Plan Review Details - Permit 08060439
Plan Review Stops For Permit 08060439
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-08-06 Cont ID  
Sent By jgomez Date 2009-08-06 Time 10:46 Rev Time 0.00
Received By jgomez Date 2009-08-06 Time 10:46 Sent To  
Notes
2009-08-06 11:01:49BUILDING REVISION CHECKLIST.
  
 1- PROVIDE ALL THE INFORMATION REQUESTED ON PROVISO
 DATED 12/18/08. PERMIT WAS ISSUED WITH PROVISO TO ALLOW
 CONTRATOR TO START WORK ON THE CONDITION THAT
 CONTRACTOR WILL PROVIDE ALL THE REQUIRED INFORMATION.
 CONTRACTOR HAS FAILED TO PROVIDE ALL THE REQUIRED
 INFORMATION. PROVIDE WRITTEN RESPONSE STATING HOW
 ADDRESSING EACH ITEM REQUESTED ON THE PROVISO.
 ***NOTE: PROVIDE COMPLETE SPECIFICATIONS. DON'T CITE
 CODE SECTION. EX: PROVIDE COMPLETE SPECIFICATIONS FOR
 GARAGE DOOR LEADING TO THE LIVING AREA AS REQUIRED BY
 SEC. R309.1 OF 2004 FLORIDA RESIDENTIAL CODE.
 INFORMATION SUBMITTED IS NOT CLEAR BECAUSE IS
 SPECIFYING HOLLOW CORE DOOR AND JUST CITING THE CODE
 SECTION. READ CODE SECTION AND REVISE SPECIFICATIONS AS
 REQUIRED.
  
 2- INFORMATION SUBMITTED SHOWN CHANGE OF INSULATION TO
 ICYNENE INSULATION. REVISE ENERGY CALCULATIONS AS
 REQUIRED TO MATCH THIS REVISIONS.
  
 3- PROVIDE COMPLETE SPECIFICATIONS FOR THE INSTALLATION
 OF ICYNENE INSULATION.
  
 4- SHEET 1 SUBMITTED IS MISSING THE DESIGN CRITERIA.
 COORDINATE INFORMATION WITH ITEM #3 OF PROVISO DATED
 12/18/08.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-12-23 Cont ID  
Sent By jgomez Date 2008-12-23 Time 13:11 Rev Time 0.00
Received By jgomez Date 2008-12-23 Time 13:11 Sent To  
Notes
2008-12-23 13:12:54RECEIVED IMPACT FEES PLANS STAMPED AND COPY OF PAID
 RECEIPT.
 ***NEED TO COMPLY WITH PROVISO DATED 12-18-08.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date 2008-12-18 Cont ID  
Sent By jgomez Date 2008-12-18 Time 16:26 Rev Time 0.00
Received By jgomez Date 2008-12-18 Time 12:22 Sent To PC
Notes
2008-12-18 17:05:46BUILDING REVIEW APPROVED WITH PROVISO: (NOTE: PROVIDE
 INFORMATION PRIOR TO CONSTRUCTION OR INSTALLATION TO
 AVOID CONFLICTS OR DELAYS)
  
 1- REVISE ENERGY CALCULATIONS. REVISE TOTAL UNDER ATTIC
 SQUARE FOOTAGE SHOWN ON ITEM #10A TO COMPLY WITH THE
 REQUIREMENTS OF CEILING AREA SEC. 13-604.1.A.1 FBC
 2004.
 NOTE: DON'T FORGET TO HAVE ALL SIGNATURES AND DATES AT
 BOTTOM OF FORM 600A-2004R.
  
 2- SPECIFY HOW LONG ARE THE ANCHORS SPECIFIED ON
 DOOR/WINDOW STRUCTURAL BUCK DETAILS. HOW MUCH EMBEDMENT
 IS REQUIRED INTO THE SUBSTRATE. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH
 SECTIONS R301 AND R613.6 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 3- DESIGN CRITERIA NEEDS TO SPECIFY ALL DESIGN LOADS
 INCLUDING THE ATTIC LIVE LOAD FOR STORAGE OR
 NON-STORAGE AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 4- SHEET 3:
 A) TYPICAL WALL SECTION: SPECIFY FIREBLOCKING AS
 REQUIRED BY SEC. R602.1.2 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 B) REVISE STUCCO FINISH ON SOFFIT TO COMPLY WITH TABLE
 R702.1(1) OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) SPECIFY FOOTING SIZE BELOW GRADE TO VERIFY
 COMPLIANCE WITH SEC. R403.1.4 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 D) SIZE OF WINDOW SPECIFIED FOR BEDROOM #3 (24SH)
 DOESN'T COMPLY WITH THE EGRESS REQUIREMENTS OF SEC.
 R310.1.2 OF 2004 FLORIDA RESIDENTIAL CODE. REVISE AS
 REQUIRED.
  
