| Plan Review Stops For Permit 08060178 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2009-03-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-03-10 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-03-10 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2009-03-10 16:24:11 | PROVISO SUBMITTAL AND REVISION SUBMITTAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2009-01-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-01-23 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-01-23 |
Time |
14:53 |
Sent To |
PC |
|
| Notes |
| 2009-01-23 15:01:07 | BUILDING REVIEW COMMENTS: | | | | | | 1- RECEIVED BY MAIL ARCHITECT'S LETTER REGARDING TENANT | | | INSULATION. LETTER IS OK. | | | | | | 2- CONTRACTOR NEEDS TO COMPLY WITH PROVISO DATED | | | 11-26-08 TO AVOID CONFLICTS OR DELAYS. THIS IS THE | | | SECOND REMAINDER IN WRITING. SEE ATTACHED COPIES OF | | | PROVISO AND REMAINDER COMMENTS. | | | CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED IF PROVISO | | | ITEMS ARE NOT CLEARED. | | | | | | 3- REVISION FEES FOR THE REVISED ENERGY CALCULATIONS | | | WILL APPLY. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2009-01-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-01-09 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-01-09 |
Time |
13:08 |
Sent To |
PC |
|
| Notes |
| 2009-01-09 13:16:49 | SUBMITTAL BUILDING REVIEW CHECKLIST: | | | | | | 1- ARCHITECT'S LETTER REGARDING INSULATION BETWEEN | | | UNITS NEEDS TO HAVE ARCHITECT'S ORIGINAL SIGNATURE, NOT | | | COPY, AS REQUIRED BY SEC. 61G1-16.003 OF FLORIDA | | | ADMINISTRATIVE CODE AND SEC. 481 FLORIDA STATUTE. | | | | | | 2- COMPLY WITH PROVISO DATED 11/26/08 TO AVOID ANY | | | CONFLICTS OR DELAYS. SEE ATTACHED COPY OF PROVISO. | | | ***REMEMBER: REVISION FEES WILL APPLY. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-11-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-11-26 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-11-26 |
Time |
10:01 |
Sent To |
FIRE |
|
| Notes |
| 2008-11-26 14:11:06 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- REVISE ENERGY CALCULATIONS: | | | A) THIS IS NOT NEW CONSTRUCTION. THIS IS AN EXISTING | | | APARTMENT. | | | B) SPECIFY NUMBER OF UNITS. THIS IS A MULTIFAMILY | | | PROJECT. | | | C) GLASS AREA ON ITEM 7A TO MATCH WITH 7B. | | | D) INCLUDE COMMON WALLS AREA AND INSULATION AS REQUIRED | | | BY SEC. 13-602.1.ABC.1.1 FBC 2004. | | | E) INCLUDE COMMON CEILINGS/FLOORS AREAS AND INSULATION | | | AS REQUIRED BY SEC. 13-304.1.ABC.1.2 FBC 2004. | | | F) TOTAL CEILING TYPES TO MATCH CONDITIONED FLOOR AREA | | | ON ITEM #6. COORDINATE WITH ITEM # 1E ABOVE. | | | ***NOTE: REVISION FEES WILL APPLY. | | | | | | 2- PROVIDE PRODUCT APPROVAL FOR OUTSWING ENTRY DOOR AS | | | SHOWN ON PLANS. INFORMATION SUBMITTED IS FOR INSWING | | | DOORS. | | | NOTE: ARCHITECT TO REVIEW AN APPROVE IN WRITING ALL | | | PRODUCT APPROVALS PRIOR TO SUBMITTAL TO THIS OFFICE. | | | | | | 3- MIN. R11 INSULATION REQUIRED ON CEILING/FLOOR AS | | | REQUIRED BY SEC. 13-604.1.ABC.1.2 FBC 2004. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2008-11-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-11-07 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-11-07 |
Time |
16:48 |
Sent To |
P |
|
| Notes |
| 2008-11-07 17:00:57 | RESIDENTIAL (R2) REHABILITATION, BUILDING REVIEW SECOND | | | CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- REVISE ENERGY CALCULATIONS SUBMITTED: | | | A) THIS IS NOT AN ADDITION. THIS IS AN EXISTING UNIT | | | THAT IS GOING TO BE REHABILITATED BECAUSE OF FIRE | | | DAMAGE. | | | B) ITEM #7A AND #7B DON'T MATCH INFORMATION SHOWN ON | | | ARCHITECTURAL PLANS. REVISE AS REQUIRED. | | | C) SQUARE FOOTAGE OF GLASS ON PAGE TWO DOESN'T MATCH | | | ACTUAL WINDOWS SHOWN ON ARCHITECTURAL PLANS. REVISE AS | | | REQUIRED. | | | ALSO, REVISE ORIENTATION OF