Plan Review Details - Permit 08060313
Plan Review Stops For Permit 08060313
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-01-07 Cont ID  
Sent By rmcdouga Date 2009-01-07 Time 13:55 Rev Time 0.00
Received By rmcdouga Date 2009-01-07 Time 13:55 Sent To  
Notes
2009-01-07 14:02:06BUILDING PROVISO
 SUBMIT INSTALLATION / ANCHORING INSTRUCTIONS FOR THE
 EXHAUST FAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-01-02 Cont ID  
Sent By rmcdouga Date 2009-01-02 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2009-01-02 Time 16:59 Sent To  
Notes
2009-01-02 16:59:192004 FBC W/2007 REVISIONS
 CHLORINE STORAGE BUILDING
  
 DENIED BY BUILDING
  
 1) PLEASE SPECIFY THE TYPE OF CONSTRUCTION , OCCUPANCY
 AND SQUARE FOOTAGE OF THE EXISTING STRUCTURE ON THE
 PLANS. FBC 602 AND 302.1
  
 2) SPECIFY THE TYPE AND AMOUNT OF CHLORINE THAT WILL IN
 USE AND STORAGE WITHIN THE BUILDING. FBC SECTION 307.9
 CONTAINS EXCEPTIONS WHICH ALLOW STRUCTURES THAT DO NOT
 CONTAIN MORE THAN THE MAXIMUM ALLOWABLE QUANTITIES PER
 CONTROL AREA OF HAZARDOUS MATERIALS AS SHOWN IN TABLES
 307.7(1) AND (2) TO NOT BE CLASSIFIED AS GROUP H, BUT
 TO BE CLASSIFIED AS THE OCCUPANCY THEY MOST NEARLY
 RESEMBLE. BECAUSE THIS BUILDING DOES NOT MEET THE 50
 FOOT DISTANCE TO LOT LINES THAT IS REQUIRED FOR AN H-3
 OCCUPANCY BY FBC 415.3.1, CONTROL AREAS WILL BE
 REQUIRED. NOTE: TABLE 307.7(2) ALLOWS 810 CUBIC FEET OF
 GAS AGGREGATE QUANTITY IN USE AND STORAGE. THE QUANTITY
 CAN BE INCREASED 100 PER CENT WHEN STORED IN APPROVED
 STORAGE CABINETS, GAS CABINETS OR EXHAUSTED ENCLOSURES
 SEE FOOTNOTE F FOR TABLE 307.7(2).
  
 3) SPECIFY THE REQUIRED FIRE RATING OF THE WALLS AND
 CEILING OF THE CHLORINE ROOM (SEE FBC 414.2 CONTROL
 AREA). FBC 414.2.1 REQUIRES ONE HOUR FIRE RATED WALLS
 AND CEILING.
  
 4) INDICATE THE LOCATIONS AND AMOUNT OF CHLORINE THAT
 WILL BE STORED IN EACH CONTROL AREA. FBC 414.1.3 AND
 TABLE 414.2.2
  
 5) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR EXHAUST VENT. FAC RULE 9B-72
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-12-03 Cont ID  
Sent By rmcdouga Date 2008-12-03 Time 14:10 Rev Time 0.00
Received By rmcdouga Date 2008-12-03 Time 14:10 Sent To  
Notes
2008-12-03 14:10:25DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOOR, WALL LOUVERS, WALL PANELS, ETC. AS
 REQUIRED BY DCA RULE 9B-72.
  
