Plan Review Details - Permit 08060438
Plan Review Stops For Permit 08060438
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-08-06 Cont ID  
Sent By rmcdouga Date 2008-08-06 Time 07:56 Rev Time 0.00
Received By rmcdouga Date 2008-08-06 Time 07:56 Sent To  
Notes
2008-08-06 07:56:36BUILDING PROVISO
  
 1) SUBMIT TWO COPIES OF THE MANUFACTURERS
 SPECIFICATIONS FOR THE ICYNENE.
  
 2) SUBMIT TWO COPIES OF REVISED ENERGY CALCULATION
 FORMS SHOWING SINGLE ASSEMBLY FOR THE ICYNENE
 INSULATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-14 Cont ID  
Sent By rmcdouga Date 2008-07-14 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2008-07-14 Time 16:50 Sent To  
Notes
2008-07-14 16:33:102004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SURVEY/SITE PLAN INDICATING THE DISTANCE TO
 PROPERTY LINES AND ADJACENT STRUCTURES. IF DISTANCES TO
 PROPERTY LINES ARE LESS THAN 6 FEET,SPECIFY THE
 DISTANCE TO STRUCTURES ON THE ADJACENT PARCELS. SEE FBC
 R302.1 EXTERIOR WALLS. EXTERIOR WALLS SEPARATED BY LESS
 THAN 6 FEET (1828 MM) SHALL HAVE NOT LESS THAN A
 ONE-HOUR FIRE-RESISTIVE RATING WITH EXPOSURE FROM BOTH
 SIDES. PROJECTIONS SHALL NOT EXTEND TO A POINT CLOSER
 THAN 4 FEET (1220 MM) FROM AN ADJACENT PROJECTION OR
 WALL.
  
 4) THE WALL SECTION ON A2 SPECIFIES 8D COMMON NAILS FOR
 FASTENING THE ROOF SHEATHING. FBC R803.2.3.1 SHEATHING
 FASTENINGS. WOOD STRUCTURAL PANEL SHEATHING SHALL BE
 FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6
 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT
 INTERMEDIATE FRAMING. WHERE ROOF FRAMING WITH A
 SPECIFIC GRAVITY, 0.42 < G < 0.49 IS USED, SPACING OF
 RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN
 NAILING ZONE 3 FOR 130 MPH OR GREATER DESIGN WIND
 SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1 . PLEASE
 REVISE.
  
 5) THE WALL SECTION ON A2 SPECIFIES BOTH FIBERGLASS AND
 ICYNENE ATTIC INSULATION. PLEASE SPECIFY ONE. FBC
 CHAPTER 13.
  
 6) THE WALL SECTION ON A2 SPECIFIES R-19 ATTIC
 INSULATION AND THE ENERGY CALCULATION FORM SPECIFIES
 R-30. PLEASE CORRECT. FBC CHAPTER 13.
  
 7) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 /
 8 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS. ALSO SEE FBC R806.3
  
 8) THE WALL SECTION ON A2 AND FOUNDATION DETAIL ON S1
 SPECIFIES 3/4" PLYWOOD AND 2 X 12 FLOOR TRUSSES WHERE A
 CONCRETE SLAB IS SHOWN. PLEASE CORRECT. FBC R 401.2
  
 9) THE WALL SECTION ON A2 SPECIFIES FLOOR TRUSSES AT
 THE ROOF TRUSS LOCATION. PLEASE CORRECT. FBC R 802
  
 10) THE WALL SECTION ON A2 SPECIFIES ASPHALT TILES.
 PLEASE REVISE TO ASPHALT SHINGLES. DCA RULE 9B-72.
  
 11) THE MAXIMUM WINDOW AND DOOR PRESSURES ON SHEETS A1
 AND S2 DO NOT AGREE. PLEASE REVISE. SEE TABLE
 R301.2(2).
  
