.4.3 OF 2004 |
| | FLORIDA RESIDENTIAL CODE AND ASTM C926 ANDC1063. |
| | REVISE AS REQUIRED. |
| | |
| | D) WALL SECTION A DOESN'T MATCH FLOOR PLANS. |
| | FRAMED WALL IS NOT ALIGNED WITH THE FOOTING. THERE IS A |
| | 4" RECESS. REVISE AS REQUIRED. |
| | |
| | E) FLOOR PLAN: CLARIFY IFTHERE IS ACCESS TO THE |
| | STORAGE ROOM FROM THEINTERIOR OF THE HOUSE. PLANS |
| | DON'T PROVIDE ANY INFORMATION OTHER THAN EXISTING.IF |
| | WALLS ARE PROVIDED TO DIVIDE THE ROOMS, THENPROVIDE |
| | COMPLETE INFORMATION.ACCORDING TO SURVEY THISNEW |
| | STORAGE ROOM USED TO BE AN SCREENED ENCLOSURE.IF |
| | THESE WHERE DOORS OPENINGS, THEN SPECIFY HOW THE |
| | OPENINGS ARE GOING TO BE CLOSED. |
| | |
| | F) ENGINEER TO SPECIFYALTERATION LEVEL AS REQUIRED |
| | BY SEC. 301.5 OF 2004 FLORIDA EXISTING BUILDING CODE. |
| | |
| | G) WALL SECTION A:* CLARIFY WHY THERE IS NOT ROOF |
| | INSULATION? |
| | ** SPECIFY ROOFCROSS VENTILATION AS REQUIRED BY |
| | SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | *** PROVIDE SPECIFICATIONS FOR ATTACHMENT OF ROOF |
| | JOISTS TO WALLAS REQUIRED BY SEC. R601.2 OF 2004 |
| | FLORIDA RESIDENTIAL CODE.DETAILS PROVIDED ONLY SHOW |
| | ATTACHMENT OF ROOF JOIST TO HEADERS AND FROM DOUBLE TOP |
| | PLATE TO STUDS, BUT THERE IS NOT A CONNECTOR SPECIFIED |
| | FOR LOAD CONTINUITY FROM CEILING TO WALL. REVISE AS |
| | REQUIRED. |
| | **** CONNECTOR SP1 SPECIFIED AT BOTTOM OF WALL |
| | SECTION DOESN'T PROVIDE THE UPLIFT SHOWN. SEE CONNECTOR |
| | CATALOG AND REVISE AS REQUIRED. |
| | ***** SPECIFY STUCCO THICKNESS. |
| | ****** PROVIDE COMPLETE SPECIFICATIONS FOR WALL |
| | SHEATHING FASTENINGTO VERIFY COMPLIANCE WITH |
| | CALCULATED LOADS OF R301 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | ******* CLARIFY TYPE OF WALL SHEATHING. T & G OR |
| | PLYWOOD. SEE INFORMATION ON WALL TYPE LEGEND AND |
| | CLARIFY AS REQUIRED. |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-101.2 OF FBC 2004. |
| | NOTE: PLEASE, MAKE SURE CORRECT2004 REVISED FORM IS |
| | USED TO AVOID DELAYS OR CONFLICTS. |
| | |
| | 3- PROVIDE PRODUCT APPROVALS (2 COPIES)AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) SINGLE HUNG WINDOW.INFORMATION SUBMITTED IS NOT |
| | A COMPLETE PRODUCT APPROVAL.SEE PRODUCT APPROVAL FOR |
| | SWING DOOR AND PROVIDE COMPLETE PACKAGE. |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. |
| | |
| | C) STORM SHUTTERS AND PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE (SEE ATTACHED SAMPLE). |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 5- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| | (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING |
| | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| | DUE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |
| | |