Plan Review Details - Permit 08060355
| Plan Review Stops For Permit 08060355 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-06-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-19 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-19 |
Time |
13:14 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-06-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-13 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-13 |
Time |
11:31 |
Sent To |
FIRE |
|
| Notes |
| 2008-06-13 11:33:02 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS | | | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | | AMENDED. | | | | | | A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED | | | UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID. | | | 108.1 FBC. | | | | | | ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY | | | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. | | | | | | 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.1.3.FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-06-19 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-06-19 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-06-19 |
Time |
13:46 |
Sent To |
E |
|
| Notes |
| 2008-06-19 14:00:29 | *****PROVISO**** | | | | | | | | | | | | DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO BE | | | EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS CONTROL | | | SYSTEM PROVIDED THAT THE CRITERIA OF NFPA 101, LIFE | | | SAFETY CODE, 2003 EDITION-SECTION 7.2.1.6.2 | | | | | | | | | (ALL OTHER COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN | | | ADDRESSED) | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-06-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-06-17 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-06-17 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2008-06-17 13:39:29 | *****UNSAT**** | | | | | | | | | 1.THE ACTUAL JOB SITE LOCATION, INCLUDING THE SUITE | | | NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED | | | PLAN SHEET. | | | | | | 2.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO | | | BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS | | | CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF NFPA 101, | | | LIFE SAFETY CODE, 2003 EDITION-SECTION 7.2.1.6.2 | | | | | | 3.PROVIDE SPEC SHEETS FOR THE DEVICES ASSOCIATED WITH | | | THE ACCESS CONTROL SYSTEM. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-06-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-06-17 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-06-13 |
Time |
11:31 |
Sent To |
|
|
| Notes |
|
|
|