Plan Review Details - Permit 08060178
Plan Review Stops For Permit 08060178
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-03-10 Cont ID  
Sent By jgomez Date 2009-03-10 Time 16:23 Rev Time 0.00
Received By jgomez Date 2009-03-10 Time 16:23 Sent To  
Notes
2009-03-10 16:24:11PROVISO SUBMITTAL AND REVISION SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2009-01-23 Cont ID  
Sent By jgomez Date 2009-01-23 Time 14:56 Rev Time 0.00
Received By jgomez Date 2009-01-23 Time 14:53 Sent To PC
Notes
2009-01-23 15:01:07BUILDING REVIEW COMMENTS:
  
 1- RECEIVED BY MAIL ARCHITECT'S LETTER REGARDING TENANT
 INSULATION. LETTER IS OK.
  
 2- CONTRACTOR NEEDS TO COMPLY WITH PROVISO DATED
 11-26-08 TO AVOID CONFLICTS OR DELAYS. THIS IS THE
 SECOND REMAINDER IN WRITING. SEE ATTACHED COPIES OF
 PROVISO AND REMAINDER COMMENTS.
 CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED IF PROVISO
 ITEMS ARE NOT CLEARED.
  
 3- REVISION FEES FOR THE REVISED ENERGY CALCULATIONS
 WILL APPLY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2009-01-09 Cont ID  
Sent By jgomez Date 2009-01-09 Time 13:09 Rev Time 0.00
Received By jgomez Date 2009-01-09 Time 13:08 Sent To PC
Notes
2009-01-09 13:16:49SUBMITTAL BUILDING REVIEW CHECKLIST:
  
 1- ARCHITECT'S LETTER REGARDING INSULATION BETWEEN
 UNITS NEEDS TO HAVE ARCHITECT'S ORIGINAL SIGNATURE, NOT
 COPY, AS REQUIRED BY SEC. 61G1-16.003 OF FLORIDA
 ADMINISTRATIVE CODE AND SEC. 481 FLORIDA STATUTE.
  
 2- COMPLY WITH PROVISO DATED 11/26/08 TO AVOID ANY
 CONFLICTS OR DELAYS. SEE ATTACHED COPY OF PROVISO.
 ***REMEMBER: REVISION FEES WILL APPLY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-11-26 Cont ID  
Sent By jgomez Date 2008-11-26 Time 13:33 Rev Time 0.00
Received By jgomez Date 2008-11-26 Time 10:01 Sent To FIRE
Notes
2008-11-26 14:11:06BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE ENERGY CALCULATIONS:
 A) THIS IS NOT NEW CONSTRUCTION. THIS IS AN EXISTING
 APARTMENT.
 B) SPECIFY NUMBER OF UNITS. THIS IS A MULTIFAMILY
 PROJECT.
 C) GLASS AREA ON ITEM 7A TO MATCH WITH 7B.
 D) INCLUDE COMMON WALLS AREA AND INSULATION AS REQUIRED
 BY SEC. 13-602.1.ABC.1.1 FBC 2004.
 E) INCLUDE COMMON CEILINGS/FLOORS AREAS AND INSULATION
 AS REQUIRED BY SEC. 13-304.1.ABC.1.2 FBC 2004.
 F) TOTAL CEILING TYPES TO MATCH CONDITIONED FLOOR AREA
 ON ITEM #6. COORDINATE WITH ITEM # 1E ABOVE.
 ***NOTE: REVISION FEES WILL APPLY.
  
 2- PROVIDE PRODUCT APPROVAL FOR OUTSWING ENTRY DOOR AS
 SHOWN ON PLANS. INFORMATION SUBMITTED IS FOR INSWING
 DOORS.
 NOTE: ARCHITECT TO REVIEW AN APPROVE IN WRITING ALL
 PRODUCT APPROVALS PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 3- MIN. R11 INSULATION REQUIRED ON CEILING/FLOOR AS
 REQUIRED BY SEC. 13-604.1.ABC.1.2 FBC 2004.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-11-07 Cont ID  
Sent By jgomez Date 2008-11-07 Time 16:49 Rev Time 0.00
Received By jgomez Date 2008-11-07 Time 16:48 Sent To P
Notes
2008-11-07 17:00:57RESIDENTIAL (R2) REHABILITATION, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) THIS IS NOT AN ADDITION. THIS IS AN EXISTING UNIT
 THAT IS GOING TO BE REHABILITATED BECAUSE OF FIRE
 DAMAGE.
 B) ITEM #7A AND #7B DON'T MATCH INFORMATION SHOWN ON
 ARCHITECTURAL PLANS. REVISE AS REQUIRED.
 C) SQUARE FOOTAGE OF GLASS ON PAGE TWO DOESN'T MATCH
 ACTUAL WINDOWS SHOWN ON ARCHITECTURAL PLANS. REVISE AS
 REQUIRED.
 ALSO, REVISE ORIENTATION OF WINDOWS. NOT ALL WINDOWS
 ARE LOCATED ON THE WEST SIDE. SEE PLANS AND REVISE AS
 REQUIRED.
 D) REVISE CEILING TYPE ITEM #10A. THERE IS NO ATTIC.
 THERE IS ANOTHER APARTMENT ON TOP OF THIS UNIT. REVISE
 AS REQUIRED.
 E) CLARIFY HOW GETTING R-4 INSULATION ON SLAB ON GRADE.
 REVISE AS REQUIRED. SEE PLANS.
 F) REVISE WALL TYPES ON ITEM #9. SEE PLANS AND REVISE
 AS REQUIRED. PLANS SHOW WOOD FRAMING CONSTRUCTION, NOT
 CONCRETE.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE SUBMITTED LATER AT TIME OF PERMIT
 PICK UP.
  
 3- ENGINEER NEEDS TO PROVIDE THE ENGINEERING FIRM
 MILTON ENGINEERING CONSULTANTS, P.A. CERTIFICATE OF
 AUTHORIZATION NUMBER ON ALL DRAWINGS AS REQUIRED BY
 SEC. 61G15--23.002(2) OF FLORIDA ADMINISTRATIVE CODE
 AND CHAPTER 471 FLORIDA STATUTE. (REPEAT COMMENT).
  
 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED DCA
 RULE 9B-72 FOR:
 A) ENTRY DOOR AS SHOWN ON PLANS. NONE SUBMITTED.
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 PAGE AND PAGE SHOWING THE CONNECTOR. NO NEED TO SUBMIT
 COMPLETE REPORT. THIS APPLIES TO CONNECTORS ONLY. OTHER
 PRODUCT APPROVALS NEED TO SUBMIT COMPLETE REPORT.
  
 5- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING (NOT SIGNING AND SEALING) BY THE
 DESIGNER OF RECORD AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004. (REPEAT COMMENT).
  
 6- DESIGNER OF RECORD TO SPECIFY LEVEL OF ALTERATION
 FOR THIS PROJECT AS REQUIRED BY SEC. 301.5 OF 2004
 FLORIDA EXISTING BUILDING CODE. (REPEAT COMMENT).
  
 7- SCOPE OF WORK SPECIFIED ON PERMIT APPLICATION IS FOR
 REPLACEMENT OF INTERIOR DRYWALL, CABINETS AND OTHER
 INTERIOR FINISHES ONLY. ELECTRICAL AND PLUMBING
 FIXTURES WERE CROSSED OUT. PLANS SUBMITTED ARE FOR NEW
 WINDOWS AND WINDOW FRAMING AND FOR COMPLETE RENOVATION
 OF APARTMENT. CLARIFY SCOPE OF WORK ON PERMIT
 APPLICATION AND REVISE TOTAL VALUATION DECLARED TO
 REFLECT ALL WORK TO BE PERFORMED. SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004.
  
 8- ARCHITECT NEEDS TO DATE PLANS WHEN THEY WERE SEALED
 AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE.
  
 9- ARCHITECT TO SPECIFY ON DRAWINGS IF FLOOR/CEILING
 ASSEMBLY IS GOING TO BE REPLACED. COMPLY WITH SEC. 503
 OF 2004 FLORIDA EXISTING BUILDING CODE.
 ***NOTE: UL SYSTEM L528 INCLUDES 16 FLOOR SYSTEMS.
 CLEARLY IDENTIFY WHICH FLOOR SYSTEM IS GOING TO BE
 INSTALLED. SEE L528 FOR DIFFERENT APPROVED SYSTEMS AND
 SELECT ONE.
  
