Plan Review Details - Permit 08060325
Plan Review Stops For Permit 08060325
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-07-03 Cont ID  
Sent By mjacobs Date 2008-07-03 Time 13:22 Rev Time 0.00
Received By mjacobs Date 2008-07-03 Time 08:08 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-20 Cont ID  
Sent By mjacobs Date 2008-06-20 Time 15:49 Rev Time 0.00
Received By mjacobs Date 2008-06-20 Time 11:24 Sent To PC
Notes
2008-06-20 15:49:35BUILDING PLAN REVIEW
 PERMIT: 08060325
 ADD: 2777 MUSKEGON WAY
 CONT: VAN NESS & CALLAWAY CONST, INC.
 TEL: (561)278-0872
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)THE PRODUCT APPROVAL SUBMITTED IS FOR SHUTTER SPANS
 90? (7?-6?) OR LESS, SEE PAGES 8 AND 9.THE SHUTTER
 SCHEDULE INDICATES SPANS GREATER THAN 90? THEREFORE; A
 DIFFERENT PRODUCT APPROVAL SHALL BE SUBMITTED FOR THE
 SPANS GREATER THAN 90?.WHEN USING THE EDGE DISTANCE
 FACTORS THE ANCHOR SPACING WILL BE CLOSER ACCORDING TO
 THE FACTOR. PLEASE TAKE THIS INTO CONSIDERATION. IF
 SOME OF THE SHUTTERS SUBSTRATE WILL BE WOOD, INDICATE
 THE INFORMATION ON THE SHUTTER SCHEDULE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-30 Cont ID  
Sent By adarroug Date 2008-06-30 Time 11:08 Rev Time 0.00
Received By adarroug Date 2008-06-30 Time 11:08 Sent To B
Notes
2008-06-30 11:08:50TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-06-20 Time   Rev Time 0.00
Received By adarroug Date 2008-06-12 Time 08:59 Sent To  
Notes
2008-06-12 09:00:00TO "MISC" BOX#1