| Plan Review Stops For Permit 08060478 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-12-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-12-09 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-12-09 |
Time |
15:17 |
Sent To |
PC |
|
| Notes |
| 2008-12-09 15:18:37 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY | | | DCA RULE 9B-72 FOR EXTERIOR SWING DOOR. | | | | | | 2- TRUSS PACKAGE: | | | A) REVISE TRUSS LOAD CRITERIA TO MATCH LOAD CRITERIA | | | SPECIFIED BY THE ENGINEER OF RECORD ON SHEET 1 OF 2. | | | B) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS | | | PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE. | | | C) ROOF LAYOUT DOESN'T MATCH ENGINEER OF RECORD PLANS. | | | TRUSS LAYOUT SHOWS GABLE ENDS WHILE ENGINEER OF RECORD | | | PLANS SHOW HIP ROOF. | | | D) TRUSS ENGINEER TO SIGN, SEAL AND DATE COVER SHEET. | | | IT WAS NOT SIGNED AND SEALED AT ALL. CHAPTER 471 | | | FLORIDA STATUTE AND SEC. 61G15-23.002 FLORIDA | | | ADMINISTRATIVE CODE. | | | E) TRUSS ENGINEER TO HAVE ORIGINAL SIGNATURE IN ALL | | | SIGNED SHEETS. COPY OF SIGNATURE IS NOT ALLOWED BY | | | CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002 | | | FLORIDA ADMINISTRATIVE CODE. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
|
Date |
2008-11-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-11-17 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-11-17 |
Time |
09:39 |
Sent To |
ENG |
|
| Notes |
| 2008-11-17 09:58:54 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- SPECIFY CORRECT WINDOW SIZE. | | | | | | 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY | | | DCA RULE 9B-72 FOR EXTERIOR SWING DOOR. | | | | | | 3- TRUSS PACKAGE: | | | A) REVISE TRUSS LOAD CRITERIA TO MATCH LOAD CRITERIA | | | SPECIFIED BY THE ENGINEER OF RECORD ON SHEET 1 OF 2. | | | B) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS | | | PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE. | | | C) ROOF LAYOUT DOESN'T MATCH ENGINEER OF RECORD PLANS. | | | TRUSS LAYOUT SHOWS GABLE ENDS WHILE ENGINEER OF RECORD | | | PLANS SHOW HIP ROOF. | | | D) TRUSS ENGINEER TO SIGN, SEAL AND DATE COVER SHEET. | | | IT WAS NOT SIGNED AND SEALED AT ALL. CHAPTER 471 | | | FLORIDA STATUTE AND SEC. 61G15-23.002 FLORIDA | | | ADMINISTRATIVE CODE. | | | E) TRUSS ENGINEER TO HAVE ORIGINAL SIGNATURE IN ALL | | | SIGNED SHEETS. COPY OF SIGNATURE IS NOT ALLOWED BY | | | CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002 | | | FLORIDA ADMINISTRATIVE CODE. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-08-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-08-06 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-08-06 |
Time |
14:56 |
Sent To |
PC |
|
| Notes |
| 2008-08-06 15:37:33 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND | | | CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH | | | COUNTY TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK | | | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. | | | (REPEAT COMMENT). | | | | | | 2- CLARIFY IF BEDROOM WINDOWS WILL BE CUSTOM MADE | | | WINDOWS. THERE ARE NOT STANDARD 4'X5' WINDOWS. SEE | | | PRODUCT APPROVAL FOR STANDARD WINDOW SIZES. PROVIDE | | | MANUFACTURER'S CUT SHEETS FOR WINDOWS OTHER THAN THE | | | STANDARD EGRESS WINDOWS TO VERIFY COMPLIANCE WITH SEC. | | | R310.1.2. (REPEAT COMMENT). | | | | | | 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY | | | DCA RULE 9B-72 FOR: | | | A) SWING DOOR AT NEW CLOSET AREA. (REPEAT COMMENT). | | | | | | B) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS AND | | | DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL | | | COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN TO SAVE | | | TIME AND PAPER. (REPEAT COMMENT). | | | | | | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | NOTE: | | | | | | 5- SHEET 2 OF 2: REVISE ROOF SHEATHING NAIL SPACING FOR | | | ZONE #3. SEE SEC. R803.2.3.1 FOR REQUIRED NAIL SPACING | | | AT ROOF ZONE #3 AND REVISE ROOF SHEATHING NAILING | | | SCHEDULE AS REQUIRED. (REPEAT COMMENT). | | | NOTE: NAIL SPACING AT INTERMEDIATE SUPPORTS IS MISSING. | | | ONLY NAILING AT EDGES WAS SPECIFIED. REVISE AS | | | REQUIRED. | | | | | | 6- TRUSS PACKAGE: | | | A) REVISE TRUSS LOAD CRITERIA TO MATCH LOAD CRITERIA | | | SPECIFIED BY THE ENGINEER OF RECORD ON SHEET 1 OF 2.. | | | INFORMATION SUBMITTED DON'T MATCH. | | | | | | B) ENGINEER OF RECORD TO REVIEW AND APPROVE TRUSS | | | PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE. | | | | | | C) PROVIDE COMPLETE TRUSS PACKAGE. ONLY THE TRUSS | | | LAYOUT WAS SUBMITTED THIS TIME. | | | | | | 7- SURVEY NEEDS TO HAVE SURVEYOR'S ORIGINAL SIGNATURE | | | (NOT COPY) AS REQUIRED BY SEC. 61G17-7.0025 OF FLORIDA | | | ADMINISTRATIVE CODE AND SEC. 472 FLORIDA STATUTE. | | | | | | ***NOTE: TO EXPEDITE REVIEW PROCESS, PLEASE DON'T | | | STAPLE TOGETHER OLD DRAWINGS WITH NEW DRAWINGS. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-07-01 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-07-01 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-07-01 |
Time |
16:34 |
Sent To |
PC |
|
| Notes |
| 2008-07-01 16:56:17 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH | | | COUNTY TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK | | | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE | | | DUE. | | | | | | 2- SHEET 1 OF 2:CLEARLY SPECIFY THE ATTIC LIVE LOAD | | | AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL | | | CODE. | | | NOTE: THIS LOAD IS IN ADDITION TO THE BOTTOM CHORD DEAD | | | LOAD. | | | | | | 3- WINDOWS SPECIFIED FOR THE NEW BEDROOM DON'T COMPLY | | | WITH THE EGRESS REQUIREMENTS OF SEC. R311.1.2 OF 2004 | | | FLORIDA RESIDENTIAL CODE.SH-48X52 WINDOWS DON'T | | | PROVIDE THE MINIMUM HEIGHT CLEARANCE.ALSO, CLARIFY IF | | | WINDOW WILL BE A CUSTOM MADE WINDOW. SEE PRODUCT | | | APPROVAL FOR STANDARD WINDOW SIZES.PROVIDE | | | MANUFACTURER'S CUT SHEETS FOR WINDOWS OTHER THAN THE | | | STANDARD EGRESS WINDOWS TO VERIFY COMPLIANCE WITH SEC. | | | R310.1.2. | | | | | | 4- PROVIDE 2 COPIES OF PRODUCT APPROVALSAS REQUIRED | | | BY DCA RULE 9B-72 FOR: | | | A) SINGLE HUNG WINDOWS. COPIES OF PRODUCT APPROVAL | | | SUBMITTED ARE MISSING THE TOP PART OFTHE DRAWINGS. | | | PROVIDE COPIES WITH COMPLETE INFORMATION. | | | | | | B) SWING DOOR AT NEW CLOSET AREA. | | | | | | C) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS | | | AND DETAILS.PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL | | | COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN TO SAVE | | | TIME AND PAPER. | | | | | | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 6- SHEET 2 OF 2: | | | A) REVISE ROOF SHEATHING NAIL SPACING FOR ZONE #3. | | | SEE SEC. R803.2.3.1 FOR REQUIRED NAIL SPACING AT ROOF | | | ZONE #3 AND REVISEROOF SHEATHING NAILING SCHEDULE AS | | | REQUIRED. | | | | | | B) SPECIFY THE MINIMUM THICKNESSMOISTURE BARRIER | | | AT CONCRETE SLAB AS REQUIRED BY SEC. R406.3.2. | | | | | | 6- OWES $3.80 FOR RADON FEES. | | | | | | 7- ENGINEER TO DATE PLANS WHEN THEY ARE SIGNED AND | | | SEALED AS REQUIRED BY SEC. 61G15-23.002 FLORIDA | | | ADMINISTRATIVE CODE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-11-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-11-04 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-11-04 |
Time |
11:53 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-08-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-08-04 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-08-04 |
Time |
15:06 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2008-06-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-25 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-25 |
Time |
16:39 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2008-11-24 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-11-24 |
Time |
13:54 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
2008-11-24 |
Time |
11:13 |
Sent To |
ENG |
|
| Notes |
| 2008-11-24 11:16:38 | - PASSED - 11 / 24 / 08 | | | | | | - OWNER / CONTRACTOR CONTACTED WILL NOT DO DRIVEWAY | | | WORK AT THIS TIME. - | | | | | | ANY QUESTIONS FEEL FREE TO CONTACT: | | | MANNY GONZALEZ | | | PROJECT COORDINATOR | | | CITY OF WPB | | | | | | | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2008-11-19 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2008-11-19 |