 E) GARAGE DOOR LEADING TO THE INSIDE OF THE HOUSE NEEDS
 TO COMPLY WITH THE REQUIREMENTS OF SEC. R309.1 OF 2004
 FLORIDA RESIDENTIAL CODE. REVISE AS REQUIRED.
  
 5- SHEET 4:
 A) PROVIDE COMPLETE ROOF FRAMING PLAN INCLUDING THE
 AREAS THAT DON'T HAVE ROOF TRUSSES BUT CONVENTIONAL
 FRAMING BY BUILDER. SPECIFY ALL CONNECTORS.
  
 B) REVISE TRUSS ANCHOR SCHEDULE. FOR SOME CONNECTOR THE
 MAX. ACTUAL UPLIFT EXCEEDS THE ALLOWABLE UPLIFT. REVISE
 AS REQUIRED. ALSO, COORDINATE WITH PRODUCT APPROVAL FOR
 CURRENT UPLIFT LOADS AND REVISE AS REQUIRED.
  
 6- SHEET 5:
 A) SPECIFY DIMENSIONS FOR ROOF ZONES: SEE FIGURE
 R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE FOR MINIMUM
 DIMENSIONS AND REVISE AS REQUIRED.
  
 B) SPECIFY HOW PROVIDING THE ATTIC VENTILATION IN
 COVERED ENTRY ROOF DETAIL TO VERIFY COMPLIANCE WITH
 SEC. R806 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 C) REVISE THICKNESS OF STUCCO FINISH ON COVERED ENTRY
 DETAIL. SEE ITEM 3B ABOVE.
  
 7- SURVEY NEEDS TO HAVE ORIGINAL SIGNATURE AS REQUIRED
 BY SEC. 61G17-7.0025 OF FLORIDA ADMINISTRATIVE CODE AND
 CHAPTER 472 FLORIDA STATUTE.
  
 8- RE-SUBMIT PRODUCT APPROVAL FOR FRENCH DOORS. NOA
 05-1116.06 EXPIRED ON JUNE 05, 2008.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-03 Cont ID  
Sent By amorse Date 2008-07-03 Time 15:33 Rev Time 0.00
Received By amorse Date 2008-07-03 Time 15:33 Sent To PC
Notes
2008-07-03 16:36:17 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 &
 2007AMENDMENTS PER 106.1.1 FBC*
  
 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 4)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $215.68 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 5)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR
 SETBACKS, PLEASE NOTE THAT SURVEY AND SITE PLAN
 MEASUREMENTS ARE NOT THE SAME
  
 6)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
  
 7)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR
 TO SUBMITTAL.
  
 8)CORRECTIONS ARE REQUIRED IN THE SUMMER AND WINTER
 AS-BUILT CALCULATIONS,INCORRECT INFORMATION FOR
 NUMBER OF GLAZED OPENINGS, ORIENTATION, OVERHANG
 LENGTHS AND HEIGHTS
  
 9)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
  
 10)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION
  
 11)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 12)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC
 2004. PHOTO COPIED, STAMPED OR REPRODUCED SIGNATURES
 ARE NOT ACCEPTABLE PER 471.025 F.S. THESE REPRODUCED
 SIGNATURES ARE PRESENT ON THE SOIL REPORT AND THE TRUSS
 ENGINEER INDEX SHEETS
  
 13)AN ENGINEER PRACTICING THROUGH A DULYAUTHORIZED
 ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND
 LICENSE #, AS WELL AS THE NAME, ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER 61G15-23.002 (2)
 FAC. THE SOIL REPORT ENGINEERING DOES NOT CONTAIN THE
 REQUIRED CA #
  
 14)PROVIDE MEAN ROOF HEIGHT ON ELEVATION DRAWINGS
  
 15)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL NEW ROOF
 AREAS AS REQUIRED PER R807.1 FBC RES.
  