 **THIS ITEM CAN BE ADDRESSED BY SUBMITTING LOCAL OR
 SITE SPECIFIC PRODUCT APPROVALS.
  
 2) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 PREVIOUS COMMENT #8
  
 **HAVE THE DESIGNER OF RECORD REVIEW AND APPROVE THE
 PRODUCT APPROVALS IN WRITING.
  
 3) THE RESPONSE TO COMMENT #13 INDICATES THAT (4) 150
 POUND CYLINDERS OF CHLORINE GAS WILL BE HOUSED IN THIS
 BUILDING. EACH 150 POUND CYLINDER CONTAINS 810 CUBIC
 FEET OF CHLORINE GAS. THEREFORE, THERE WILL BE 3240
 CUBIC FEET OF GAS STORED IN THE BUILDING. THE MATERIAL
 SAFETY DATA SHEET CLASSIFIES CHLORINE AS AN OXIDIZING
 GAS. PER FBC TABLE 307.7(1), THE MAXIMUM ALLOWABLE
 QUANTITY THAT CAN BE STORED (OR IN USE PER FOOTNOTE B)
 IS 1500 CUBIC FEET. IF THIS AMOUNT IS EXCEEDED THEN THE
 OCCUPANCY IS REQUIRED TO BE CONSIDERED H-3. FOOTNOTES D
 AND E TO THE TABLE EACH ALLOW THE QUANTITIES TO BE
 INCREASED 100 PERCENT. THE INCREASE FOR BOTH ARE
 APPLIED ACCUMULATIVELY. SEE FBC 307.1 AND TABLE
 307.7(1)
  
 **THE PROPOSED SAFETY FEATURE DOES NOT ADDRESS THIS
 COMMENT. IT WILL CLOSE THE VALVE BUT DOES NOT CONTAIN
 OR PROTECT THE CYLINDERS.
  
 4) THE SITE PLAN SHOWS THAT THE 1 STORY BUILDING IS
 3.20' TO THE WEST OF THE NEW BUILDING. FBC 704.3
 ADDRESSES BUILDINGS ON THE SAME LOT WITH AN IMAGINARY
 LINE BETWEEN THEM. SEE FBC 702.1 FOR DEFINITION OF FIRE
 SEPARATION DISTANCE. NOTE THAT THE FIRE SEPARATION
 DISTANCE IS NOT THE DISTANCE FROM BUILDING TO BUILDING,
 BUT TO AN IMAGINARY LINE BETWEEN THEM SUCH THAT EACH
 BUILDING COMPLIES WITH TABLE 602 AND TABLE 704.8. TABLE
 602 REQUIRES GROUP H TYPE V-B WITH LESS THAN 5 FEET
 FIRE SEPARATION DISTANCE TO HAVE 3 HOUR FIRE RATED
 WALLS. USING THE EXCEPTION TO 704.3 ALLOWS THE
 BUILDINGS TO BE CONSIDERED AS PORTIONS OF ONE BUILDING
 IF THE AGGREGATE AREA OF THE BUILDINGS IS WITHIN THE
 LIMITS SPECIFIED FOR ONE BUILDING. UNDER 302.3.2
 SEPARATED USES THE NEW H-3 OCCUPANCY WOULD BE REQUIRED
 TO BE SEPARATED FROM THE EXISTING F-1 OCCUPANCY WITH
 ONE HOUR FIRE RATED WALLS. PREVIOUS COMMENTS #9,
 #10,#11 AND #12.
  
 **THE PROPOSED SAFETY FEATURE DOES NOT ADDRESS THIS
 COMMENT. H-3 OCCUPANCY SEPARATION SHALL COMPLY WITH FBC
 TABLE 602 AND 415.3.1 FOR DISTANCE TO LOT LINES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-10-15 Cont ID  
Sent By rmcdouga Date 2008-10-15 Time 16:36 Rev Time 0.00
Received By rmcdouga Date 2008-10-15 Time 13:22 Sent To  
Notes
2008-10-15 13:38:372004 FBC W/2007 REVISIONS
 INSTALL FIBERGLASS STRUCTURE
  
 DENIED BY BUILDING
  
 1) THE ENGINEER FOR SHELTER WORKS IS REQUIRED TO USE AN
 EMBOSSING IMPRESSION SEAL AS SPECIFIED IN FLORIDA
 ADMINISTRATIVE CODE 61G15-23.001 UNDER THE AUTHORITY OF
 FLORIDA STATUTE 471.025. SEE PREVIOUS COMMENT #1.
  
