| 2008-06-17 12:08:54 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | 1. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | 2. MANUF. SPECIFICATION SHEETS REQUIRED FOR |
| | THE GAS REGULATORS. INDICATE THE MODEL |
| | NUMBER FOR REGULATORS. REGULATORS SHALL |
| | BE LISTED. |
| | |
| | 3. REVISION REQUIRED FOR SHT P3.16 |
| | INDICATING THE CORRECT INLET PRESSURE |
| | FROM THE METER, AND SHOWING UNIONS |
| | DOWNSTREAM OF THE SHUT OFF VALVES FOR |
| | THE REGULATORS.-PIPE SIZING SHALL BE |
| | CHECKED WHEN INLET PRESSURE IS |
| | CLARIFIED.--(REVISION SHALL BE SUBMITTED UNDER |
| | BUILD-COM PERMIT 05091265) |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |