| Plan Review Stops For Permit 08060201 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-08-08 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-08-08 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-08-08 |
Time |
13:32 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-07-08 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-07-08 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-07-08 |
Time |
06:01 |
Sent To |
PC |
|
| Notes |
| 2008-07-08 12:45:51 | 2ND REVIEW | | | 7-8-08 | | | BUILDING PLAN REVIEW | | | PERMIT: 08060201 | | | ADD: 3700 GEORGIA AVE #10 | | | CONT: PRINCIPLE CONSTRUCTION LLC | | | TEL: (561) 533-5252 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 2ND | | | ACTION: DENIED | | | | | | 1)OK | | | 2)OK | | | | | | 3)ADDITIONAL INFORMATION REQUIRED 106.1.2* SUBMIT AN | | | EXISTING FLOOR PLAN AND A PROPOSED FLOOR PLAN SHOWING | | | ALL CHANGES TO THE EXISTING LAYOUT. THE ADDRESS ON THE | | | PLANS SHALL INCLUDE THE UNIT/SUITE NUMBER FOR | | | INSPECTION PURPOSES. THE DRAWINGS SUBMITTED DO NOT | | | CLEARLY SHOW THE EXISTING PLAN FROM THE PROPOSED PLAN. | | | THE EXISTING FLOOR PLAN SHALL ONLY SHOW THE WALLS AND | | | SYSTEMS WHICH ARE PRESANTLY AT THIS LOACTION. THE | | | EXISTING PLAN NEEDS TO SHOW THE PRESENT LAY-OUT OF THE | | | SPACE. THE PROPOSE PLAN NEEDS TO SHOW THE FUTURE | | | LAY-OUT OF THE SPACE. IF BOTH PLANS ARE ON THE SAME | | | DRAWING THE WALLS TO BE DEMOLISH SHALL BE CLEARLY | | | IDENTIFY WITH DOTED LINESOR SOME OTHER MEANS TO SHOW | | | WHAT IS NEW AND WHAT IS EXISTING. CONSTRUCTION | | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE | | | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED | | | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THE CODE. 106.1.1* | | | | | | 4)OK | | | 5)OK | | | | | | PARTIALLY ADDRESSED | | | 6)INDICATE ON THE PLANS THE OCCUPANT LOAD OF THE | | | SPACE PER SECTION 1004 AND TABLE 1004.1.2. STATE THE | | | USE OF THE OPEN AREA. PROVIDE A WALL LEGEND SHOWING THE | | | EXISTING WALLS AND THE NEW CONSTRUCTED WALLS. DEPENDING | | | ON THE USE OF OPEN SPACE ADDITIONAL COMMENTS MAY APPEAR | | | ON THE NEXT REVIEW. | | | | | | 7)OK | | | | | | NEEDS TO BE ADDRSSED | | | 8)108.3* THE CLAIMED VALUATION ON THE PERMIT | | | APPLICATION IS LOW. FOR PERMITTING PURPOSES VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT | | | STRUCTURAL, ELECTRIC INTERIOR FINISHES, ARCHITECTURAL | | | DESIGN FEES, MARKETING COSTS OVERHEAD AND PROFIT | | | EXCLUDING LAND. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-06-19 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-06-19 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-06-19 |
Time |
08:10 |
Sent To |
PC |
|
| Notes |
| 2008-06-19 11:30:11 | 6-19-08 | | | BUILDING PLAN REVIEW | | | PERMIT: 08060201 | | | ADD: 3700 GEORGIA AVE #10 | | | CONT: PRINCIPLE CONSTRUCTION LLC | | | TEL: (561) 533-5252 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 2)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 SUPPLEMENTS. | | | | | | 3)ADDITIONAL INFORMATION REQUIRED 106.1.2* SUBMIT AN | | | EXISTING FLOOR PLAN AND A PROPOSED FLOOR PLAN SHOWING | | | ALL CHANGES TO THE EXISTING LAYOUT. THE ADDRESS ON THE | | | PLANS SHALL INCLUDE THE UNIT/SUITE NUMBER FOR | | | INSPECTION PURPOSES. | | | | | | 4)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; | | | PROVIDE INFORMATION BASED ON INTERIOR FINISH | | | REQUIREMENTS BASED ON OCCUPANCY. | | | | | | 5)THE DOOR IN THE CORRIDOR SHALL A MINIMUM FIRE | | | PROTECTION RATING OF 20 MINUTES, SO PLEASE INDICATE THE | | | RATING IN MINUTES PER TABLE 715.3 SEE SECTION 715.3.3 | | | FOR MORE INFORMATION. | | | | | | 6)INDICATE ON THE PLANS THE OCCUPANT LOAD OF THE | | | SPACE PER SECTION 1004 AND TABLE 1004.1.2. STATE THE | | | USE OF THE OPEN AREA. PROVIDE A WALL LEGEND SHOWING THE | | | EXISTING WALLS AND THE NEW CONSTRUCTED WALLS. DEPENDING | | | ON THE USE OF OPEN SPACE ADDITIONAL COMMENTS MAY APPEAR | | | ON THE NEXT REVIEW. | | | | | | 7)OFFICE #3 HAS NO ACCESS TO THE SPACE EXCEPT GOING | | | THROUGH THE CORRIDOR. IF THIS IS A SEPARATE TENANT, THE | | | SEVEN FOOT INTERIOR WALLS AROUND THIS SPACE WILL HAVE | | | TO BE CHANGED TO PROVIDE TENANT SEPARATION FBC708.1 | | | | | | 8)108.3* THE CLAIMED VALUATION ON THE PERMIT | | | APPLICATION IS LOW. FOR PERMITTING PURPOSES VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT | | | STRUCTURAL, ELECTRIC INTERIOR FINISHES, ARCHITECTURAL | | | DESIGN FEES, MARKETING COSTS OVERHEAD AND PROFIT | | | EXCLUDING LAND. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-08-01 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-08-01 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-08-01 |
Time |
10:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-06-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-24 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-24 |
Time |
11:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2008-06-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-12 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-12 |
Time |
16:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-08-04 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-08-04 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-08-04 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2008-08-04 16:43:38 | *****APPROVED***** | | | | | | PLANS WERE PREVIOUSLY APPROVED ON 07/01/08;SHEET A-1 | | | RESTAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-07-01 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-07-01 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-07-01 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-06-16 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-06-16 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-06-16 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2008-06-16 14:53:02 | *****DENIED***** | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DE3MOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OIR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | ACCESS TO / EGRESS FROM THE OTHER TENANT OFFICES/SUITES | | | IN THE SAID BUILDING. | | | | | | 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 5.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW | | | WALL PARTITION IN TERMS OF CLASS A, CLASS B, OR CLASS | | | C. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-07-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-23 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-23 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2008-07-28 09:01:59 | TO "BOB"#12 | | 2008-07-23 09:22:58 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-06-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-23 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-23 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2008-06-23 11:32:34 | TO "BOB"#6 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-06-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-19 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-09 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2008-06-09 10:51:22 | TO "BOB"#5 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2008-06-10 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-06-10 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-06-10 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2008-06-10 08:39:10 | *ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE | | | VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | | IMPROVEMENT VALUE. |
|
|