 2) IF THE 10 FOOT SEPARATION IS NOT REQUIRED, THEN
 REMOVE GENERAL NOTE #2 FROM THE THIRD PAGE OF THE
 SHELTER ENGINEERING. PREVIOUS COMMENT #5.
  
 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOOR, WALL LOUVERS, WALL PANELS, ETC. AS
 REQUIRED BY DCA RULE 9B-72.
  
 4) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 PREVIOUS COMMENT #8
  
 5) THE RESPONSE TO COMMENT #13 INDICATES THAT (4) 150
 POUND CYLINDERS OF CHLORINE GAS WILL BE HOUSED IN THIS
 BUILDING. EACH 150 POUND CYLINDER CONTAINS 810 CUBIC
 FEET OF CHLORINE GAS. THEREFORE, THERE WILL BE 3240
 CUBIC FEET OF GAS STORED IN THE BUILDING. THE MATERIAL
 SAFETY DATA SHEET CLASSIFIES CHLORINE AS AN OXIDIZING
 GAS. PER FBC TABLE 307.7(1), THE MAXIMUM ALLOWABLE
 QUANTITY THAT CAN BE STORED (OR IN USE PER FOOTNOTE B)
 IS 1500 CUBIC FEET. IF THIS AMOUNT IS EXCEEDED THEN THE
 OCCUPANCY IS REQUIRED TO BE CONSIDERED H-3. FOOTNOTES D
 AND E TO THE TABLE EACH ALLOW THE QUANTITIES TO BE
 INCREASED 100 PERCENT. THE INCREASE FOR BOTH ARE
 APPLIED ACCUMULATIVELY. SEE FBC 307.1 AND TABLE
 307.7(1)
  
 6) THE SITE PLAN SHOWS THAT THE 1 STORY BUILDING IS
 3.2O' TO THE WEST OF THE NEW BUILDING. FBC 704.3
 ADDRESSES BUILDINGS ON THE SAME LOT WITH AN IMAGINARY
 LINE BETWEEN THEM. SEE FBC 702.1 FOR DEFINITION OF FIRE
 SEPARATION DISTANCE. NOTE THAT THE FIRE SEPARATION
 DISTANCE IS NOT THE DISTANCE FROM BUILDING TO BUILDING,
 BUT TO AN IMAGINARY LINE BETWEEN THEM SUCH THAT EACH
 BUILDING COMPLIES WITH TABLE 602 AND TABLE 704.8. TABLE
 602 REQUIRES GROUP H TYPE V-B WITH LESS THAN 5 FEET
 FIRE SEPARATION DISTANCE TO HAVE 3 HOUR FIRE RATED
 WALLS. USING THE EXCEPTION TO 704.3 ALLOWS THE
 BUILDINGS TO BE CONSIDERED AS PORTIONS OF ONE BUILDING
 IF THE AGGREGATE AREA OF THE BUILDINGS IS WITHIN THE
 LIMITS SPECIFIED FOR ONE BUILDING. UNDER 302.3.2
 SEPARATED USES THE NEW H-3 OCCUPANCY WOULD BE REQUIRED
 TO BE SEPARATED FROM THE EXISTING F-1 OCCUPANCY WITH
 ONE HOUR FIRE RATED WALLS. PREVIOUS COMMENTS #9,
 #10,#11 AND #12.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-02 Cont ID  
Sent By rmcdouga Date 2008-07-02 Time 14:00 Rev Time 0.00
Received By rmcdouga Date 2008-07-02 Time 06:47 Sent To FIRE
Notes
2008-07-02 13:59:462004 FBC W/2007 REVISIONS
 INSTALL FIBERGLASS STRUCTURE
  
 DENIED BY BUILDING
  
 1) THE ENGINEER FOR SHELTER WORKS IS USING AN EMBOSSED
 SEAL THAT IS NO LONGER ACCEPTABLE AS OF JANUARY 1,
 2006. SEE FAC 61G15-23.001 AND F.S.471.025.
  