 12) ON SHEET S2 IMPACT PROTECTION IS SPECIFIED AS
 SHUTTERS AND PRODUCT APPROVALS ARE FOR IMPACT GLAZING.
 PLEASE CLARIFY. FBC R301.2.1.2
  
 13) THE FOUNDATION PLAN ON S1 AND THE ROOF FRAMING PLAN
 ON S2 ARE BOTH LABELED 4 ON A2. PLEASE CLARIFY.
  
 14) SPECIFY THE REQUIRED BEARING CAPACITY OF THE SOIL
 ON THE PLANS. FBC R401.2
  
 15) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR
 TERMITES IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
  
 16) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY CALCULATION FORMS. FBC CHAPTER 13.
  
 17) THE ENERGY CALC. FORM INDICATES THAT THE CEILING
 FAN CREDIT IS BEING TAKEN, HOWEVER, THE PLANS DO NOT
 SPECIFY A CEILING FAN IN THE NEW GUEST BEDROOM. PLEASE
 CORRECT. SEE FBC CHAPTER 13.
  
 18) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS THAT HAVE BEEN APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. SEE DCA RULE 9B-72
 AND FBC 106.3.3* CITY AMENDMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-04 Cont ID  
Sent By btrobaug Date 2008-08-04 Time 14:46 Rev Time 0.00
Received By btrobaug Date 2008-08-04 Time 14:35 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-17 Cont ID  
Sent By btrobaug Date 2008-06-17 Time 11:44 Rev Time 0.00
Received By btrobaug Date 2008-06-17 Time 10:45 Sent To M
Notes
2008-06-17 11:19:26 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE NEW GUEST BEDROOM NEEDS A RECEPTACLE TO COMPLY
 WITH 210.52(A)(1).
  
 2} LOCATE PANEL "B" ON THE PLAN. 106.1.3 FBC AS
 AMENDED.
  
 3} THE BATH CIRCUIT FOR THE NEW MASTER BATH MUST COMPLY
 WITH 210.11(C)(3). THE PANEL SCHEDULE PROVIDED FOR
 PANEL "B" DOES NOT INCLUDE THAT CIRCUIT. IT IS UNCLEAR
 IF THAT CIRCUIT IS SUPPLIED FROM THE EXISTING PANEL.
  
 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE THE
 SMOKE ALARMS ON THE PLAN AND NOTE THE INTERCONNECTION
 REQUIREMENT WITH THE EXISTING ALARMS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-24 Cont ID  
Sent By rregueir Date 2009-01-24 Time 13:20 Rev Time 0.00
Received By rregueir Date 2009-01-20 Time 15:34 Sent To  
Notes
2009-01-20 15:35:06TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-23 Cont ID  
Sent By adarroug Date 2008-07-23 Time 11:22 Rev Time 0.00
Received By adarroug Date 2008-07-23 Time 11:22 Sent To Z
Notes
2008-07-23 11:23:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-14 Cont ID  
Sent By rmcdouga Date 2008-07-14 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2008-06-16 Time 15:49 Sent To  
Notes
2008-06-16 15:51:52TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-01-27 Cont ID  
Sent By rregueir Date 2009-01-27 Time 16:07 Rev Time 0.00
Received By rregueir Date 2009-01-27 Time 16:05 Sent To PC
Notes
2009-01-27 16:07:10REVISED AC PLAN, ENERGY CALCS, COOLING LOAD CALCS AND
 LETTER FROM ARCHITECT RELEASING DESIGNER
 RESPONSIBILITIES FOR HVAC PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2009-01-24 Cont ID  
Sent By rregueir Date 2009-01-24 Time 13:39 Rev Time 0.00
Received By rregueir Date 2009-01-24 Time 13:20 Sent To PC
Notes
2009-01-24 13:39:27ORIGINAL MECHANICAL PLANS ARE SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD. ANY REVISIONS TO PLANS MUST BE
 DONE BY THE ARCHITECT OF RECORD FOR THIS PROJECT IN
 ACCORDANCE WITH FS 481.
  