 16)PROVIDE MIN ROOF SHEATHING ATTACHMENT PER
 R803.2.3.1 FBC RES.
  
 17)PROVIDE ENGINEERED SUBSTRATE ATTACHMENT FOR WOOD
 BUCKS PER 1714.5.4.1 FBC
  
 18)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 19)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 20)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL SHEETS WHEN AVAILABLE. THEY CAN
 BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.WHEN
 AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
  
 21)NO PRODUCT APPROVALS WERE SUBMITTED FOR NEW
 SWINGING GARAGE DOOR, LINTELS AND CONNECTORS AND
 STRAPS. IN LUE OF PRODUCT APPROVALS STRAPS/CONNECTORS
 MAY BE LISTED IN A SCHEDULE ON THE DRAWINGS COMPLETE
 WITH THE STATEWIDE PRODUCT APPROVAL NUMBERS OR SUBMIT
 SIMPSON TIE'S COMPLETE FLORIDA INDEX WITH CONNECTORS TO
 BE USED HIGHLIGHTED
  
 22)PRODUCT APPROVAL FOR THE METAL ROOF DOES NOT HAVE
 THE COMPLIANCE/INSTALLATION REPORT, LOAD TABLES AND
 EVALUATION REPORT FROM THE LINK ON PAGE 2
  
 23)PROVIDE TRUSS UPLIFT ANCHOR SCHEDULE, ENGINEERING
 DOES NOT PROVIDE THIS INFORMATION, ONLY THE AMOUNT OF
 UPLIFT AT THE BEARING LOCATIONS
  
 24)PROVIDE DETAILS FOR ATTACHMENT OF THE COPULAS TO
 THE ROOF
  
 25)PROVIDE SCHEDULE FOR PRECAST LINTEL THAT WILL BE
 USED AND OPENING SIZES TO COMPLY WITH 2104.1.5 FBC FOR
 MIN BEARING
  
 26)ADDITIONAL PERMITS WILL BE REQUIRED FOR PLUMBING,
 ELECTRICAL, MECHANICAL, ROOFING AND DRIVEWAY
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-08-17 Cont ID  
Sent By btrobaug Date 2009-08-17 Time 11:55 Rev Time 0.00
Received By btrobaug Date 2009-08-17 Time 10:35 Sent To PC
Notes
2009-08-17 11:58:44PROVISO
  
 9B-3.0472 CARBON MONOXIDE PROTECTION.
 (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
 (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR
 PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING
 IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS
 SHALL HAVE BATTERY BACK UP.
 (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED
 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS.
 HISTORY???NEW 11-18-07 LOCATE DETECTORS ON THE PLAN.
 NOTE: MAY BE COMBINATION SMOKE/CARBON MONOXIDE.. NOTE:
 MAY BE COMBINATION SMOKE/CARBON MONOXIDE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-03 Cont ID  
Sent By btrobaug Date 2008-12-03 Time 16:29 Rev Time 0.00
Received By btrobaug Date 2008-12-03 Time 15:35 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-17 Cont ID  
Sent By btrobaug Date 2008-06-17 Time 13:34 Rev Time 0.00
Received By btrobaug Date 2008-06-17 Time 11:50 Sent To M
Notes
2008-06-17 13:33:02 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 408.4 NEC,
 106.3.5.4 FBC AS AMENDED.THERE ARE THREE SMALL
 APPLIANCE CIRCUITS ON ONE CIRCUIT, NO BATH CIRCUIT IS
 SHOWN (210.11(C)(3), THE CONDENSING UNITS ARE NOT SHOW,
 ETC.
  
 3} PLEASE SUBMIT A SITE PLAN INDICATING THE LOCATION OF
 THE METER AND THE MAIN DISCONNECT.
  
 4} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 5} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66 ALL AVAILABLE. ALSO SEE 250.52(A)(3) FOR FOOTER
 STEEL.
  
 6} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE SAME ON
 THE PLANS.
  
 7} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING.
  