 2) ENGINEER IS REQUIRED TO LEGIBLY INDICATE THEIR NAME,
 ADDRESS AND LICENSE NUMBER ON EACH SHEET. SEE FAC
 61G15-23.002.
  
 3) THE WRONG CODES ARE SPECIFIED ON THE PLANS AND
 CALCULATIONS. THE CODE CURRENTLY IN EFFECT IS THE 2004
 FBC W/2007 REVISIONS.
  
 4) THE CALCULATIONS REFERENCE THE WRONG EDITIONS OF
 FBC, ASCE7 AND ACI 318. THE 2004 FBC REFERENCES
 ASCE7-02 AND ACI 318-02. PLEASE REVISE.
  
 5) GENERAL NOTE #2 ON SHEET 1 OF PLANS SPECIFIES THAT A
 MINIMUM SEPARATION DISTANCE OF 10 FEET IS REQUIRED FROM
 THE NEAREST BUILDING. THE SITE PLAN DOES NOT COMPLY.
  
 6) SPECIFY THE SIZE AND LENGTH/EMBED DEPTH OF THE
 EXPANSION ANCHORS @ 6" OC ON SHEET 4 OF THE PLANS. THE
 CALCULATIONS SPECIFY 3/8" DIAMETER ANCHOR BOLTS WITH
 1-1/2" EMBEDMENT SPACED 12" OC. SEE CALCULATION SHEET 7
 OF 13.
  
 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOOR AS REQUIRED BY DCA RULE 9B-72.
  
 8) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9) FBC TABLE 602 REQUIRES TWO HOUR FIRE RATED WALLS FOR
 A BUILDING OF TYPE V-B CONSTRUCTION AND F-1 OCCUPANCY
 AND A FIRE SEPARATION DISTANCE OF LESS THAN 5' . NOTE:
 SEE 702.1 DEFINITIONS. FIRE SEPARATION DISTANCE. THE
 DISTANCE MEASURED FROM THE BUILDING FACE TO THE CLOSEST
 INTERIOR LOT LINE, TO THE CENTERLINE OF A STREET, ALLEY
 OR PUBLIC WAY, OR TO AN IMAGINARY LINE BETWEEN TWO
 BUILDINGS ON THE LOT. THE DISTANCE SHALL BE MEASURED AT
 RIGHT ANGLES FROM THE FACE OF THE WALL.
  
 10) SPECIFY THE OCCUPANCY, CONSTRUCTION TYPE AND AREA
 OF WALL OPENINGS FOR THE ADJACENT BUILDING IN ORDER TO
 DETERMINE COMPLIANCE WITH FIRE SEPARATION REQUIREMENTS.
 FBC 702.
  
 11) THE MAXIMUM AREA OF WALL OPENINGS IN BOTH BUILDINGS
 IS REQUIRED TO COMPLY WITH FBC TABLE 704.8. NO OPENINGS
 ARE PERMITTED FOR A FIRE SEPARATION DISTANCE OF 0-3
 FEET.
  
 12) FBC 503.1.3 PERMITS TWO BUILDINGS ON THE SAME LOT
 TO BE CONSIDERED AS PORTIONS OF ONE BUILDING IF CERTAIN
 CONDITIONS ARE MET. SEE FBC 503.1.3 BUILDINGS ON SAME
 LOT.
 TWO OR MORE BUILDINGS ON THE SAME LOT SHALL BE
 REGULATED AS SEPARATE BUILDINGS OR SHALL BE CONSIDERED
 AS PORTIONS OF ONE BUILDING IF THE HEIGHT OF EACH
 BUILDING AND THE AGGREGATE AREA OF BUILDINGS ARE WITHIN
 THE LIMITATIONS OF TABLE 503 AS MODIFIED BY SECTIONS
 504 AND 506 . THE PROVISIONS OF THIS CODE APPLICABLE TO
 THE AGGREGATE BUILDING SHALL BE APPLICABLE TO EACH
 BUILDING. IF YOU CHOOSE TO DO THIS SHOW HOW THE TWO
 BUILDINGS WILL COMPLY.
  
 13) SPECIFY THE TYPE (LIQUID OR GAS) AND AMOUNT OF
 CHLORINE THAT WILL BE STORED IN THE BUILDING. SUBMIT
 MATERIAL SAFETY DATA SHEETS FOR THE PRODUCT.THIS
 INFORMATION TO BE USED TO DETERMINE IF THE OCCUPANCY
 WILL BE DETERMINED AS HIGH HAZARD GROUP H. SEE FBC
 307.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-01-08 Cont ID  
Sent By btrobaug Date 2009-01-08 Time 09:49 Rev Time 0.00
Received By btrobaug Date 2009-01-08 Time 09:38 Sent To B
Notes
2009-01-08 09:50:07TO LUIS./WRT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-12-02 Cont ID  
Sent By btrobaug Date 2008-12-02 Time 10:06 Rev Time 0.00
Received By btrobaug Date 2008-12-02 Time 09:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-15 Cont ID  
Sent By btrobaug Date 2008-10-15 Time 08:11 Rev Time 0.00
Received By btrobaug Date 2008-10-14 Time 16:22 Sent To  
Notes
2008-10-14 16:56:44 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} INDICATE HOW THE BUILDING IS BEING FED AND FROM
 WHERE. FEEDER SIZES AND OCP ARE REQUIRED FOR
 REVIEW.215.5 NEC*** A RISER DIAGRAM IS REQUIRED PER
 THIS ARTICLE TO COMPLY WITH THIS COMMENT..
  
 2} 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S)
 OR BRANCH CIRCUIT(S)
 (A) GROUNDING ELECTRODE BUILDING(S) OR STRUCTURE(S)
 SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A
 GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM
 INSTALLED IN ACCORDANCE WITH 250.50. THE GROUNDING
 ELECTRODE CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE
 WITH 250.32(B) OR (C). WHERE THERE IS NO EXISTING
 GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S)
 REQUIRED IN 250.50 SHALL BE INSTALLED.*** THIS COMMENT
 CAN ALSO BE RESPONDED TO WITH A RISER DIAGRAM, BUT
 CANNOT BE A RESPONSE ON THE COMMENT SHEET (WHICH IS NOT
 PRINTED OUT CORRECTLY, SEE COMMENT #2 ON THE RES SHEET
 AND COMMENT #2 ON THE ORIGINAL COMMENT SHEET) THE RISER
 DIAGRAM MUST BE DRAWN AND SUBMITTED AS PART OF THE
 CONSTRUCTION DOCUMENTS. THE ELECTRICAL CONTRACTOR MAY
 DRAW THESE UNDER THE EXEMPTIONS OF FS 471..
  
 3} NEW COMMENT THAT WAS NOT MADE IN THE PREVIOUS
 REVIEW.***THE ENGINEER WHOSE NAME APPEARS ON THE TITLE
 BLOCK MUST SIGN, DATE AND SEAL THE DOCUMENT.
 61G15-23.002 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-16 Cont ID  
Sent By btrobaug Date 2008-06-16 Time 11:58 Rev Time 0.00
Received By btrobaug Date 2008-06-16 Time 11:51 Sent To  
Notes
2008-06-16 11:58:40 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} INDICATE HOW THE BIULDING IS BEING FED AND FROM
 WHERE.FEEDER SIIZES AND OCP ARE REQUIRED FOR
 REVIEW.215.5 NEC.
  