 10- CONTRACTOR NEEDS TO UPDATE INSURANCE INFORMATION
 WITH PERMIT CLERK.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-09-26 Cont ID  
Sent By jgomez Date 2008-09-26 Time 13:22 Rev Time 0.00
Received By jgomez Date 2008-09-26 Time 13:22 Sent To  
Notes
2008-09-26 13:24:14TALKED TO ANTHONY COOPER. NEED TO PAY PERMIT FEES TO DO
 PLAN REVIEW. HE SAID HE'LL PAY OVER INTERNET/PHONE.
 WAITING FOR FEES TO BE PAID TO PERFORM PLAN REVIEW AND
 ROUTE TO PROPER TRADES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-07-22 Cont ID  
Sent By jgomez Date 2008-07-22 Time 10:31 Rev Time 0.00
Received By jgomez Date 2008-07-22 Time 10:26 Sent To PC
Notes
2008-07-22 10:44:02BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- ACCORDING TO PRE-INSPECTION PERFORMED BY CHIEF
 BUILDING INSPECTOR, KEN CONRAD, PLANS ARE REQUIRED TO
 ILLUSTRATE ALL SCOPE OF WORK TO BE PERFORMED. SEE
 ATTACHED COPY OF COMMENTS DONE BY KEN CONRAD ON
 6-18-08.
 NEED TO PROVIDE BUILDING, MECHANICAL, ELECTRICAL AND
 PLUMBING PLANS. IN ADDITION ENERGY CALCULATIONS WILL BE
 REQUIRED.
  
 ***NOTE: ENGINEERING PLANS SUBMITTED ONLY ILLUSTRATE
 THE REPLACEMENT OF 5 WINDOWS AND ONE DOOR. NEED TO
 PROVIDE COMPLETE SET OF PLANS SHOWING ALL SCOPE OF WORK
 TO BE PERFORMED. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004 TO VERIFY COMPLIANCE WITH PROPOSED WORK.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE SUBMITTED LATER AT TIME OF PERMIT
 PICK UP.
  
 3- ENGINEER NEEDS TO PROVIDE THE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER ON ALL DRAWINGS AS
 REQUIRED BY SEC. 61G15--23.002(2) OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE.
  
 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED DCA
 RULE 9B-72 FOR:
 A) WINDOWS.
 B) INSWING ENTRY DOOR AS SHOWN ON PLANS.
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
 D) STORM SHUTTERS IF WINDOWS/DOORS DON'T HAVE MISSILE
 IMPACT GLAZING.
 ***NOTE: ALSO, PROVIDE STORM SHUTTERS COMPLETE
 INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE.
  
 5- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING (NOT SIGNING AND SEALING) BY THE
 ENGINEER OF RECORD AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 6- ENGINEER TO SPECIFY LEVEL OF ALTERATION FOR THIS
 PROJECT AS REQUIRED BY SEC. 301.5 OF 2004 FLORIDA
 EXISTING BUILDING CODE.
  
 7- SPECIFY SIZE OF WINDOWS TO VERIFY COMPLIANCE WITH
 BEDROOMS EGRESS REQUIREMENTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-18 Cont ID  
Sent By kconrad Date 2008-06-18 Time 08:41 Rev Time 0.00
Received By kconrad Date 2008-06-18 Time 08:41 Sent To I
Notes
2008-06-18 08:56:46PERFORMED A PRE-INSPECT. ADVISED THE CONTRACTOR THAT
 PLANS WILL BE REQUIRED FOR BUILDING, MECHANICAL,
 ELECTRICAL AND PLUMBING. ALSO, ENERGY CALCULATIONS
 SHALL BE SUBMITTED AS WELL.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-11-07 Cont ID  
Sent By btrobaug Date 2008-11-07 Time 10:58 Rev Time 0.00
Received By btrobaug Date 2008-11-07 Time 10:24 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-01 Cont ID  
Sent By btrobaug Date 2008-10-01 Time 16:22 Rev Time 0.00
Received By btrobaug Date 2008-10-01 Time 12:14 Sent To P
Notes
2008-10-01 16:21:41 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET E-1, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE
 FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE INDICATE
 THE CODE CYCLES UNDER WHICH THIS PLAN WAS DESIGNED.
  
 1} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.***
 LOCATE ON THE PLANS. ALSO SEE THE DEFINITION OF "SMOKE
 DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS
 OR ALARMS, TO AVOID CONFUSION IN THE FIELD. IF USING
 DETECTORS INDICATE THE LOCATIONS OF THE SOUNDING
 DEVICES.THIS IS MENTIONED AS "SMOKE DETECTORS" IN THE
 LEGEND.
  
 2} 210.52(B)(1) RECEPTACLE OUTLETS SERVED IN THE
 KITCHEN, PANTRY, BREAKFAST ROOM, DINING ROOM, OR
 SIMILAR AREA OF A DWELLING UNIT, THE TWO OR MORE
 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY
 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP OUTLETS
 COVERED BY 210.52(C), AND RECEPTACLE OUTLETS FOR
 REFRIGERATION EQUIPMENT.*** THE DINING ROOM HAS CIRCUIT
 # 13 WHICH IS THE LIVING ROOM CIRCUIT IN THE PANEL AND
 IN VIOLATION OF THIS ARTICLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-11-12 Cont ID  
Sent By mwennerg Date 2008-11-12 Time 14:51 Rev Time 0.00
Received By mwennerg Date 2008-11-12 Time 14:51 Sent To  
Notes
2008-11-12 14:54:50***PROVISO***
  
 1) LIFE SAFETY CODE REFERENCE ON SHEET A-02 IS
 INCORRECT EDITION. DOORS SHALL COMPLY WITH NFPA 101,
 SEC. 7.2.1.5.
  
 PLANS WILL BE STAMPED WHEN RETURNED WITH THIS AND OTHER
 REVIEW CORRECTIONS
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-01-08 Cont ID  
Sent By adarroug Date 2009-01-08 Time 13:39 Rev Time 0.00
Received By adarroug Date 2009-01-08 Time 13:39 Sent To B
Notes
2009-01-08 13:39:43TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-12-31 Cont ID  
Sent By adarroug Date 2008-12-31 Time 10:25 Rev Time 0.00
Received By adarroug Date 2008-12-31 Time 10:25 Sent To M
Notes
2008-12-31 10:26:01TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-11-24 Cont ID  
Sent By adarroug Date 2008-11-24 Time 10:10 Rev Time 0.00
Received By adarroug Date 2008-11-24 Time 10:10 Sent To B
Notes
2008-11-24 10:11:38TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-04 Cont ID  
Sent By adarroug Date 2008-11-04 Time 13:42 Rev Time 0.00
Received By adarroug Date 2008-11-04 Time 13:42 Sent To E
Notes
2008-11-04 13:43:47TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-26 Cont ID  
Sent By adarroug Date 2008-09-26 Time 10:18 Rev Time 0.00
Received By adarroug Date 2008-09-26 Time 10:18 Sent To B
Notes
2008-09-26 10:19:11TO "JGOMEZ' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-22 Cont ID  
Sent By jgomez Date 2008-07-22 Time 10:59 Rev Time 0.00
Received By jgomez Date 2008-07-22 Time 10:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-01-10 Cont ID  
Sent By rregueir Date 2009-01-10 Time 14:05 Rev Time 0.00
Received By rregueir Date 2009-01-10 Time 14:05 Sent To PC
Notes
2009-01-10 14:05:20M1 8X11 SHEET REVISION

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-09-30 Cont ID  
Sent By tgordon Date 2008-09-30 Time 11:50 Rev Time 0.45
Received By tgordon Date 2008-09-30 Time 11:49 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-11-10 Cont ID  
Sent By mperson Date 2008-11-10 Time 11:16 Rev Time 0.45
Received By jgomez Date 2008-11-10 Time 11:16 Sent To FIRE
Notes
2008-11-26 13:47:30BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE ENERGY CALCULATIONS:
 A) GLASS SQUARE FOOTAGE ON ITEM 7A DOESN'T MATCH 7B.
 REVISE AS REQUIRED.
 B) ITEM 9: NEED TO INCLUDE COMMON WALLS AS REQUIRED BY
 SEC. 13-602.1.ABC.1.1 FBC 2004.
 C) ITEM 10: NEED TO INCLUDE COMMON CEILING/FLOORS AS
 REQUIRED BY SEC. 13-604.1.ABC.1.2 FBC 2004.
 D) REVISE CEILING AREA ON ITEM #10 TO MATCH CONDITIONED
 AREA ON ITEM #6. COORDINATE WITH ITEM 1C ABOVE.
  
 2- PROVIDE PRODUCT APPROVAL FOR OUTSWING ENTRY DOOR AS
 SHOWN ON PLANS. PRODUCT APPROVAL SUBMITTED IS FOR
 INSWING DOORS.
 ***NOTE: ARCHITECT TO REVIEW AN APPROVE IN WRITING ALL
 PRODUCT APPROVALS PRIOR TO SUBMITTAL TO THIS OFFICE.