Plan Review Details - Permit 08060355
Plan Review Stops For Permit 08060355
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-19 Cont ID  
Sent By btrobaug Date 2008-06-19 Time 13:23 Rev Time 0.00
Received By btrobaug Date 2008-06-19 Time 13:14 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-13 Cont ID  
Sent By btrobaug Date 2008-06-13 Time 11:33 Rev Time 0.00
Received By btrobaug Date 2008-06-13 Time 11:31 Sent To FIRE
Notes
2008-06-13 11:33:02 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-06-19 Cont ID  
Sent By mawillia Date 2008-06-19 Time 14:14 Rev Time 0.00
Received By mawillia Date 2008-06-19 Time 13:46 Sent To E
Notes
2008-06-19 14:00:29*****PROVISO****
  
  
  
 DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO BE
 EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS CONTROL
 SYSTEM PROVIDED THAT THE CRITERIA OF NFPA 101, LIFE
 SAFETY CODE, 2003 EDITION-SECTION 7.2.1.6.2
  
  
 (ALL OTHER COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED)
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-17 Cont ID  
Sent By mawillia Date 2008-06-17 Time 13:48 Rev Time 0.00
Received By mawillia Date 2008-06-17 Time 13:22 Sent To  
Notes
2008-06-17 13:39:29*****UNSAT****
  
  
 1.THE ACTUAL JOB SITE LOCATION, INCLUDING THE SUITE
 NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 2.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS
 CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF NFPA 101,
 LIFE SAFETY CODE, 2003 EDITION-SECTION 7.2.1.6.2
  
 3.PROVIDE SPEC SHEETS FOR THE DEVICES ASSOCIATED WITH
 THE ACCESS CONTROL SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-17 Cont ID  
Sent By mawillia Date 2008-06-17 Time 13:22 Rev Time 0.00
Received By mawillia Date 2008-06-13 Time 11:31 Sent To  
Notes
***NONE***