Plan Review Details - Permit 08060531
Plan Review Stops For Permit 08060531
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-05 Cont ID  
Sent By jgomez Date 2008-08-05 Time 09:22 Rev Time 0.00
Received By jgomez Date 2008-08-05 Time 09:21 Sent To  
Notes
2008-08-05 09:33:29PROVISO ITEMS WERE SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-01 Cont ID  
Sent By jgomez Date 2008-08-01 Time 10:49 Rev Time 0.00
Received By jgomez Date 2008-08-01 Time 09:28 Sent To PC
Notes
2008-08-01 10:55:47BUILDING REVIEW APPROVED WITH PROVISO;
 1- PROVIDECOMPLETE INSTALLATION SCHEDULE FOR STORM
 SHUTTERS AS REQUIRED BY CITY IMPLEMENTATION STANDARD.
 SEE ATTACHED SAMPLE. OR PROVIDE INFORMATION IN ANY
 FORMAT THAT WILL SHOW ALL THE REQUIRED INFORMATION.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR ALL SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS AND DETAILS.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-03 Cont ID  
Sent By jgomez Date 2008-07-03 Time 09:32 Rev Time 0.00
Received By jgomez Date 2008-07-03 Time 08:40 Sent To PC
Notes
2008-07-03 10:37:18RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-SHEET A1-0:
 A) REVISE TYPE OF OCCUPANCY. THIS IS NOT OCCUPANCY
 GROUP R2, BUT R3. REVISE AS REQUIRED.
  
 B) DESIGN PRESSURES SHOWN ON DESIGN CRITERIA DON'T
 MATCH DESIGN PRESSURES SHOWN ON DOORS AND WINDOWS
 SCHEDULES. REVISE AS REQUIRED.
  
 C) WALL TYPE LEGEND: REVISE STUCCO THICKNESS. MIN.
 7/8" STUCCO IS REQUIRED. SEC. R703.6.4.3 OF 2004
 FLORIDA RESIDENTIAL CODE AND ASTM C926 ANDC1063.
 REVISE AS REQUIRED.
  
 D) WALL SECTION A DOESN'T MATCH FLOOR PLANS.
 FRAMED WALL IS NOT ALIGNED WITH THE FOOTING. THERE IS A
 4" RECESS. REVISE AS REQUIRED.
  
 E) FLOOR PLAN: CLARIFY IFTHERE IS ACCESS TO THE
 STORAGE ROOM FROM THEINTERIOR OF THE HOUSE. PLANS
 DON'T PROVIDE ANY INFORMATION OTHER THAN EXISTING.IF
 WALLS ARE PROVIDED TO DIVIDE THE ROOMS, THENPROVIDE
 COMPLETE INFORMATION.ACCORDING TO SURVEY THISNEW
 STORAGE ROOM USED TO BE AN SCREENED ENCLOSURE.IF
 THESE WHERE DOORS OPENINGS, THEN SPECIFY HOW THE
 OPENINGS ARE GOING TO BE CLOSED.
  
 F) ENGINEER TO SPECIFYALTERATION LEVEL AS REQUIRED
 BY SEC. 301.5 OF 2004 FLORIDA EXISTING BUILDING CODE.
  
 G) WALL SECTION A:* CLARIFY WHY THERE IS NOT ROOF
 INSULATION?
 ** SPECIFY ROOFCROSS VENTILATION AS REQUIRED BY
 SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE.
 *** PROVIDE SPECIFICATIONS FOR ATTACHMENT OF ROOF
 JOISTS TO WALLAS REQUIRED BY SEC. R601.2 OF 2004
 FLORIDA RESIDENTIAL CODE.DETAILS PROVIDED ONLY SHOW
 ATTACHMENT OF ROOF JOIST TO HEADERS AND FROM DOUBLE TOP
 PLATE TO STUDS, BUT THERE IS NOT A CONNECTOR SPECIFIED
 FOR LOAD CONTINUITY FROM CEILING TO WALL. REVISE AS
 REQUIRED.
 **** CONNECTOR SP1 SPECIFIED AT BOTTOM OF WALL
 SECTION DOESN'T PROVIDE THE UPLIFT SHOWN. SEE CONNECTOR
 CATALOG AND REVISE AS REQUIRED.
 ***** SPECIFY STUCCO THICKNESS.
 ****** PROVIDE COMPLETE SPECIFICATIONS FOR WALL
 SHEATHING FASTENINGTO VERIFY COMPLIANCE WITH
 CALCULATED LOADS OF R301 OF 2004 FLORIDA RESIDENTIAL
 CODE.
 ******* CLARIFY TYPE OF WALL SHEATHING. T & G OR
 PLYWOOD. SEE INFORMATION ON WALL TYPE LEGEND AND
 CLARIFY AS REQUIRED.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-101.2 OF FBC 2004.
 NOTE: PLEASE, MAKE SURE CORRECT2004 REVISED FORM IS
 USED TO AVOID DELAYS OR CONFLICTS.
  
 3- PROVIDE PRODUCT APPROVALS (2 COPIES)AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) SINGLE HUNG WINDOW.INFORMATION SUBMITTED IS NOT
 A COMPLETE PRODUCT APPROVAL.SEE PRODUCT APPROVAL FOR
 SWING DOOR AND PROVIDE COMPLETE PACKAGE.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS.
  
 C) STORM SHUTTERS AND PROVIDE COMPLETE INSTALLATION
 SCHEDULE (SEE ATTACHED SAMPLE).
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 5- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-06-23 Cont ID  
Sent By btrobaug Date 2008-06-23 Time 15:47 Rev Time 0.00
Received By btrobaug Date 2008-06-23 Time 15:41 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-29 Cont ID  
Sent By adarroug Date 2008-07-29 Time 14:34 Rev Time 0.00
Received By adarroug Date 2008-07-29 Time 14:34 Sent To B
Notes
2008-07-29 14:35:02TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-03 Cont ID  
Sent By jgomez Date 2008-07-03 Time 10:42 Rev Time 0.00
Received By jgomez Date 2008-06-19 Time 11:32 Sent To  
Notes
2008-06-19 11:33:38TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-06-23 Cont ID  
Sent By tgordon Date 2008-06-23 Time 16:42 Rev Time 0.25
Received By tgordon Date 2008-06-23 Time 16:42 Sent To B
Notes
2008-06-23 16:43:25NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop Z ZONING
Rev No 1 Status P Date 2008-06-19 Cont ID  
Sent By choops Date 2008-06-19 Time 14:37 Rev Time 0.00
Received By choops Date 2008-06-19 Time 14:37 Sent To E
Notes
2008-06-19 14:38:08***APPROVED***
  
  
  
  
 SENT TO "E" - SF RACK