Time |
09:02 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2008-11-19 |
Time |
08:56 |
Sent To |
ENG |
|
| Notes |
| 2008-11-19 09:02:38 | -FAILED- | | | | | | PLANS DO NOT REFLECT OR ANY STANDARD DRIVEWAY DETAILS | | | HAVE BEEN ADDED. | | | DRIVEWAY MUST MEET MINIMUM DIMENSION CRITERIA FROM | | | PROPERTY LINE 3'+/- | | | | | | PLEASE CALL CWPB ENGINEERING DEPT. ROW DIVISION (561) | | | 494-1040. | | | THEY CAN FURNISH DETAIL AND ROW PERMIT. THEN MAKE | | | CONTACT BELOW TO APPROVE PERMIT: | | | | | | MANUEL J GONZALEZ, PROJECT COORDINATOR | | | LOCATION ADDRESS: | | | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | 1000 - 45TH STREET, SUITE 15 | | | WEST PALM BEACH FL 33407 | | | MAILING ADDRESS: | | | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | P.O. BOX 3506 | | | WEST PALM BEACH FL 33401 | | | TELEPHONE: | | | 45TH STREET OFFICE : 561-494-1040 | | | 45TH DIRECT: 561-494-1085 | | | FAX: 561-494-1117 | | | CITY HALL OFFICE: (561) 805-6723 | | | CITY HALL DIRECT: (561) 805-6327 | | | CITY HALL FAX: (561) 805-6731 OR 805-6676 | | | NEXTEL: 561-644-7301 | | | NEXTEL DIRECT CONNECT: 159*28165*38 | | | EMERGENCIES: | | | CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210 | | | E-MAIL: | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2008-06-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-11-17 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-06-25 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2008-06-25 16:07:46 | FAILED FOR FOLLOWING REASONS: | | | | | | 1. PLEASE PROVIDE A DETAIL DRAWING SHOWING ALL THE | | | DIMENSIONS FOR DRIVEWAY, APPROACH, SIDEWALK ETC2 | | | COPIES. | | | | | | 2. YOU ARE PUTTING AN APPROACH, DRIVEWAY, SIDEWALK & | | | CUTTING A CURB IN CITY'S RIGHT OF WAY. THEREFORE, YOU | | | NEED CITY'S RIGHT OF WAY APPROVAL FROM WINDEL PALMER | | | 494-1040, 1000 45TH STREET, ENG DEPT.ONCE WE HAVE AN | | | APPROVAL FROM WINDEL PALMER, WE WILL REVIEW YOUR | | | DRAWINGS. | | | | | | 3. MUST MEET CITY'S STANDARDS FOR APPROACH, | | | SIDEWALK,DRIVEWAY ETC. A SHEET " TYPICAL PAVER | | | STONE/CONCRETE DRIVEWAY APPROACH DETAILS" ENCLOSED FOR | | | YOUR USE. | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-12-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-01 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-01 |
Time |
16:37 |
Sent To |
Z |
|
| Notes |
| 2008-12-01 16:37:39 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-10-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-29 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-29 |
Time |
14:40 |
Sent To |
Z |
|
| Notes |
| 2008-10-29 14:41:29 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-07-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-24 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-24 |
Time |
11:44 |
Sent To |
Z |
|
| Notes |
| 2008-07-24 11:44:46 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-07-01 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-07-01 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-06-18 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2008-06-18 09:30:23 | TO "SFR" "Z" |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
2008-12-02 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2008-12-02 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2008-12-02 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2008-12-02 08:50:23 | ***LANDSCAPE REVIEW PASSED WITH PROVISO*** | | | | | | LANDSCAPE PLAN MUST BE SUBMITTED, APPROVED AND THE | | | LANDSCAPE MUST PASS INSPECTION PRIOR TO C/O. RAK | | | 12/2/2008 |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2008-11-03 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2008-11-03 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2008-11-03 |
Time |
08:29 |
Sent To |
PC |
|
| Notes |
