Plan Review Details - Permit 08060176
Plan Review Stops For Permit 08060176
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-07-15 Cont ID  
Sent By mjacobs Date 2008-07-15 Time 12:41 Rev Time 0.00
Received By mjacobs Date 2008-07-15 Time 11:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-17 Cont ID  
Sent By mjacobs Date 2008-06-17 Time 06:44 Rev Time 0.00
Received By mjacobs Date 2008-06-16 Time 14:36 Sent To PC
Notes
2008-06-17 06:44:40BUILDING PLAN REVIEW
 PERMIT: 08060176
 ADD: 5200 N. FLAGLER DR. #1604
 CONT: PAONE BUILDERS
 TEL: (561)575-0664
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)2004 FBC EXISTING 301.5.A DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 6)FBC 1207.3 FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS SHALL HAVE AN IMPACT INSULATION CLASS
 (IIC) RATING OR NOT LESS THAN 50 (45 IF FIELD TESTED)
 WHEN TESTED IN ACCORDANCE WITH ASTM E 492. PROVIDE MORE
 INFORMATION.
  
 7)ANY PLUMBING OR ELECTRICAL WORK FOR THIS PROJECT
 WILL REQUIRE A SEPARATE PERMIT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-07-15 Cont ID  
Sent By mwennerg Date 2008-07-15 Time 13:11 Rev Time 0.00
Received By mwennerg Date 2008-07-15 Time 13:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-16 Cont ID  
Sent By mawillia Date 2008-06-16 Time 11:31 Rev Time 0.00
Received By mawillia Date 2008-06-16 Time 11:21 Sent To  
Notes
2008-06-16 11:31:04*****UNSAT*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 ACCESS TO / EGRESS FROM THE OTHER UNITS ON THE SAID
 FLOOR OR THE BUILDING.
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6.SHOW AND/OR EXPLAIN HOW THE FIRE SPRINKLER HEADS
 AND SMOKE ALARMS WITHIN THE DWELLING UNIT WILL BE
 IMPACTED AS A RESULT OF THE REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-25 Cont ID  
Sent By adarroug Date 2008-06-25 Time 13:33 Rev Time 0.00
Received By adarroug Date 2008-06-25 Time 13:33 Sent To  
Notes
2008-06-25 13:34:08TO "BOB"#18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-15 Cont ID  
Sent By mjacobs Date 2008-06-16 Time   Rev Time 0.00
Received By mjacobs Date 2008-06-06 Time 14:57 Sent To  
Notes
2008-06-06 15:01:26TO "BOB"#2

Review Stop Z ZONING
Rev No 1 Status N Date 2008-06-10 Cont ID  
Sent By choops Date 2008-06-10 Time 08:36 Rev Time 0.00
Received By choops Date 2008-06-10 Time 08:36 Sent To  
Notes
2008-06-10 08:37:10*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.