Plan Review Details - Permit 08060436
Plan Review Stops For Permit 08060436
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-07-22 Cont ID  
Sent By lmartine Date 2008-07-22 Time 14:58 Rev Time 0.00
Received By lmartine Date 2008-07-22 Time 14:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-06-19 Cont ID  
Sent By btrobaug Date 2008-06-19 Time 10:01 Rev Time 0.00
Received By btrobaug Date 2008-06-19 Time 09:44 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-08-18 Cont ID  
Sent By mperson Date 2008-08-18 Time 09:07 Rev Time 0.00
Received By mperson Date 2008-08-18 Time 09:07 Sent To PC
Notes
2008-08-18 09:09:35****************PROVISO****************
 A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-08-07 Cont ID  
Sent By mperson Date 2008-08-07 Time 13:24 Rev Time 0.00
Received By mperson Date 2008-08-07 Time 13:24 Sent To PC
Notes
2008-08-07 13:35:18GAS PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND
 WITH THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. AT A MINIMUM THE GAS RISER DIAGRAM SHALL REFLECT
 WHAT IS BEING INDICATED ON THE SUBMITTED SURVEY. THE
 SUBMITTED GAS RISER DIAGRAM IS INDICATING THE GAS METER
 AS BEING INSTALLED UNDERGROUND WITH THE ONLY PIPING
 MATERIAL BENG USED AS PE. PLEASE CORRECT THE GAS
 ISOMETRIC TO INDICATE THE CORRESPONDING LENGTHS TO ALL
 CUT SECTIONS OF PIPE AS WELL AS INDICATING THE PIPING
 MATERIAL TO ALL CUT SECTIONS OF PIPE. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
  
 ** RESPONSE NOTED, HOWEVER THE COMMENT WAS ONLY
 PARTIALLY ADDRESSED. THE RESUBMITTED GAS ISOMETRIC
 STILL IS NOT INDICATING THE CORRESPONDING LENGTHS TO
 ALL CUT SECTIONS OF PIPE. THE RESUBMITTED GAS ISOMETRIC
 IS NOW INDICATING ONLY ONE CUT SECTION OF PE PIPE @
 40'. WHAT ARE THE CORRESPONDING LENGTHS TO THE OTHER
 CUT SECTIONS OF PIPE? PLEASE KNOW THAT THE LONGEST
 LENGTH OF THE SYSTEM IS THE ADDED SUM OF ALL CUT
 SECTIONS OF PIPE FROM THE METER TO THE FARTHEST
 APPLIANCE. THE LONGEST RUN INDICATED ON THE RESUBMITTED
 PLANS IS 40', HOWEVER THIS IS WRONG DUE TO NOT ALL
 CORRESPONDING LENGTHS ARE INDICATED FOR ALL CUT SECTIOS
 OF PIPE. PLEASE ALSO KNOW THAT THE EXISTING SYSTEM IS
 UNDERSIZED PER FBC-2004 FUEL GAS CODE TABLES402.4(2)
 & 402.4(20) DUE TO THE REVISED LONGEST LENGTH OF 40'.
 THE GAS SYSTEM WILL NEED TO BE UPGRADED TO A 2 PSI
 DELIVERY PRESSURE AND SO NOTED ON THE RESUBMITTED PLANS
 WITH A CLEAR LOCATION OF THE MP REGULATORS (TWO COPIES
 OF MANUFACTURER SPECIFICATIONS OF THE MP REGULATORS
 WILL BE REQUIRED CLEARLY INDICATING THE MAKE, MODEL
 NUMBER, BTU LOAD CAPACITY, AND A LISTING FROM A
 NATIONALY RECOGNIZED TESTING LABORATORY SUCH AS CSA,
 AGA, UL). PLEASE REFERENCE THE SIZING TABLES ATTACHED
 TO THESE COMMENTS INDICATING THIS. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
  
 2. "OK" COMMENT ADDRESSED.
  
 3. "OK" COMMENT ADDRESSED.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #1.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED PLANS ARE
 STILL NOT COMPLIANT. PLEASE REFERENCE COMMENT #1 AND
 COMPLY.
  
 5. "OK" COMMENT ADDRESSED.
  
 6. "OK" COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-06-23 Cont ID  
Sent By mperson Date 2008-06-23 Time 10:36 Rev Time 0.00
Received By mperson Date 2008-06-23 Time 10:36 Sent To B
Notes
2008-06-23 11:08:20GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE ON THE
 RESUBMITTED GAS ISOMETRIC RISER DIAGRAM.
  
