| 2008-07-17 12:23:39 | 2ND REVIEW: 7-17-08 |
| | SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY |
| | |
| | __OK 1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN |
| | PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE |
| | DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY |
| | AN ENGINEER. DOCUMENTS PREPARED BY AN ENGINEER AND |
| | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED |
| | ORIGINALS FAC61G15-23.002. |
| | |
| | __XX 2.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR |
| | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| | ANOTHER FORMAT. THE SPANS OF THE SHUTTERS INDICATED ON |
| | THE INSTALLATION SCHEDULE DO NOT CORRESPOND WITH THE |
| | OPENING HEIGHTS. IF ONE OF THE OPENINGS HAS A HEIGHT OF |
| | 100 INCHES, HOW CAN THE SPAN BE 163 INCHES?SHOW THE |
| | CORRECT SHUTTER SPANS ON THE INSTALLATION SCHEDULE. |
| | |
| | _OK 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG. |
| | |
| | _XX 4.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS |
| | APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A |
| | HIGHLIGHTER. ON SHEET #7 OF THE PRODUCT APPROVAL THE |
| | DESIGN PRESSURE 47.2 CANNOT BE USED BECAUSE THE HOUSE |
| | IS LOCATED IN AN EXPOSURE C PER YOUR INFORMATION. THE |
| | NEXT DESIGN PRESSURE ON THE ANCHOR SCHEDULE IS 77PSF, |
| | WHICH MEANS THIS ROW SHALL BE USED WHEN INDICATING THE |
| | FASTENER SPACING INSTEAD OF 47.2 PSF. IF MORE THAN ONE |
| | TYPE OF ANCHOR WILL BE USED, MAKE SURE THE CORRECT |
| | DESIGN PRESSURE IS USED. SEE PAGES 7 AND 8. |
| | |
| | _OK 5.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310. |
| | |
| | _OK 6.PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS |
| | WILL BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH |
| | THE INSTALLATION SCHEDULE, ITEM 4 ABOVE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | MJACOBS@WPB. |