| 2008-11-03 09:17:56 | ***LANDSCAPE FAILED*** | | | | | | 1. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE | | | EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE | | | XERISCAPE DESIGN OPTIONS. | | | | | | 2. PURSUANT TO SECTION 94-448(D)(2), THE LANDSCAPE PLAN | | | SHALL SHOW EXISTING AND PROPOSED UNDERGROUND OR | | | OVERHEAD UTILITY SERVICES, EASEMENTS AND OTHER ITEMS | | | THAT MAY IMPACT THE LANDSCAPING. ALL EXISTING AND | | | PROPOSED LANDSCAPING SHALL BE CLEARLY IDENTIFIED. THE | | | COMMON AND BOTANICAL NAME, SIZE AND QUANTITY OF ALL | | | PROPOSED TREES, SHRUBS AND GROUND COVER SHALL BE SHOWN | | | ON THE PLAN IN TABULAR FORM. | | | REQUIRED NOTES ON THE PLAN SHALL INCLUDE STATEMENTS | | | THAT ALL LANDSCAPED AREAS THROUGHOUT THE SITE AND | | | INCLUDING THE RIGHTS-OF-WAY SHALL BE PROVIDED WITH 100% | | | IRRIGATION COVERAGE, A (3) INCH DEPTH OF MULCH IS | | | REQUIRED IN ALL PLANT BEDS AND ALL PROPOSED AND | | | EXISTING PLANT MATERIAL SHALL BE FLORIDA #1 GRADE OR | | | BETTER. | | | | | | 3. PURSUANT TO SECTION 94-441(C), BECAUSE THIS | | | ALERATION EXCEEDS 50% OF THE VALUE OF THE STRUCTURE, | | | THE SITE MUST BE BROUGHT UP TO CURRENT STANDARDS AND | | | MEET ALL MINIMUM LANDSCAPE REQUIREMENTS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS REGARDING THESE COMMENTS, | | | PLEASE CONTACT ROBERT KUSSNER @ (561) 822-1462, | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2008-06-26 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-06-26 |
Time |
14:00 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2008-06-26 |
Time |
14:00 |
Sent To |
P |
|
| Notes |
| 2008-06-26 14:01:25 | NO MECHANICAL PLANS SUBMITTED, AND NO | | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | | THIS TIME. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-11-04 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-11-04 |
Time |
14:21 |
Rev Time |
0.30 |
| Received By |
mperson |
Date |
2008-11-04 |
Time |
14:21 |
Sent To |
ENG |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2008-08-05 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-08-05 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-08-05 |
Time |
13:41 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-06-27 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-06-27 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-06-27 |
Time |
09:56 |
Sent To |
B |
|
| Notes |
| 2008-06-27 10:44:49 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | NOTE: THERE ARE TWO SEPERATE SANITARY ISOMETRIC RISER | | | DIAGRAMS SUBMITTED BY TWO DIFFERENT PEOPLE. ONE IS | | | SIGNED AND SEALED BY WILLIAM YURASEK P.E. AND THE OTHER | | | RISER DIAGRAM IS AN 8-1/2" X 11" ATTACHED TO THE SIGNED | | | AND SEALED SET WHICH DOES NOT HAVE THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON TAKING RESPOSIBILITY FOR IT. | | | THEREFORE TWO SEPERATE REVIEWS WILL BE DONE. FOR ALL | | | PRACTICLE PURPOSES ONLY ONE SET OF SANITARY RISER | | | DIAGRAMS WILL BE APPROVED. THE RESUBMITTED PLANS SHOULD | | | ONLY HAVE ONE SANITARY RISER DIAGRAM FOR PLUMBING TO | | | REVIEW. | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE FOR THE | | | SIGNED AND SEALED ENGINEERED PLANS. | | | | | | 1. SHEET 2 PLUMBING RISER: THE FOLLOWING CORRECTIONS | | | ARE REQUIRED FROM FBC- PLUMBING SECTIONS. | | | A} SHOWER REQUIRES A VENT. PER 901.2.1 VENTING | | | REQUIRED. | | | B} CLEARLY INDICATE THE CLEANOUT AT THE JUNCTION OF | | | THE BUILDING DRAIN AND BUILDING SEWER AS BEING A | | | TWO-WAY CLEANOUT. PER SECTION 708.3.5. | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR | | | THE 8-1/2" X 11 RISER DIAGRAM ATTACHED TO THE SIGNED | | | AND SEALED SET. | | | | | | 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING | | | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE | | | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE | | | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER | | | SECTION *106.3.4.3. (THIS CAN BE THE PLUMBING | | | CONTRACTOR PER 105.3.1.2 (2) | | | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR | | | ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER | | | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER | | | FLORIDA STATUTES 481 AND 471 RESPECTIVELY. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2008-12-09 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-12-09 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-12-09 |
Time |