 2} 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S)
 OR BRANCH CIRCUIT(S)
 (A) GROUNDING ELECTRODE BUILDING(S) OR STRUCTURE(S)
 SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A
 GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM
 INSTALLED IN ACCORDANCE WITH 250.50. THE GROUNDING
 ELECTRODE CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE
 WITH 250.32(B) OR (C). WHERE THERE IS NO EXISTING
 GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S)
 REQUIRED IN 250.50 SHALL BE INSTALLED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-01-08 Cont ID  
Sent By mwennerg Date 2009-01-08 Time 15:14 Rev Time 0.00
Received By mwennerg Date 2009-01-08 Time 15:14 Sent To  
Notes
2009-01-08 15:16:06SENT TO LUIS M.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-12-08 Cont ID  
Sent By mawillia Date 2008-12-08 Time 14:50 Rev Time 0.00
Received By mawillia Date 2008-12-08 Time 14:35 Sent To  
Notes
2008-12-08 14:47:46*****APPROVED*****
  
  
 SITE PLAN 1/1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-10-16 Cont ID  
Sent By mawillia Date 2008-10-16 Time 11:58 Rev Time 0.00
Received By mawillia Date 2008-10-16 Time 11:43 Sent To  
Notes
2008-10-16 11:57:49*****DENIED*****
  
  
 COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW OF
 07/22/2008 STILL NEED TO BE ADDRESSED. A COPY OF THOSE
 COMMENTS HAVE BEEN ATTECHED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-22 Cont ID  
Sent By mwennerg Date 2008-07-22 Time 16:02 Rev Time 0.00
Received By mwennerg Date 2008-07-22 Time 16:02 Sent To  
Notes
2008-07-22 16:13:51***DENIED***
  
 1) PLEASE ADD LIFE SAFETY TO COMPLY WITH NFPA 101, 2003
 EDITION TO CODE SUMMARY.
  
 2) FLORIDA FIRE PREVENTION CODE 2004 EDITION SHALL BE
 REFERENCED.
  
 3) IDENTIFY THE TYPE AND AMOUNT OF ALL
 PRODUCTS/MATERIAL THAT WILL BE STORED IN THE
 STRUCTURE.
  
 4) PROVIDE MSDS (MATERIAL SAFETY DATA SHEETS)
 INFORMATION ON ALL PRODUCTS BEING STORED.
  
 5) PLACARDING REQUIRED THAT MEETS THE STANDARDS FOR
 NFPA 704. OTHER APPLICABLE SIGNAGE MAY BE REQUIRED.
  
 6) PLEASE EXPLAIN WHAT FIRE PREVENTION MEASURES WILL BE
 TAKEN SHOULD AN EMERGENCY OR SPILL OCCUR.
  
 7) WILL THERE BE ANY TYPE OF FIRE EXTINGUISHMENT
 EQUIPMENT PROVIDED?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-12-19 Cont ID  
Sent By adarroug Date 2008-12-19 Time 16:24 Rev Time 0.00
Received By adarroug Date 2008-12-19 Time 16:24 Sent To B
Notes
2008-12-19 16:24:42TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-11-21 Cont ID  
Sent By adarroug Date 2008-11-21 Time 16:28 Rev Time 0.00
Received By adarroug Date 2008-11-21 Time 16:28 Sent To  
Notes
2008-11-21 16:31:50TO "COMM" BD#21--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-29 Cont ID  
Sent By adarroug Date 2008-09-29 Time 11:53 Rev Time 0.00
Received By adarroug Date 2008-09-29 Time 11:53 Sent To  
Notes
2008-09-29 11:56:25TO "COMM" BD#16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 12:20 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 12:20 Sent To B
Notes
2008-06-16 12:21:12TO "MISC" BOX#3--DOES NOT NEED A FIRE REVIEW, PER
 "LMARTINEZ"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-22 Cont ID  
Sent By mwennerg Date 2008-07-22 Time 16:14 Rev Time 0.00
Received By mwennerg Date 2008-06-12 Time 16:46 Sent To  
Notes
2008-06-12 16:46:37TO "Z" BOX