 REVISIONS AND CALCULATIONS ARE OTHERWISE CODE
 COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-08-12 Cont ID  
Sent By tgordon Date 2008-08-12 Time 08:20 Rev Time 0.40
Received By tgordon Date 2008-08-12 Time 08:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-08-05 Cont ID  
Sent By tgordon Date 2008-08-05 Time 08:30 Rev Time 0.45
Received By tgordon Date 2008-08-05 Time 08:30 Sent To P
Notes
2008-08-05 08:37:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 6-17-08 NOTE #5. THE AIR
 HANDLER MODEL NUMBERS TWE0400E13FB LISTED ON THE A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE AND THE CONDENSER UNIT MODEL NUMBER
 2TTX5024A1000A STATUS HAS BEEN DISCONTINUED, PLEASE
 CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004 FBC
 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-17 Cont ID  
Sent By tgordon Date 2008-06-17 Time 14:26 Rev Time 0.45
Received By tgordon Date 2008-06-17 Time 14:26 Sent To P
Notes
2008-06-17 15:04:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE ENERGY CALCULATIONS NEED TO BE SIGNED BY THE
 PREPARER ALSO, PER 2004 FBC 13-103.1.1,
  
 2) THE ENERGY CALCULATIONS LINE 15 IS TAKING THE
 CEILING FAN CREDIT. THE PLANS SHOW NO CEILING FAN IN
 THE NEW GUEST BEDROOM SO THIS CREDIT CAN NOT BE TAKEN,
 PER 2004 FBC 13-607.2.A.3.1.
  
 3) ENERGY CALCULATIONS LINE 10A SHOWS R-30 FOR CEILING
 INSULATION, PLAN A-2 IS SHOWING R-19 FOR CEILING
 INSULATION. PLEASE CORRECT PLANS PER 2004 FBC
 13-103.3.
  
 4) THE COOLING LOAD CALCULATIONS ARE CALLING FOR 14,545
 TOTAL COOLING BTU'S, THE MECHANICAL PLAN EQUIPMENT
 SCHEDULE IS SHOWING 27,000 TOTAL COOLING BTU'S, THE
 PLANS CAN ONLY CALL FOR 15% MORE TOTAL COOLING BTU'S
 THAN THE COOLING LOAD CALCULATIONS, PER 2004 FBC
 13-607.1.ABC.1.1. A NOTE ON PLAN MEP-1 STATES 'SMALLEST
 AVAILABLE PRODUCT LINE ETC.' SEE ATTACHED ARI PRINT-OUT
 SHOWING TRANE MAKES 83 SYSTEMS THAT MEET THE
 REQUIREMENTS OF THE COOLING LOAD CAL'S AND ENERGY
 CAL'S. PLEASE CORRECT.
  
 5)THE AIR HANDLER MODEL NUMBERS TWE0400E13FB LISTED
 ON THE A/C EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE
 ARI DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-08-05 Cont ID  
Sent By mperson Date 2008-08-05 Time 13:25 Rev Time 0.00
Received By mperson Date 2008-08-05 Time 13:25 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-06-23 Cont ID  
Sent By mperson Date 2008-06-23 Time 11:46 Rev Time 0.00
Received By mperson Date 2008-06-23 Time 11:46 Sent To B
Notes
2008-06-23 13:26:21PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-1 FLOOR PLAN: CLEARLY IDENTIFY ALL PROPOSED
 PLUMBING FIXTURES ON THE FLOOR PLAN. SHEET MEP-1
 SANITARY RISER DIAGRAM IS INDICATING A SHOWER, HOWEVER
 ON SHEET A-1 FLOOR PLAN THIS FIXTURE APPEARS TO BE A
 TUB. PLEASE CLARIFY AND CORRELATE SHEETS. PER FBC-
 PLUMBING SECTION 401.1 SCOPE.
  