10:15 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2008-11-02 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-11-02 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-11-02 |
Time |
11:39 |
Sent To |
L |
|
| Notes |
| 2008-11-02 11:42:52 | PLANNING AND ZONING DEPT: ***ZONING FAILED*** | | | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | REPEAT COMMENTS: | | | | | | 1. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-482: | | | REQUIRED OFF-STREET PARKING SPACES FOR LESS THAN FOUR | | | RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE | | | PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED | | | PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE | | | LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT | | | YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN | | | THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH, | | | NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION | | | 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO | | | PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE. | | | | | | PLEASE INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE | | | SURFACES (EXISTING AND PROPOSED) LOCATED WITHIN THE | | | FRONT YARD (FROM FRONT PROPERTY LINE TO THE FRONT | | | BUILDING FACADE). | | | | | | 2. A RIGHT-OF-WAY PERMIT WILL NEED TO BE ACQUIRED FROM | | | THE CITY'S ENGINEERING DEPARTMENT (561.494.1040), FOR | | | THE PROPOSED APPROACH EXTENSION. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-08-04 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-08-04 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-08-04 |
Time |
09:45 |
Sent To |
E |
|
| Notes |
| 2008-08-04 09:45:48 | **ZONING FAILED 1ST RESUB ** | | | | | | 1.PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | 2.REPEAT COMMENT - PURSUANT TO SECTION 94-441(C)(2) | | | OF THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS): | | | AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF THE | | | STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT VALUE" WITH | | | THE P.B.C. PROPERTY APPRAISER'S OFFICE), LANDSCAPING | | | SHALL BE IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS | | | FOUND IN ARTICLE XIV OF THE ZLDRS. | | | | | | PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN | | | SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF | | | THE ZLDRS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME AT:(561) 822-1444 OR (561) 805-6720 OR | | | [email protected] | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-06-18 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-06-18 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-06-18 |
Time |
15:03 |
Sent To |
ENG |
|
| Notes |
| 2008-06-18 15:07:34 | ***FAILED*** | | | | | | | | | 1)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF | | | THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE | | | (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | | THE ZLDRS. | | | | | | PLEASE SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH | | | SECTIONS 94-442 AND 94-445 OF THE ZLDRS. | | | | | | 2)PURSUANT TO SECTION 94-482 OF THE ZLDRS: REQUIRED | | | OFF-STREET PARKING SPACES FOR LESS THAN FOUR | | | RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE | | | PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED | | | PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE | | | LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT | | | YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN | | | THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH, | | | NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION | | | 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO | | | PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS | | | ARTICLE. | | | | | | | | | PLEASE INDICATE DIMENSIONS AND SQUARE FOOTAGE OF ALL | | | IMPERMEABLE SURFACES (EXISTING AND PROPOSED) LOCATED | | | WITHIN THE FRONT YARD (FROM FRONT PROPERTY LINE TO THE | | | FRONT BUILDING FACADE). | | | | | | | | | NOTE:A RIGHT-OF-WAY PERMIT IS REQUIRED FOR THE | | | INSTALLATION OF THE APPROACH, SEE ENGINEERING | | | COMMENTS. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 |
|
|