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-01-09 Cont ID  
Sent By kstevens Date 2009-01-09 Time 10:06 Rev Time 0.00
Received By kstevens Date 2009-01-09 Time 10:06 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-12-03 Cont ID  
Sent By kstevens Date 2008-12-03 Time 15:26 Rev Time 0.00
Received By kstevens Date 2008-12-03 Time 15:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-10-06 Cont ID  
Sent By kstevens Date 2008-10-06 Time 11:58 Rev Time 0.00
Received By kstevens Date 2008-10-06 Time 11:58 Sent To  
Notes
2008-10-06 13:42:03DENIED
 REFERENCE: FBC-2004 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****NEW COMMENTS TO ADDRESS NEW CONDITIONS &
 INFORMATION:
  
 1. THE SEAL OF THE PROFESSIONAL ENGINEER SHALL BE AN
 EMBOSSED TYPE SEAL PER FAC 61G15-23.001 & FS 471.025.
  
 2. NEW INFORMATION RECIEVED IN THE FORM OF MSDS SHEETS
 FOR THE CLORINE INDICATE THE REQUIREMENTS FOR AN EYE
 WASH AND AN EMERGENCY SHOWER. PLEASE SHOW THE LOCATION
 OF THE REQUIRED FIXTURE/FIXTURES. TABLE 403.1 & SECTION
 411. SUBMIT A WATER RISER DIAGRAM SHOWING CONNECTION TO
 WATER SOURCE, VALVES, PIPE SIZE ETC. PER SECTION
 11-6.3.5.1.3(3)(8)(13).
  
 3. THE MSDS SHEETS INDICATE THAT LUKEWARM WATER IS
 REQUIRED TO BE FLUSHED OVER THE SKIN OR EYES FOR A
 MINIMUM OF 20 MINUTES. AS SUCH A WATER HEATER AND A
 MIXING VALVE IS REQUIRED. SECTION 501.8.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-11 Cont ID  
Sent By mperson Date 2008-07-11 Time 11:43 Rev Time 0.00
Received By mperson Date 2008-07-11 Time 11:43 Sent To  
Notes
2008-07-11 12:01:03PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 1 INDICATES A 4 INCH (4") FLOOR DRAIN. THE
 FOLLOWING IS REQUIRED FOR THE 4" FLOOR DRAIN PER
 (W.P.B. AS AMENDED) CHAPTER 1, SECTION 106.3.5.1.3
 COMMERCIAL PLUMBING (4)(6)(13), PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS OF THE FLOOR DRAIN.
 NOTE: WHERE A TRAP SEAL IS SUBJECT TO LOSS BY
 EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. A TRAP SEAL PRIMER VALVE SHALL CONFORM TO
 ASSA 1018 OR ASSE 1044. CLEARLY INDICATE THE TRAP SEAL
 PRIMER VALVE ON THE RESUBMITTED PLANS. PER FBC-
 PLUMBING SECTION 1002.4 TRAP SEALS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 4 Status N Date 2008-12-16 Cont ID  
Sent By kdfreema Date 2008-12-16 Time 15:36 Rev Time 0.00
Received By kdfreema Date 2008-12-16 Time 15:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-11-24 Cont ID  
Sent By kdfreema Date 2008-11-24 Time 14:49 Rev Time 0.00
Received By kdfreema Date 2008-11-24 Time 14:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-10-01 Cont ID  
Sent By kdfreema Date 2008-10-01 Time 16:43 Rev Time 0.00
Received By kdfreema Date 2008-10-01 Time 16:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-13 Cont ID  
Sent By choops Date 2008-06-13 Time 14:24 Rev Time 0.00
Received By choops Date 2008-06-13 Time 14:24 Sent To E
Notes
2008-06-13 14:25:30***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM THE PROPOSED
 BUILDING TO ALL ADJACENT PROPERTY LINES.
  
 NOTE:MINIMUM SETBACKS.
 A.FRONT: 25 FEET;
 B.CORNER SIDE: 12.5 FEET;
 C.REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH,
 WHICHEVER IS LESS;
 D.SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  