WINDOWS. NOT ALL WINDOWS | | | ARE LOCATED ON THE WEST SIDE. SEE PLANS AND REVISE AS | | | REQUIRED. | | | D) REVISE CEILING TYPE ITEM #10A. THERE IS NO ATTIC. | | | THERE IS ANOTHER APARTMENT ON TOP OF THIS UNIT. REVISE | | | AS REQUIRED. | | | E) CLARIFY HOW GETTING R-4 INSULATION ON SLAB ON GRADE. | | | REVISE AS REQUIRED. SEE PLANS. | | | F) REVISE WALL TYPES ON ITEM #9. SEE PLANS AND REVISE | | | AS REQUIRED. PLANS SHOW WOOD FRAMING CONSTRUCTION, NOT | | | CONCRETE. | | | | | | 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | ***NOTE: THIS MAY BE SUBMITTED LATER AT TIME OF PERMIT | | | PICK UP. | | | | | | 3- ENGINEER NEEDS TO PROVIDE THE ENGINEERING FIRM | | | MILTON ENGINEERING CONSULTANTS, P.A. CERTIFICATE OF | | | AUTHORIZATION NUMBER ON ALL DRAWINGS AS REQUIRED BY | | | SEC. 61G15--23.002(2) OF FLORIDA ADMINISTRATIVE CODE | | | AND CHAPTER 471 FLORIDA STATUTE. (REPEAT COMMENT). | | | | | | 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED DCA | | | RULE 9B-72 FOR: | | | A) ENTRY DOOR AS SHOWN ON PLANS. NONE SUBMITTED. | | | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS | | | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL | | | PAGE AND PAGE SHOWING THE CONNECTOR. NO NEED TO SUBMIT | | | COMPLETE REPORT. THIS APPLIES TO CONNECTORS ONLY. OTHER | | | PRODUCT APPROVALS NEED TO SUBMIT COMPLETE REPORT. | | | | | | 5- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND | | | APPROVED IN WRITING (NOT SIGNING AND SEALING) BY THE | | | DESIGNER OF RECORD AS REQUIRED BY SEC. 106.3.3 CITY | | | AMENDMENTS TO FBC 2004. (REPEAT COMMENT). | | | | | | 6- DESIGNER OF RECORD TO SPECIFY LEVEL OF ALTERATION | | | FOR THIS PROJECT AS REQUIRED BY SEC. 301.5 OF 2004 | | | FLORIDA EXISTING BUILDING CODE. (REPEAT COMMENT). | | | | | | 7- SCOPE OF WORK SPECIFIED ON PERMIT APPLICATION IS FOR | | | REPLACEMENT OF INTERIOR DRYWALL, CABINETS AND OTHER | | | INTERIOR FINISHES ONLY. ELECTRICAL AND PLUMBING | | | FIXTURES WERE CROSSED OUT. PLANS SUBMITTED ARE FOR NEW | | | WINDOWS AND WINDOW FRAMING AND FOR COMPLETE RENOVATION | | | OF APARTMENT. CLARIFY SCOPE OF WORK ON PERMIT | | | APPLICATION AND REVISE TOTAL VALUATION DECLARED TO | | | REFLECT ALL WORK TO BE PERFORMED. SEC. 108.3 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 8- ARCHITECT NEEDS TO DATE PLANS WHEN THEY WERE SEALED | | | AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA | | | ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE. | | | | | | 9- ARCHITECT TO SPECIFY ON DRAWINGS IF FLOOR/CEILING | | | ASSEMBLY IS GOING TO BE REPLACED. COMPLY WITH SEC. 503 | | | OF 2004 FLORIDA EXISTING BUILDING CODE. | | | ***NOTE: UL SYSTEM L528 INCLUDES 16 FLOOR SYSTEMS. | | | CLEARLY IDENTIFY WHICH FLOOR SYSTEM IS GOING TO BE | | | INSTALLED. SEE L528 FOR DIFFERENT APPROVED SYSTEMS AND | | | SELECT ONE. | | | | | | 10- CONTRACTOR NEEDS TO UPDATE INSURANCE INFORMATION | | | WITH PERMIT CLERK. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-09-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-09-26 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-09-26 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2008-09-26 13:24:14 | TALKED TO ANTHONY COOPER. NEED TO PAY PERMIT FEES TO DO | | | PLAN REVIEW. HE SAID HE'LL PAY OVER INTERNET/PHONE. | | | WAITING FOR FEES TO BE PAID TO PERFORM PLAN REVIEW AND | | | ROUTE TO PROPER TRADES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-07-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-07-22 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-07-22 |
Time |
10:26 |
Sent To |
PC |
|
| Notes |