 8} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NECLOCATE ON THE PLANS TO SHOW
 COMPLIANCE IN ALL ROOMS
  
 9} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-08-04 Cont ID  
Sent By rmcdouga Date 2009-08-04 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2009-08-04 Time 11:20 Sent To  
Notes
2009-08-04 11:21:12REVISION TO R3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-19 Cont ID  
Sent By adarroug Date 2008-11-19 Time 10:02 Rev Time 0.00
Received By adarroug Date 2008-11-19 Time 10:02 Sent To Z
Notes
2008-11-19 10:07:49TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-07-03 Time   Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 16:12 Sent To  
Notes
2008-06-16 16:12:42TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2008-12-17 Cont ID  
Sent By rkussner Date 2008-12-17 Time 14:27 Rev Time 0.00
Received By rkussner Date 2008-12-17 Time 14:27 Sent To PC
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-12-02 Cont ID  
Sent By rkussner Date 2008-12-02 Time 18:30 Rev Time 0.00
Received By rkussner Date 2008-12-02 Time 18:30 Sent To PC
Notes
2008-12-02 18:40:00***LANDSCAPE REVIEW FAILED***
  
 1. PURSUANT TO SECTION 94-441 (C) (2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE,
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.
  
 2. SUBMIT A COMPLETE LANDSCAPE PLAN AND CALCULATIONS
 NECESSARY TO DEMONSTRATE COMPLIANCE WITH THE LANDSCAPE
 ORDINANCE.
  
 3. THE PLAN SHALL CONTAIN A PLANT LIST WITH THE PLANT
 NAMES, QUANTITY, SIZE AND SPACING.
  
 4. IT SHALL BE DRAWN TO SCALE.
  
 5. ALL UTILITIES, OVERHEAD LINES, TREE CANOPIES FROM
 TREES LOCATED ON NEIGHBORING PROPERTIES IN CLOSE
 PROXIMITY TO SHARED PROPERTY LINES AND ANYTHING ELSE
 THAT MAY INTERFERE WITH PROPOSED LANDSCAPING SHALL BE
 SHOWN ON THE PLAN.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-08-07 Cont ID  
Sent By rregueir Date 2009-08-07 Time 14:08 Rev Time 0.00
Received By rregueir Date 2009-08-07 Time 13:27 Sent To  
Notes
2009-08-07 14:08:46REVISED PAGE 8 DATED 7/29/09 **PROVISO**
  
 THE PROPOSED SCOPE OF WORK SHOWS AN ATTACHED GARAGE AND
 GAS APPLIANCES. AS SUCH, CARBON MONOXIDE ALARMS ARE
 REQUIRED WITHIN 10 FEET OF EVERY SLEEPING ROOM IN
 ACCORDANCE WITH FLORIDA STATUTE 553.885. REVISE PAGE 7
 SHOWING PROPOSED LOCATION OF C.O. ALARMS.
  
 IF YOU HAVE ANY QUESTIONS REGARDING THIS OR ANY OTHER
 MATTER RELATED TO THIS PROJECT PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-12-14 Cont ID  
Sent By rregueir Date 2008-12-14 Time 13:43 Rev Time 0.00
Received By rregueir Date 2008-12-14 Time 13:43 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-18 Cont ID  
Sent By tgordon Date 2008-06-18 Time 09:39 Rev Time 1.00
Received By tgordon Date 2008-06-18 Time 09:39 Sent To P
Notes
2008-06-18 09:49:19PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 2) NEED TO SHOW THE SUPPLY AND RETURN AIR GRILL SIZES
 AND CFM'S ON THE MECHANICAL PLAN, PER 2004 WPB AMEND.
 106.3.5.4 (10).
  
 3) THE EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN IS
 SHOWING THE WRONG MODEL NUMBER AND HEATER KW FOR AIR
 HANDLER UNIT #1 (SEE RED LINE INFORMATION ON MECHANICAL
 PLAN), PLEASE CORRECT PER 2004 WPB AMEND.106.3.5.4
 (10).
  