 2. SHEET MEP-1 SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN ON SHEET A-1 PER THE FOLLOWING.
  
 A} ONE LAVATORY IS MISSING FROM THE RISER DIAGRAM.
  
 B} THE WASHING MACHINE IS MISSING FROM THE RISER
 DIAGRAM.
  
 PLEASE CLEARLY INDICATE ALL PROPOSED FIXTURES ON THE
 RESUBMITTED SANITARY RISER DIAGRAM. PER FBC- PLUMBING
 SECTION 701.1 SCOPE. PLEASE CLEARLY INDICATE THE
 FOLLOWING FOR THE WASHING MACHINE.
  
 C} 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 D} 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
  
 E} 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE
 3".
  
 F} 708.9 ACCESS. ACCESS SHALL BE
 NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE
 LOCATED AT 4' A.F.F.
 PROVIDED TO ALL CLEANOUTS.
  
 G} PER FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 NOTE: THE WASHING MACHINE SHALL DISCHARGE DOWNSTREAM
 OF THE PROPOSED WET VENTED BATHROOM GROUP.
  
 3. SHEET MEP-1 SANITARY RISER DIAGRAM: THE SHOWER
 REQUIRES A WATER-SEAL TRAP AND THE WATER CLOSET DOES
 NOT REQUIRE A WATER-SEAL TRAP DUE TO HAVING AN INTEGRAL
 TRAP. PER FBC- PLUMBING SECTION 1002.1 FIXTURE TRAPS.
  
 4. SHEET MEP-1 SANITARY RISER DIAGRAM: CLEARLY SIZE
 THE LAVATORY TRAP. PER (W.P.B. AS AMENDED) SECTION
 106.3.5.4 (9) PLUMBING.
  
 5. SHEET MEP-1 PLUMBING NOTES #11: AIR CHAMBERS ARE
 NOT APPROVED UNLESS INSTALLED PER "STANDARD PDI-WH-201,
 A RECHARGEABLE TYPE OF AIR CHAMBER" IS INSTALLED AND A
 DETAIL OF THIS TYPE OF AIR CHAMBER IS REQUIRED TO BE ON
 THE PLANS OR DELETE AIR CHAMBER FROM THE PLANS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-08-03 Cont ID  
Sent By mcruz Date 2008-08-03 Time 12:31 Rev Time 0.00
Received By mcruz Date 2008-08-03 Time 12:31 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-17 Cont ID  
Sent By choops Date 2008-06-17 Time 08:22 Rev Time 0.00
Received By choops Date 2008-06-17 Time 08:22 Sent To E
Notes
2008-06-17 08:27:14***FAILED***
  
  
 1)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDRS.
  
 PLEASE SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH
 SECTIONS 94-442 AND 94-445 OF THE ZLDRS.
  
 2)SITE PLAN WITH PROPOSED ADDITION SHALL INDICATE
 SETBACK DIMENSIONS FROM THE PROPOSED TO ALL ADJACENT
 PROPERTY LINES.
  
 NOTE:PURSUANT TO SECTION 94-72 OF THE ZLDRS:
  
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING.
 A.FRONT: 25 FEET;
 B.REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH,
 WHICHEVER IS LESS;
 C.SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL BETWEEN THE
 TWO SIDES.
  
 3)INDICATE SETBACK DIMENSIONS OF EXISTING COVERED
 PATIO STRUCTURE, AT THE SOUTHWEST CORNER OF THE
 PROPERTY, TO ALL ADJACENT PROPERTY LINES.
  
 4)INDICATE THE SEPARATION DISTANCE FROM THE PROPOSED
 ADDITION TO THE EXISTING COVERED PATIO STRUCTURE.
  
 NOTE:DEPENDENT ON THE EXISTING COVERED PATIO
 SETBACKS, THE PROPOSED ADDITION MAY BE REQUIRED TO
 MAINTAIN A MINIMUM SEPARATION DISTANCE OF 6' FROM THE
 COVERED PATIO STRUCTURE.
  
 5)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - SF RACK