| 2008-07-22 10:44:02 | BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- ACCORDING TO PRE-INSPECTION PERFORMED BY CHIEF | | | BUILDING INSPECTOR, KEN CONRAD, PLANS ARE REQUIRED TO | | | ILLUSTRATE ALL SCOPE OF WORK TO BE PERFORMED. SEE | | | ATTACHED COPY OF COMMENTS DONE BY KEN CONRAD ON | | | 6-18-08. | | | NEED TO PROVIDE BUILDING, MECHANICAL, ELECTRICAL AND | | | PLUMBING PLANS. IN ADDITION ENERGY CALCULATIONS WILL BE | | | REQUIRED. | | | | | | ***NOTE: ENGINEERING PLANS SUBMITTED ONLY ILLUSTRATE | | | THE REPLACEMENT OF 5 WINDOWS AND ONE DOOR. NEED TO | | | PROVIDE COMPLETE SET OF PLANS SHOWING ALL SCOPE OF WORK | | | TO BE PERFORMED. SEC. 106.1.2 CITY AMENDMENTS TO FBC | | | 2004 TO VERIFY COMPLIANCE WITH PROPOSED WORK. | | | | | | 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | ***NOTE: THIS MAY BE SUBMITTED LATER AT TIME OF PERMIT | | | PICK UP. | | | | | | 3- ENGINEER NEEDS TO PROVIDE THE ENGINEERING FIRM | | | CERTIFICATE OF AUTHORIZATION NUMBER ON ALL DRAWINGS AS | | | REQUIRED BY SEC. 61G15--23.002(2) OF FLORIDA | | | ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE. | | | | | | 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED DCA | | | RULE 9B-72 FOR: | | | A) WINDOWS. | | | B) INSWING ENTRY DOOR AS SHOWN ON PLANS. | | | C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS | | | AND DETAILS. | | | D) STORM SHUTTERS IF WINDOWS/DOORS DON'T HAVE MISSILE | | | IMPACT GLAZING. | | | ***NOTE: ALSO, PROVIDE STORM SHUTTERS COMPLETE | | | INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE. | | | | | | 5- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND | | | APPROVED IN WRITING (NOT SIGNING AND SEALING) BY THE | | | ENGINEER OF RECORD AS REQUIRED BY SEC. 106.3.3 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 6- ENGINEER TO SPECIFY LEVEL OF ALTERATION FOR THIS | | | PROJECT AS REQUIRED BY SEC. 301.5 OF 2004 FLORIDA | | | EXISTING BUILDING CODE. | | | | | | 7- SPECIFY SIZE OF WINDOWS TO VERIFY COMPLIANCE WITH | | | BEDROOMS EGRESS REQUIREMENTS. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-06-18 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2008-06-18 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2008-06-18 |
Time |
08:41 |
Sent To |
I |
|
| Notes |
| 2008-06-18 08:56:46 | PERFORMED A PRE-INSPECT. ADVISED THE CONTRACTOR THAT | | | PLANS WILL BE REQUIRED FOR BUILDING, MECHANICAL, | | | ELECTRICAL AND PLUMBING. ALSO, ENERGY CALCULATIONS | | | SHALL BE SUBMITTED AS WELL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-11-07 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-11-07 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-11-07 |
Time |
10:24 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-10-01 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-10-01 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-10-01 |
Time |
12:14 |
Sent To |
P |
|
| Notes |
| 2008-10-01 16:21:41 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | ALL COMMENTS RELATE TO SHEET E-1, UNLESS OTHERWISE | | | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | | OTHERWISE NOTED. | | | | | | FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE | | | FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE INDICATE | | | THE CODE CYCLES UNDER WHICH THIS PLAN WAS DESIGNED. | | | | | | 1} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS | | | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING | | | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE | | | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE | | | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE | | | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.*** | | | LOCATE ON THE PLANS. ALSO SEE THE DEFINITION OF "SMOKE | | | DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS | | | OR ALARMS, TO AVOID CONFUSION IN THE FIELD. IF USING | | | DETECTORS INDICATE THE LOCATIONS OF THE SOUNDING | | | DEVICES.THIS IS MENTIONED AS "SMOKE DETECTORS" IN THE | | | LEGEND. | | | | | | 2} 210.52(B)(1) RECEPTACLE OUTLETS SERVED IN THE | | | KITCHEN, PANTRY, BREAKFAST ROOM, DINING ROOM, OR | | | SIMILAR AREA OF A DWELLING UNIT, THE TWO OR MORE | | | 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY | | | 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR RECEPTACLE | | | OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP OUTLETS | | | COVERED BY 210.52(C), AND RECEPTACLE OUTLETS FOR | | | REFRIGERATION EQUIPMENT.