 4) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status N Date 2009-08-07 Cont ID  
Sent By kstevens Date 2009-08-07 Time 17:45 Rev Time 0.00
Received By kstevens Date 2009-08-07 Time 17:45 Sent To  
Notes
2009-08-07 17:45:45NO PLUMBING REVISION SUBMITTED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-12-11 Cont ID  
Sent By kstevens Date 2008-12-11 Time 13:42 Rev Time 0.00
Received By kstevens Date 2008-12-11 Time 13:42 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-06-23 Cont ID  
Sent By mperson Date 2008-06-23 Time 14:31 Rev Time 0.00
Received By mperson Date 2008-06-23 Time 14:31 Sent To B
Notes
2008-06-23 14:51:14PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 3, PROPOSED FLOOR PLAN: PLEASE CLARIFY IF A
 NEW DBL SINK W/DISP & DW IS BEING INSTALLED OR IF THE
 EXISTING ARE BEING REUSED. PER FBC- PLUMBING SECTION
 401.1 SCOPE.
  
 2. SHEET 7,SANITARY RISER AT MASTER BATH: THE RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN ON SHEET 3.
 CLEARLY IDENTIFY ALL PROPOSED FIXTURES ON THE RISER
 DIAGRAM. IT APPEARS THAT THERE ARE 2 WATER/CLOSETS
 BEING INDICATED INSTEAD OF ONE. PER FBC- PLUMBING
 SECTION 401.1 SCOPE.
  
 3. SHEET 7, SANITARY RISER AT BATH #3 & UTILITY: THE
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN ON SHEET
 3. THE WASHING MACHINE IS BEING INDICATED IN THE WRONG
 LOCATION AND THE LAUNDRY TUB IS NOT BEING INDICATED AT
 ALL. PER FBC- PLUMBING SECTION 701.1 SCOPE.
 NOTE: THE WASHING MACHINE MUST DRAIN DOWNSTREAM OF THE
 WET VENTED BATHROOM GROUP. PER FBC- PLUMBING SECTION
 909.1 WET VENT PERMITTED.
  
 4. SHEET 7, ON BOTH THE MASTER BATH AND BATH #3
 SANITARY RISER DIAGRAMS: CLEARLY INDICATE THE CLEANOUT
 AT THE JUCTION OF THE BUILDING DRAIN AND BUILDING SEWER
 AS BEING A TWO-WAY CLEANOUT. PER FBC- PLUMBING SECTION
 708.3.5.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-12-01 Cont ID  
Sent By mcruz Date 2008-12-01 Time 11:39 Rev Time 0.00
Received By mcruz Date 2008-12-01 Time 11:38 Sent To L
Notes
2008-12-01 11:39:28**LANDSCAPE PLAN SHALL BE APPROVED PRIOR TO RECEIVING
 FINAL C.O.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-17 Cont ID  
Sent By choops Date 2008-06-17 Time 09:56 Rev Time 0.00
Received By choops Date 2008-06-17 Time 09:52 Sent To E
Notes
2008-06-17 10:08:29***FAILED***
  
  
 1)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDRS.
  
 PLEASE SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH
 SECTIONS 94-442 AND 94-445 OF THE ZLDRS.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 3)SITE PLAN (SHEET 1) SHOWS A DRIVEWAY, IS THIS TO
 BE INCLUDED WITH THE SCOPE OF WORK?IF NOT, DELETE
 FROM PLANS.IF SO, INCLUDE DIMENSIONS AND SQUARE
 FOOTAGE OF ALL PROPOSED AND ANY EXISTING CONCRETE.
  
 4)INDICATE SETBACK DIMENSIONS FROM EVERYTHING THAT
 IS BEING PROPOSED TO ALL ADJACENT PROPERTY LINES.
  
 5)SOME SETBACK DIMENSIONS DO NOT MATCH FROM SURVEY
 TO SITE PLAN, PLEASE CLARIFY.
  
 6)ON THE ELEVATIONS (SHEET 6), INDICATE THE HEIGHT
 OF THE PROPOSED ADDITIONS FROM GRADE TO THE MIDPOINT OF
 THE ROOF'S PITCH.NOTE: MUST NOT EXCEED 30 FEET.
  
 7)ON THE ELEVATIONS (SHEET 6), INDICATE THE HEIGHT
 OF THE PROPOSED COPULAS FROM GRADE TO THEIR UPPERMOST
 POINT.NOTE: MUST NOT EXCEED 33 FEET.
  
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - SF RACK