 1. AT A MINIMUM THE GAS RISER DIAGRAM SHALL REFLECT
 WHAT IS BEING INDICATED ON THE SUBMITTED SURVEY. THE
 SUBMITTED GAS RISER DIAGRAM IS INDICATING THE GAS METER
 AS BEING INSTALLED UNDERGROUND WITH THE ONLY PIPING
 MATERIAL BENG USED AS PE. PLEASE CORRECT THE GAS
 ISOMETRIC TO INDICATE THE CORRESPONDING LENGTHS TO ALL
 CUT SECTIONS OF PIPE AS WELL AS INDICATING THE PIPING
 MATERIAL TO ALL CUT SECTIONS OF PIPE. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
  
 2. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 BEING USED ON THE RESUBMITTED GAS ISOMETRIC.NOTE: THE
 TYPE OF GAS IS INDICATED ON THE PERMIT APPLICATION AND
 THE SURVEY, HOWEVER IT IS NOT INDICATED ON THE GAS
 ISOMETRIC. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: CLEARLY INDICATE THE BTU LOAD OF THE PROPOSED
 GENERATOR PER THE SUBMITTED PROPOSED GENERATOR
 MANUFACTURE SUBMITTAL SHEETS.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #1.
  
 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 6. THE SUBMITTED PIPE SIZING TABLES ARE WRONG PER THE
 FOLLOWING.
 NOTE: FLORIDA PUBLIC UTILITIES IS PROVIDING A 12" WC
 DELIVERY PRESSURE WITH A .5" WC PRESSURE DROP. THE
 FOLLOWING TABLES WILL BE USED FROM THE FBC-2004 FUEL
 GAS CODE:
 SCHEDULE 40 METALLIC PIPE= TABLE 402.4(2)
 POLYETHYLENE PLASTIC PIPE (PE)= TABLE 402.4(20)
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-14 Cont ID  
Sent By adarroug Date 2008-08-14 Time 14:14 Rev Time 0.00
Received By adarroug Date 2008-08-14 Time 14:14 Sent To Z
Notes
2008-08-14 14:14:45TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-30 Cont ID  
Sent By adarroug Date 2008-07-30 Time 14:35 Rev Time 0.00
Received By adarroug Date 2008-07-30 Time 14:35 Sent To Z
Notes
2008-07-30 14:35:39TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-30 Cont ID  
Sent By btrobaug Date 2008-07-22 Time 14:31 Rev Time  
Received By adarroug Date 2008-06-16 Time 16:07 Sent To  
Notes
2008-06-16 16:07:40TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-06-19 Cont ID  
Sent By btrobaug Date 2008-06-19 Time 14:56 Rev Time 0.20
Received By tgordon Date 2008-06-19 Time 14:56 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-08-15 Cont ID  
Sent By adavila Date 2008-08-15 Time 13:39 Rev Time 0.00
Received By adavila Date 2008-08-15 Time 13:39 Sent To I
Notes
2008-08-15 13:39:44PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-08-04 Cont ID  
Sent By adavila Date 2008-08-04 Time 15:41 Rev Time 0.00
Received By adavila Date 2008-08-04 Time 15:41 Sent To  
Notes
2008-08-04 15:46:52PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.REPEAT COMMENT - INDICATE SETBACK DIMENSIONS FROM
 PROPOSED GENERATOR EQUIPMENT TO ALL PROPERTY LINES.AS
 PER SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 2.ACCORDING TO THE SURVEY THE GENERATOR WILL BE 4
 FEET FROM THE SIDE PROPERTY LINE.THE SIDE SETBACK AT
 THIS LOCATION IS 8.5 FEET.THEREFORE, THE GENERATOR
 SHALL BE A MINIMUM OF 4.5 FEET FROM THE EAST PROPERTY
 LINE TO THE FURTHEST PROJECTION POINT OF THE
 GENERATOR.
  
 3.PLEASE CLEARLY INDICATE THE SETBACK DIMENSIONS ON
 BOTH COPIES OF THE SURVEY.THE SETBACK DIMENSIONS
 SHALL BE PROVIDED FROM THE PROPERTY LINE TO THE CLOSEST
 PROJECTION POINT OF THE GENERATOR.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-17 Cont ID  
Sent By choops Date 2008-06-17 Time 11:51 Rev Time 0.00
Received By choops Date 2008-06-17 Time 11:51 Sent To E
Notes
2008-06-17 11:53:10***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED
 GENERATOR EQUIPMENT TO ALL PROPERTY LINES.AS PER
 SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - GENRES BOX