*** THE DINING ROOM HAS CIRCUIT | | | # 13 WHICH IS THE LIVING ROOM CIRCUIT IN THE PANEL AND | | | IN VIOLATION OF THIS ARTICLE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2008-11-12 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-11-12 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-11-12 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2008-11-12 14:54:50 | ***PROVISO*** | | | | | | 1) LIFE SAFETY CODE REFERENCE ON SHEET A-02 IS | | | INCORRECT EDITION. DOORS SHALL COMPLY WITH NFPA 101, | | | SEC. 7.2.1.5. | | | | | | PLANS WILL BE STAMPED WHEN RETURNED WITH THIS AND OTHER | | | REVIEW CORRECTIONS | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2009-01-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-08 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-08 |
Time |
13:39 |
Sent To |
B |
|
| Notes |
| 2009-01-08 13:39:43 | TO "JGOMEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-12-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-31 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-31 |
Time |
10:25 |
Sent To |
M |
|
| Notes |
| 2008-12-31 10:26:01 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-11-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-24 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-24 |
Time |
10:10 |
Sent To |
B |
|
| Notes |
| 2008-11-24 10:11:38 | TO "JGOMEZ" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-11-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-04 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-04 |
Time |
13:42 |
Sent To |
E |
|
| Notes |
| 2008-11-04 13:43:47 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-09-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-26 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-26 |
Time |
10:18 |
Sent To |
B |
|
| Notes |
| 2008-09-26 10:19:11 | TO "JGOMEZ' DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-07-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2008-07-22 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2008-07-22 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-01-10 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-01-10 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-01-10 |
Time |
14:05 |
Sent To |
PC |
|
| Notes |
| 2009-01-10 14:05:20 | M1 8X11 SHEET REVISION |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2008-09-30 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-09-30 |
Time |
11:50 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2008-09-30 |
Time |
11:49 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2008-11-10 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-11-10 |
Time |
11:16 |
Rev Time |
0.45 |
| Received By |
jgomez |
Date |
2008-11-10 |
Time |
11:16 |
Sent To |
FIRE |
|
| Notes |
| 2008-11-26 13:47:30 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- REVISE ENERGY CALCULATIONS: | | | A) GLASS SQUARE FOOTAGE ON ITEM 7A DOESN'T MATCH 7B. | | | REVISE AS REQUIRED. | | | B) ITEM 9: NEED TO INCLUDE COMMON WALLS AS REQUIRED BY | | | SEC. 13-602.1.ABC.1.1 FBC 2004. | | | C) ITEM 10: NEED TO INCLUDE COMMON CEILING/FLOORS AS | | | REQUIRED BY SEC. 13-604.1.ABC.1.2 FBC 2004. | | | D) REVISE CEILING AREA ON ITEM #10 TO MATCH CONDITIONED | | | AREA ON ITEM #6. COORDINATE WITH ITEM 1C ABOVE. | | | | | | 2- PROVIDE PRODUCT APPROVAL FOR OUTSWING ENTRY DOOR AS | | | SHOWN ON PLANS. PRODUCT APPROVAL SUBMITTED IS FOR | | | INSWING DOORS. | | | ***NOTE: ARCHITECT TO REVIEW AN APPROVE IN WRITING ALL | | | PRODUCT APPROVALS PRIOR TO SUBMITTAL TO THIS OFFICE. |
|
|