| Plan Review Stops For Permit 08060313 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2009-01-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-01-07 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-01-07 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2009-01-07 14:02:06 | BUILDING PROVISO | | | SUBMIT INSTALLATION / ANCHORING INSTRUCTIONS FOR THE | | | EXHAUST FAN. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2009-01-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-01-02 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-01-02 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2009-01-02 16:59:19 | 2004 FBC W/2007 REVISIONS | | | CHLORINE STORAGE BUILDING | | | | | | DENIED BY BUILDING | | | | | | 1) PLEASE SPECIFY THE TYPE OF CONSTRUCTION , OCCUPANCY | | | AND SQUARE FOOTAGE OF THE EXISTING STRUCTURE ON THE | | | PLANS. FBC 602 AND 302.1 | | | | | | 2) SPECIFY THE TYPE AND AMOUNT OF CHLORINE THAT WILL IN | | | USE AND STORAGE WITHIN THE BUILDING. FBC SECTION 307.9 | | | CONTAINS EXCEPTIONS WHICH ALLOW STRUCTURES THAT DO NOT | | | CONTAIN MORE THAN THE MAXIMUM ALLOWABLE QUANTITIES PER | | | CONTROL AREA OF HAZARDOUS MATERIALS AS SHOWN IN TABLES | | | 307.7(1) AND (2) TO NOT BE CLASSIFIED AS GROUP H, BUT | | | TO BE CLASSIFIED AS THE OCCUPANCY THEY MOST NEARLY | | | RESEMBLE. BECAUSE THIS BUILDING DOES NOT MEET THE 50 | | | FOOT DISTANCE TO LOT LINES THAT IS REQUIRED FOR AN H-3 | | | OCCUPANCY BY FBC 415.3.1, CONTROL AREAS WILL BE | | | REQUIRED. NOTE: TABLE 307.7(2) ALLOWS 810 CUBIC FEET OF | | | GAS AGGREGATE QUANTITY IN USE AND STORAGE. THE QUANTITY | | | CAN BE INCREASED 100 PER CENT WHEN STORED IN APPROVED | | | STORAGE CABINETS, GAS CABINETS OR EXHAUSTED ENCLOSURES | | | SEE FOOTNOTE F FOR TABLE 307.7(2). | | | | | | 3) SPECIFY THE REQUIRED FIRE RATING OF THE WALLS AND | | | CEILING OF THE CHLORINE ROOM (SEE FBC 414.2 CONTROL | | | AREA). FBC 414.2.1 REQUIRES ONE HOUR FIRE RATED WALLS | | | AND CEILING. | | | | | | 4) INDICATE THE LOCATIONS AND AMOUNT OF CHLORINE THAT | | | WILL BE STORED IN EACH CONTROL AREA. FBC 414.1.3 AND | | | TABLE 414.2.2 | | | | | | 5) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE | | | EXTERIOR EXHAUST VENT. FAC RULE 9B-72 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-12-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-12-03 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-12-03 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2008-12-03 14:10:25 | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | | EXTERIOR DOOR, WALL LOUVERS, WALL PANELS, ETC. AS | | | REQUIRED BY DCA RULE 9B-72. | | | | | | **THIS ITEM CAN BE ADDRESSED BY SUBMITTING LOCAL OR | | | SITE SPECIFIC PRODUCT APPROVALS. | | | | | | 2) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | PREVIOUS COMMENT #8 | | | | | | **HAVE THE DESIGNER OF RECORD REVIEW AND APPROVE THE | | | PRODUCT APPROVALS IN WRITING. | | | | | | 3) THE RESPONSE TO COMMENT #13 INDICATES THAT (4) 150 | | | POUND CYLINDERS OF CHLORINE GAS WILL BE HOUSED IN THIS | | | BUILDING. EACH 150 POUND CYLINDER CONTAINS 810 CUBIC | | | FEET OF CHLORINE GAS. THEREFORE, THERE WILL BE 3240 | | | CUBIC FEET OF GAS STORED IN THE BUILDING. THE MATERIAL | | | SAFETY DATA SHEET CLASSIFIES CHLORINE AS AN OXIDIZING | | | GAS. PER FBC TABLE 307.7(1), THE MAXIMUM ALLOWABLE | | | QUANTITY THAT CAN BE STORED (OR IN USE PER FOOTNOTE B) | | | IS 1500 CUBIC FEET. IF THIS AMOUNT IS EXCEEDED THEN THE | | | OCCUPANCY IS REQUIRED TO BE CONSIDERED H-3. FOOTNOTES D | | | AND E TO THE TABLE EACH ALLOW THE QUANTITIES TO BE | | | INCREASED 100 PERCENT. THE INCREASE FOR BOTH ARE | | | APPLIED ACCUMULATIVELY. SEE FBC 307.1 AND TABLE | | | 307.7(1) | | | | | | **THE PROPOSED SAFETY FEATURE DOES NOT ADDRESS THIS | | | COMMENT. IT WILL CLOSE THE VALVE BUT DOES NOT CONTAIN | | | OR PROTECT THE CYLINDERS. | | | | | | 4) THE SITE PLAN SHOWS THAT THE 1 STORY BUILDING IS | | | 3.20' TO THE WEST OF THE NEW BUILDING. FBC 704.3 | | | ADDRESSES BUILDINGS ON THE SAME LOT WITH AN IMAGINARY | | | LINE BETWEEN THEM. SEE FBC 702.1 FOR DEFINITION OF FIRE | | | SEPARATION DISTANCE. NOTE THAT THE FIRE SEPARATION | | | DISTANCE IS NOT THE DISTANCE FROM BUILDING TO BUILDING, | | | BUT TO AN IMAGINARY LINE BETWEEN THEM SUCH THAT EACH | | | BUILDING COMPLIES WITH TABLE 602 AND TABLE 704.8. TABLE | | | 602 REQUIRES GROUP H TYPE V-B WITH LESS THAN 5 FEET | | | FIRE SEPARATION DISTANCE TO HAVE 3 HOUR FIRE RATED | | | WALLS. USING THE EXCEPTION TO 704.3 ALLOWS THE | | | BUILDINGS TO BE CONSIDERED AS PORTIONS OF ONE BUILDING | | | IF THE AGGREGATE AREA OF THE BUILDINGS IS WITHIN THE | | | LIMITS SPECIFIED FOR ONE BUILDING. UNDER 302.3.2 | | | SEPARATED USES THE NEW H-3 OCCUPANCY WOULD BE REQUIRED | | | TO BE SEPARATED FROM THE EXISTING F-1 OCCUPANCY WITH | | | ONE HOUR FIRE RATED WALLS. PREVIOUS COMMENTS #9, | | | #10,#11 AND #12. | | | | | | **THE PROPOSED SAFETY FEATURE DOES NOT ADDRESS THIS | | | COMMENT. H-3 OCCUPANCY SEPARATION SHALL COMPLY WITH FBC | | | TABLE 602 AND 415.3.1 FOR DISTANCE TO LOT LINES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-10-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-10-15 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-10-15 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2008-10-15 13:38:37 | 2004 FBC W/2007 REVISIONS | | | INSTALL FIBERGLASS STRUCTURE | | | | | | DENIED BY BUILDING | | | | | | 1) THE ENGINEER FOR SHELTER WORKS IS REQUIRED TO USE AN | | | EMBOSSING IMPRESSION SEAL AS SPECIFIED IN FLORIDA | | | ADMINISTRATIVE CODE 61G15-23.001 UNDER THE AUTHORITY OF | | | FLORIDA STATUTE 471.025. SEE PREVIOUS COMMENT #1. | | | | | | 2) IF THE 10 FOOT SEPARATION IS NOT REQUIRED, THEN | | | REMOVE GENERAL NOTE #2 FROM THE THIRD PAGE OF THE | | | SHELTER ENGINEERING. PREVIOUS COMMENT #5. | | | | | | 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | | EXTERIOR DOOR, WALL LOUVERS, WALL PANELS, ETC. AS | | | REQUIRED BY DCA RULE 9B-72. | | | | | | 4) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | PREVIOUS COMMENT #8 | | | | | | 5) THE RESPONSE TO COMMENT #13 INDICATES THAT (4) 150 | | | POUND CYLINDERS OF CHLORINE GAS WILL BE HOUSED IN THIS | | | BUILDING. EACH 150 POUND CYLINDER CONTAINS 810 CUBIC | | | FEET OF CHLORINE GAS. THEREFORE, THERE WILL BE 3240 | | | CUBIC FEET OF GAS STORED IN THE BUILDING. THE MATERIAL | | | SAFETY DATA SHEET CLASSIFIES CHLORINE AS AN OXIDIZING | | | GAS. PER FBC TABLE 307.7(1), THE MAXIMUM ALLOWABLE | | | QUANTITY THAT CAN BE STORED (OR IN USE PER FOOTNOTE B) | | | IS 1500 CUBIC FEET. IF THIS AMOUNT IS EXCEEDED THEN THE | | | OCCUPANCY IS REQUIRED TO BE CONSIDERED H-3. FOOTNOTES D | | | AND E TO THE TABLE EACH ALLOW THE QUANTITIES TO BE | | | INCREASED 100 PERCENT. THE INCREASE FOR BOTH ARE | | | APPLIED ACCUMULATIVELY. SEE FBC 307.1 AND TABLE | | | 307.7(1) | | | | | | 6) THE SITE PLAN SHOWS THAT THE 1 STORY BUILDING IS | | | 3.2O' TO THE WEST OF THE NEW BUILDING. FBC 704.3 | | | ADDRESSES BUILDINGS ON THE SAME LOT WITH AN IMAGINARY | | | LINE BETWEEN THEM. SEE FBC 702.1 FOR DEFINITION OF FIRE | | | SEPARATION DISTANCE. NOTE THAT THE FIRE SEPARATION | | | DISTANCE IS NOT THE DISTANCE FROM BUILDING TO BUILDING, | | | BUT TO AN IMAGINARY LINE BETWEEN THEM SUCH THAT EACH | | | BUILDING COMPLIES WITH TABLE 602 AND TABLE 704.8. TABLE | | | 602 REQUIRES GROUP H TYPE V-B WITH LESS THAN 5 FEET | | | FIRE SEPARATION DISTANCE TO HAVE 3 HOUR FIRE RATED | | | WALLS. USING THE EXCEPTION TO 704.3 ALLOWS THE | | | BUILDINGS TO BE CONSIDERED AS PORTIONS OF ONE BUILDING | | | IF THE AGGREGATE AREA OF THE BUILDINGS IS WITHIN THE | | | LIMITS SPECIFIED FOR ONE BUILDING. UNDER 302.3.2 | | | SEPARATED USES THE NEW H-3 OCCUPANCY WOULD BE REQUIRED | | | TO BE SEPARATED FROM THE EXISTING F-1 OCCUPANCY WITH | | | ONE HOUR FIRE RATED WALLS. PREVIOUS COMMENTS #9, | | | #10,#11 AND #12. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-07-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-07-02 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-07-02 |
Time |
06:47 |
Sent To |
FIRE |
|
| Notes |
| 2008-07-02 13:59:46 | 2004 FBC W/2007 REVISIONS | | | INSTALL FIBERGLASS STRUCTURE | | | | | | DENIED BY BUILDING | | | | | | 1) THE ENGINEER FOR SHELTER WORKS IS USING AN EMBOSSED | | | SEAL THAT IS NO LONGER ACCEPTABLE AS OF JANUARY 1, | | | 2006. SEE FAC 61G15-23.001 AND F.S.471.025. | | | | | | 2) ENGINEER IS REQUIRED TO LEGIBLY INDICATE THEIR NAME, | | | ADDRESS AND LICENSE NUMBER ON EACH SHEET. SEE FAC | | | 61G15-23.002. | | | | | | 3) THE WRONG CODES ARE SPECIFIED ON THE PLANS AND | | | CALCULATIONS. THE CODE CURRENTLY IN EFFECT IS THE 2004 | | | FBC W/2007 REVISIONS. | | | | | | 4) THE CALCULATIONS REFERENCE THE WRONG EDITIONS OF | | | FBC, ASCE7 AND ACI 318. THE 2004 FBC REFERENCES | | | ASCE7-02 AND ACI 318-02. PLEASE REVISE. | | | | | | 5) GENERAL NOTE #2 ON SHEET 1 OF PLANS SPECIFIES THAT A | | | MINIMUM SEPARATION DISTANCE OF 10 FEET IS REQUIRED FROM | | | THE NEAREST BUILDING. THE SITE PLAN DOES NOT COMPLY. | | | | | | 6) SPECIFY THE SIZE AND LENGTH/EMBED DEPTH OF THE | | | EXPANSION ANCHORS @ 6" OC ON SHEET 4 OF THE PLANS. THE | | | CALCULATIONS SPECIFY 3/8" DIAMETER ANCHOR BOLTS WITH | | | 1-1/2" EMBEDMENT SPACED 12" OC. SEE CALCULATION SHEET 7 | | | OF 13. | | | | | | 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | | EXTERIOR DOOR AS REQUIRED BY DCA RULE 9B-72. | | | | | | 8) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 9) FBC TABLE 602 REQUIRES TWO HOUR FIRE RATED WALLS FOR | | | A BUILDING OF TYPE V-B CONSTRUCTION AND F-1 OCCUPANCY | | | AND A FIRE SEPARATION DISTANCE OF LESS THAN 5' . NOTE: | | | SEE 702.1 DEFINITIONS. FIRE SEPARATION DISTANCE. THE | | | DISTANCE MEASURED FROM THE BUILDING FACE TO THE CLOSEST | | | INTERIOR LOT LINE, TO THE CENTERLINE OF A STREET, ALLEY | | | OR PUBLIC WAY, OR TO AN IMAGINARY LINE BETWEEN TWO | | | BUILDINGS ON THE LOT. THE DISTANCE SHALL BE MEASURED AT | | | RIGHT ANGLES FROM THE FACE OF THE WALL. | | | | | | 10) SPECIFY THE OCCUPANCY, CONSTRUCTION TYPE AND AREA | | | OF WALL OPENINGS FOR THE ADJACENT BUILDING IN ORDER TO | | | DETERMINE COMPLIANCE WITH FIRE SEPARATION REQUIREMENTS. | | | FBC 702. | | | | | | 11) THE MAXIMUM AREA OF WALL OPENINGS IN BOTH BUILDINGS | | | IS REQUIRED TO COMPLY WITH FBC TABLE 704.8. NO OPENINGS | | | ARE PERMITTED FOR A FIRE SEPARATION DISTANCE OF 0-3 | | | FEET. | | | | | | 12) FBC 503.1.3 PERMITS TWO BUILDINGS ON THE SAME LOT | | | TO BE CONSIDERED AS PORTIONS OF ONE BUILDING IF CERTAIN | | | CONDITIONS ARE MET. SEE FBC 503.1.3 BUILDINGS ON SAME | | | LOT. | | | TWO OR MORE BUILDINGS ON THE SAME LOT SHALL BE | | | REGULATED AS SEPARATE BUILDINGS OR SHALL BE CONSIDERED | | | AS PORTIONS OF ONE BUILDING IF THE HEIGHT OF EACH | | | BUILDING AND THE AGGREGATE AREA OF BUILDINGS ARE WITHIN | | | THE LIMITATIONS OF TABLE 503 AS MODIFIED BY SECTIONS | | | 504 AND 506 . THE PROVISIONS OF THIS CODE APPLICABLE TO | | | THE AGGREGATE BUILDING SHALL BE APPLICABLE TO EACH | | | BUILDING. IF YOU CHOOSE TO DO THIS SHOW HOW THE TWO | | | BUILDINGS WILL COMPLY. | | | | | | 13) SPECIFY THE TYPE (LIQUID OR GAS) AND AMOUNT OF | | | CHLORINE THAT WILL BE STORED IN THE BUILDING. SUBMIT | | | MATERIAL SAFETY DATA SHEETS FOR THE PRODUCT.THIS | | | INFORMATION TO BE USED TO DETERMINE IF THE OCCUPANCY | | | WILL BE DETERMINED AS HIGH HAZARD GROUP H. SEE FBC | | | 307. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2009-01-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-01-08 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-01-08 |
Time |
09:38 |
Sent To |
B |
|
| Notes |
| 2009-01-08 09:50:07 | TO LUIS./WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-12-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-12-02 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-12-02 |
Time |
09:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-10-15 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-10-15 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-10-14 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2008-10-14 16:56:44 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS | | | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | | | | 1} INDICATE HOW THE BUILDING IS BEING FED AND FROM | | | WHERE. FEEDER SIZES AND OCP ARE REQUIRED FOR | | | REVIEW.215.5 NEC*** A RISER DIAGRAM IS REQUIRED PER | | | THIS ARTICLE TO COMPLY WITH THIS COMMENT.. | | | | | | 2} 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) | | | OR BRANCH CIRCUIT(S) | | | (A) GROUNDING ELECTRODE BUILDING(S) OR STRUCTURE(S) | | | SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A | | | GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM | | | INSTALLED IN ACCORDANCE WITH 250.50. THE GROUNDING | | | ELECTRODE CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE | | | WITH 250.32(B) OR (C). WHERE THERE IS NO EXISTING | | | GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S) | | | REQUIRED IN 250.50 SHALL BE INSTALLED.*** THIS COMMENT | | | CAN ALSO BE RESPONDED TO WITH A RISER DIAGRAM, BUT | | | CANNOT BE A RESPONSE ON THE COMMENT SHEET (WHICH IS NOT | | | PRINTED OUT CORRECTLY, SEE COMMENT #2 ON THE RES SHEET | | | AND COMMENT #2 ON THE ORIGINAL COMMENT SHEET) THE RISER | | | DIAGRAM MUST BE DRAWN AND SUBMITTED AS PART OF THE | | | CONSTRUCTION DOCUMENTS. THE ELECTRICAL CONTRACTOR MAY | | | DRAW THESE UNDER THE EXEMPTIONS OF FS 471.. | | | | | | 3} NEW COMMENT THAT WAS NOT MADE IN THE PREVIOUS | | | REVIEW.***THE ENGINEER WHOSE NAME APPEARS ON THE TITLE | | | BLOCK MUST SIGN, DATE AND SEAL THE DOCUMENT. | | | 61G15-23.002 FAC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-06-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-16 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-16 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2008-06-16 11:58:40 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS | | | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | | | | 1} INDICATE HOW THE BIULDING IS BEING FED AND FROM | | | WHERE.FEEDER SIIZES AND OCP ARE REQUIRED FOR | | | REVIEW.215.5 NEC. | | | | | | 2} 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) | | | OR BRANCH CIRCUIT(S) | | | (A) GROUNDING ELECTRODE BUILDING(S) OR STRUCTURE(S) | | | SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A | | | GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM | | | INSTALLED IN ACCORDANCE WITH 250.50. THE GROUNDING | | | ELECTRODE CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE | | | WITH 250.32(B) OR (C). WHERE THERE IS NO EXISTING | | | GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S) | | | REQUIRED IN 250.50 SHALL BE INSTALLED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2009-01-08 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2009-01-08 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2009-01-08 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2009-01-08 15:16:06 | SENT TO LUIS M. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-12-08 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-12-08 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-12-08 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2008-12-08 14:47:46 | *****APPROVED***** | | | | | | | | | SITE PLAN 1/1 STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-10-16 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-10-16 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-10-16 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2008-10-16 11:57:49 | *****DENIED***** | | | | | | | | | COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW OF | | | 07/22/2008 STILL NEED TO BE ADDRESSED. A COPY OF THOSE | | | COMMENTS HAVE BEEN ATTECHED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-07-22 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-07-22 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-07-22 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2008-07-22 16:13:51 | ***DENIED*** | | | | | | 1) PLEASE ADD LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 | | | EDITION TO CODE SUMMARY. | | | | | | 2) FLORIDA FIRE PREVENTION CODE 2004 EDITION SHALL BE | | | REFERENCED. | | | | | | 3) IDENTIFY THE TYPE AND AMOUNT OF ALL | | | PRODUCTS/MATERIAL THAT WILL BE STORED IN THE | | | STRUCTURE. | | | | | | 4) PROVIDE MSDS (MATERIAL SAFETY DATA SHEETS) | | | INFORMATION ON ALL PRODUCTS BEING STORED. | | | | | | 5) PLACARDING REQUIRED THAT MEETS THE STANDARDS FOR | | | NFPA 704. OTHER APPLICABLE SIGNAGE MAY BE REQUIRED. | | | | | | 6) PLEASE EXPLAIN WHAT FIRE PREVENTION MEASURES WILL BE | | | TAKEN SHOULD AN EMERGENCY OR SPILL OCCUR. | | | | | | 7) WILL THERE BE ANY TYPE OF FIRE EXTINGUISHMENT | | | EQUIPMENT PROVIDED? | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-12-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-19 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-19 |
Time |
16:24 |
Sent To |
B |
|
| Notes |
| 2008-12-19 16:24:42 | TO "RMCDOUGAL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-11-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-21 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-21 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2008-11-21 16:31:50 | TO "COMM" BD#21--EXPEDITED-- |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-09-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-29 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-29 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2008-09-29 11:56:25 | TO "COMM" BD#16 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-06-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-16 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-16 |
Time |
12:20 |
Sent To |
B |
|
| Notes |
| 2008-06-16 12:21:12 | TO "MISC" BOX#3--DOES NOT NEED A FIRE REVIEW, PER | | | "LMARTINEZ" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-07-22 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-07-22 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-06-12 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2008-06-12 16:46:37 | TO "Z" BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2009-01-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-01-09 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-01-09 |
Time |
10:06 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-12-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-12-03 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-12-03 |
Time |
15:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-10-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-10-06 |
Time |
11:58 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-10-06 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2008-10-06 13:42:03 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****NEW COMMENTS TO ADDRESS NEW CONDITIONS & | | | INFORMATION: | | | | | | 1. THE SEAL OF THE PROFESSIONAL ENGINEER SHALL BE AN | | | EMBOSSED TYPE SEAL PER FAC 61G15-23.001 & FS 471.025. | | | | | | 2. NEW INFORMATION RECIEVED IN THE FORM OF MSDS SHEETS | | | FOR THE CLORINE INDICATE THE REQUIREMENTS FOR AN EYE | | | WASH AND AN EMERGENCY SHOWER. PLEASE SHOW THE LOCATION | | | OF THE REQUIRED FIXTURE/FIXTURES. TABLE 403.1 & SECTION | | | 411. SUBMIT A WATER RISER DIAGRAM SHOWING CONNECTION TO | | | WATER SOURCE, VALVES, PIPE SIZE ETC. PER SECTION | | | 11-6.3.5.1.3(3)(8)(13). | | | | | | 3. THE MSDS SHEETS INDICATE THAT LUKEWARM WATER IS | | | REQUIRED TO BE FLUSHED OVER THE SKIN OR EYES FOR A | | | MINIMUM OF 20 MINUTES. AS SUCH A WATER HEATER AND A | | | MIXING VALVE IS REQUIRED. SECTION 501.8. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-07-11 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-07-11 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-07-11 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2008-07-11 12:01:03 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. SHEET 1 INDICATES A 4 INCH (4") FLOOR DRAIN. THE | | | FOLLOWING IS REQUIRED FOR THE 4" FLOOR DRAIN PER | | | (W.P.B. AS AMENDED) CHAPTER 1, SECTION 106.3.5.1.3 | | | COMMERCIAL PLUMBING (4)(6)(13), PLEASE SUBMIT A | | | PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING | | | ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT | | | LOCATIONS OF THE FLOOR DRAIN. | | | NOTE: WHERE A TRAP SEAL IS SUBJECT TO LOSS BY | | | EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE | | | INSTALLED. A TRAP SEAL PRIMER VALVE SHALL CONFORM TO | | | ASSA 1018 OR ASSE 1044. CLEARLY INDICATE THE TRAP SEAL | | | PRIMER VALVE ON THE RESUBMITTED PLANS. PER FBC- | | | PLUMBING SECTION 1002.4 TRAP SEALS. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
N |
Date |
2008-12-16 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2008-12-16 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2008-12-16 |
Time |
15:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-11-24 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2008-11-24 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2008-11-24 |
Time |
14:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-10-01 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2008-10-01 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2008-10-01 |
Time |
16:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-06-13 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-06-13 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-06-13 |
Time |
14:24 |
Sent To |
E |
|
| Notes |
| 2008-06-13 14:25:30 | ***FAILED*** | | | | | | | | | 1)INDICATE SETBACK DIMENSIONS FROM THE PROPOSED | | | BUILDING TO ALL ADJACENT PROPERTY LINES. | | | | | | NOTE:MINIMUM SETBACKS. | | | A.FRONT: 25 FEET; | | | B.CORNER SIDE: 12.5 FEET; | | | C.REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, | | | WHICHEVER IS LESS; | | | D.SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 | | | |
|
|