| 2008-08-07 13:35:18 | GAS PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND |
| | WITH THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. AT A MINIMUM THE GAS RISER DIAGRAM SHALL REFLECT |
| | WHAT IS BEING INDICATED ON THE SUBMITTED SURVEY. THE |
| | SUBMITTED GAS RISER DIAGRAM IS INDICATING THE GAS METER |
| | AS BEING INSTALLED UNDERGROUND WITH THE ONLY PIPING |
| | MATERIAL BENG USED AS PE. PLEASE CORRECT THE GAS |
| | ISOMETRIC TO INDICATE THE CORRESPONDING LENGTHS TO ALL |
| | CUT SECTIONS OF PIPE AS WELL AS INDICATING THE PIPING |
| | MATERIAL TO ALL CUT SECTIONS OF PIPE. PER FBC-2004 FUEL |
| | GAS SECTION 401.1 SCOPE. |
| | |
| | ** RESPONSE NOTED, HOWEVER THE COMMENT WAS ONLY |
| | PARTIALLY ADDRESSED. THE RESUBMITTED GAS ISOMETRIC |
| | STILL IS NOT INDICATING THE CORRESPONDING LENGTHS TO |
| | ALL CUT SECTIONS OF PIPE. THE RESUBMITTED GAS ISOMETRIC |
| | IS NOW INDICATING ONLY ONE CUT SECTION OF PE PIPE @ |
| | 40'. WHAT ARE THE CORRESPONDING LENGTHS TO THE OTHER |
| | CUT SECTIONS OF PIPE? PLEASE KNOW THAT THE LONGEST |
| | LENGTH OF THE SYSTEM IS THE ADDED SUM OF ALL CUT |
| | SECTIONS OF PIPE FROM THE METER TO THE FARTHEST |
| | APPLIANCE. THE LONGEST RUN INDICATED ON THE RESUBMITTED |
| | PLANS IS 40', HOWEVER THIS IS WRONG DUE TO NOT ALL |
| | CORRESPONDING LENGTHS ARE INDICATED FOR ALL CUT SECTIOS |
| | OF PIPE. PLEASE ALSO KNOW THAT THE EXISTING SYSTEM IS |
| | UNDERSIZED PER FBC-2004 FUEL GAS CODE TABLES402.4(2) |
| | & 402.4(20) DUE TO THE REVISED LONGEST LENGTH OF 40'. |
| | THE GAS SYSTEM WILL NEED TO BE UPGRADED TO A 2 PSI |
| | DELIVERY PRESSURE AND SO NOTED ON THE RESUBMITTED PLANS |
| | WITH A CLEAR LOCATION OF THE MP REGULATORS (TWO COPIES |
| | OF MANUFACTURER SPECIFICATIONS OF THE MP REGULATORS |
| | WILL BE REQUIRED CLEARLY INDICATING THE MAKE, MODEL |
| | NUMBER, BTU LOAD CAPACITY, AND A LISTING FROM A |
| | NATIONALY RECOGNIZED TESTING LABORATORY SUCH AS CSA, |
| | AGA, UL). PLEASE REFERENCE THE SIZING TABLES ATTACHED |
| | TO THESE COMMENTS INDICATING THIS. PER FBC-2004 FUEL |
| | GAS SECTION 401.1 SCOPE. |
| | |
| | 2. "OK" COMMENT ADDRESSED. |
| | |
| | 3. "OK" COMMENT ADDRESSED. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: REFERENCE COMMENT #1. |
| | |
| | **RESPONSE NOTED, HOWEVER THE RESUBMITTED PLANS ARE |
| | STILL NOT COMPLIANT. PLEASE REFERENCE COMMENT #1 AND |
| | COMPLY. |
| | |
| | 5. "OK" COMMENT ADDRESSED. |
| | |
| | 6. "OK" COMMENT ADDRESSED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |