| Plan Review Stops For Permit 08060210 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-08-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-08-11 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-08-11 |
Time |
13:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-06-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-06-30 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-06-30 |
Time |
14:17 |
Sent To |
ENG |
|
| Notes |
| 2008-06-30 15:25:42 | 2004 FBC W/2007 REVISIONS | | | GARAGE ADDITION | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | | BE REQUIRED. | | | | | | 2) ON SHEET 4.0 SPECIFY 8D RING SHANK NAILS FOR THE | | | ROOF SHEATHING FASTENING AS REQUIRED BY FBC R 803.2.1. | | | | | | 3) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | | | | 4) THE PRODUCT APPROVAL FOR THE HARDIPLANK SIDING | | | REQUIRES 5/8" PLYWOOD WALL SHEATHING AND 1/2" IS | | | SPECIFIED ON THE WALL SECTION ON 3.0. PLEASE REVISE. | | | DCA RULE 9B-72 | | | | | | 5) SPECIFY WHICH ONE OF THE ATTACHMENT METHODS LISTED | | | IN THE TABLES OF THE ROOF TILE PRODUCT APPROVAL WILL BE | | | USED TO INSTALL THEM. FBC R905.3.7 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-08-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-08-04 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-08-04 |
Time |
12:14 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2008-06-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-13 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-13 |
Time |
11:14 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2008-07-30 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-07-30 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-07-30 |
Time |
13:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2008-07-02 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-07-02 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-07-02 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2008-07-02 09:45:56 | FAILED FOR FOLLOWING REASONS: | | | | | | 1. PLEASE PROVIDE A DETAIL DRAWING SHOWING ALL THE | | | DIMENSIONS FOR DRIVEWAY, APPROACH, SIDEWALK ETC2 | | | COPIES. | | | | | | 2. YOU ARE PUTTING AN APPROACH, DRIVEWAY, SIDEWALK & | | | CUTTING A CURB IN CITY'S RIGHT OF WAY. THEREFORE, YOU | | | NEED CITY'S RIGHT OF WAY APPROVAL FROM WINDEL PALMER | | | 494-1040, 1000 45TH STREET, ENG DEPT.ONCE WE HAVE AN | | | APPROVAL FROM WINDEL PALMER, WE WILL REVIEW YOUR | | | DRAWINGS. | | | | | | 3. MUST MEET CITY'S STANDARDS FOR APPROACH, | | | SIDEWALK,DRIVEWAY ETC. A SHEET " TYPICAL PAVER | | | STONE/CONCRETE DRIVEWAY APPROACH DETAILS" ENCLOSED FOR | | | YOUR USE. | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-01-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-13 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-13 |
Time |
09:08 |
Sent To |
M |
|
| Notes |
| 2009-01-13 09:10:13 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-07-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-21 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-21 |
Time |
09:25 |
Sent To |
Z |
|
| Notes |
| 2008-07-21 09:25:54 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-07-02 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-07-02 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-06-09 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2008-06-09 11:32:51 | TO "SFR" "Z" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-01-24 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-01-24 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-01-24 |
Time |
10:09 |
Sent To |
PC |
|
| Notes |
| 2009-01-24 10:15:49 | 8 1/2 X11 DWG REVISING ORIGINAL PLANS TO SHOW DUCT | | | SIZES USED IN RELOCATION OF AHUS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2008-06-09 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-06-09 |
Time |
14:16 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-06-09 |
Time |
14:16 |
Sent To |
E |
|
| Notes |
| 2008-06-09 14:17:49 | RELOCATE 2 EXISTING AIR HANDLER UNITS & 2 CONDENSER | | | UNITS ONLY. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2008-06-18 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-06-18 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-06-18 |
Time |
16:35 |
Sent To |
B |
|
| Notes |
| 2008-06-18 16:36:18 | NOTE: NO PLUMBING WORK ON PLANS OR PERMIT APPLIED FOR. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-08-24 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-08-24 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-08-24 |
Time |
11:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-08-03 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2008-08-03 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2008-08-03 |
Time |
09:56 |
Sent To |
E |
|
| Notes |
| 2008-08-03 09:56:48 | ****ZONING FAILED*** | | | | | | | | | | | | ***REPEAT COMMENTS FROM 6/9/08*** | | | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | 2. DRIVEWAY\APPROACH EXTENSION REQUIRES A SEPARATE | | | PERMIT.PLEASE REMOVE FROM THE SCOPE OF WORK ON THESE | | | PLANS AND APPLY FOR SEPARATELY. | | | | | | NOTE:PURSUANT TO SECTION 94-482 OF THE ZLDRS: | | | REQUIRED OFF-STREET PARKING SPACES FOR LESS THAN FOUR | | | RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE | | | PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED | | | PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE | | | LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT | | | YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN | | | THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH, | | | NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION | | | 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO | | | PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE. | | | | | | | | | 3. WHEN SUBMITTING FOR A DRIVEWAY PERMIT, PLEASE | | | INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE SURFACES | | | (EXISTING AND PROPOSED) LOCATED WITHIN THE FRONT YARD | | | (FROM FRONT PROPERTY LINE TO THE FRONT BUILDING | | | FACADE).ADDITIONALLY, A RIGHT-OF-WAY PERMIT WILL NEED | | | TO BE ACQUIRED FROM THE CITY?S ENGINEERING DEPARTMENT | | | (561.494.1040), FOR THE PROPOSED APPROACH EXTENSION. | | | | | | ADDITIONALLY, A RIGHT-OF-WAY PERMIT WILL NEED TO BE | | | ACQUIRED FROM THE CITY?S ENGINEERING DEPARTMENT | | | (561.494.1040), FOR THE PROPOSED APPROACH EXTENSION. | | | | | | 4. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C | | | EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION | | | 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | | | | | 5. INDICATE OVERHAND DIMENSIONS OF THE PROPOSED | | | ADDITION.AS PER SECTION 94-305(B) OF THE ZLDRS: | | | OVERHANGS SHALL NOT PROJECT MORE THAN THREE (3) FEET | | | INTO A REQUIRED SETBACK. | | | | | | 6. INDICATE THE HEIGHT OF THE PROPOSED ADDITION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME AT:(561) 822-1444 OR (561) 805-6720 OR | | | [email protected] | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-06-09 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-06-09 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-06-09 |
Time |
13:04 |
Sent To |
E |
|
| Notes |
| 2008-06-09 13:11:27 | ***FAILED*** | | | | | | | | | 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | | INCLUDES THE PROPERTY'S LEGAL DESCRIPTION AND ADDRESS. | | | | | | 2)DRIVEWAY/APPROACH EXTENSION REQUIRE A SEPARATE | | | PERMIT.PLEASE REMOVE FROM THE SCOPE OF WORK ON THESE | | | PLANS AND APPLY FOR SEPARATELY. | | | | | | NOTE:PURSUANT TO SECTION 94-482 OF THE ZLDRS: | | | REQUIRED OFF-STREET PARKING SPACES FOR LESS THAN FOUR | | | RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE | | | PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED | | | PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE | | | LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT | | | YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN | | | THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH, | | | NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION | | | 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO | | | PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE. | | | | | | | | | WHEN SUBMITTING FOR DRIVEWAY PERMIT, PLEASE INDICATE | | | SQUARE FOOTAGE OF ALL IMPERMEABLE SURFACES (EXISTING | | | AND PROPOSED) LOCATED WITHIN THE FRONT YARD (FROM FRONT | | | PROPERTY LINE TO THE FRONT BUILDING FACADE). | | | ADDITIONALLY A RIGHT-OF-WAY PERMIT WILL NEED TO BE | | | ACQUIRED FROM THE CITY'S ENGINEERING DEPARTMENT | | | (561.494.1040), FOR THE PROPOSED APPROACH EXTENSION. | | | | | | 3)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C | | | EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION | | | 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | | | | | 4)INDICATE OVERHANG DIMENSIONS OF THE PROPOSED | | | ADDITION.AS PER SECTION 94-305(B) OF THE ZLDRS: | | | OVERHANGS SHALL NOT PROJECT MORE THAN 3 FEET INTO A | | | REQUIRED SETBACK. | | | | | | 5)INDICATE THE HEIGHT OF THE PROPOSED ADDITION. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 | | | | | | | | | | | | | | | SENT TO "E" - SF RACK |
|
|