Plan Review Details - Permit 08060146
Plan Review Stops For Permit 08060146
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-02-13 Cont ID  
Sent By rregueir Date 2009-02-13 Time 12:32 Rev Time 0.00
Received By rregueir Date 2009-02-13 Time 12:32 Sent To PC
Notes
2009-02-13 12:33:19IMPACT FEES PAID AND RECEIPT PROVIDED PER JULIO'S
 REQUEST. PASSED REVIEW ENTERED TO ALLOW PERMIT TO
 PRINT. RJR

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date 2008-12-17 Cont ID  
Sent By jgomez Date 2008-12-16 Time 10:06 Rev Time 0.00
Received By jgomez Date 2008-12-16 Time 09:49 Sent To PC
Notes
2008-12-17 11:11:20BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- REVISE STAIR DETAILS TO COMPLY WITH THE RISER TO
 TREAD RATIO OF SEC. R311.5.3.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) ROOF SHINGLES.
 B) PRECAST LINTELS
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE THEM IN
 WRITING PRIOR TO SUBMITTAL. SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-26 Cont ID  
Sent By jgomez Date 2008-06-26 Time 17:14 Rev Time 0.00
Received By jgomez Date 2008-06-26 Time 16:42 Sent To PC
Notes
2008-06-26 17:53:37RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- REVISE LOCATION OF ATTIC ACCESS TO COMPLY WITH SEC.
 R807.1 OF 2004 FLORIDA RESIDENTIAL CODE. CHECK CLEAR
 ROOM ABOVE OPENING.
  
 2- DESIGN INFORMATION ON SHEET 1 OF 2:
 A) ADD THE ATTIC LIVE LOAD AND SECOND FLOOR LIVE LOAD
 AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 B) SPECIFY BUILDING EXPOSURE USED FOR THE DESIGN AS
 REQUIRED BY SEC. R301.2.1.4 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE SUBMITTED AT TIME OF PRINTING THE
 PERMIT.
  
 4- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 5- OWES $549.69 FOR RADON FEES AND UPDATED VALUATION AS
 REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 6- PROVIDE COMPLETE SECTION/DETAILS AND SPECIFICATIONS
 FOR STAIRWAY AND RAILINGS TO SHOW COMPLIANCE WITH TABLE
 R301.5, SEC. R311.5.1, SEC. R311.5.3 , SEC. R311.5.6.1
 AND SEC. R312 OF 2004 FLORIDA RESIDENTIAL CODE. CLEARLY
 IDENTIFY NUMBER OF RISERS/TREADS AND PROVIDE ALL
 DIMENSIONS, INCLUDING STAIR DIMENSIONS.
 ***NOTE: CLARIFY CONSTRUCTION OF STAIRS AT BASE.
 DRAWINGS SUBMITTED DON'T SPECIFY ATTACHMENT AT BOTTOM
 OF STAIRS AND WHAT ARE STAIRS RESTING ON. DRAWINGS
 DON'T SHOW ANY INFORMATION.
  
 7- CLEARLY IDENTIFY DISTANCE BETWEEN PROPOSED BUILDING
 AND ADJACENT BUILDINGS (EVEN ON ADJACENT LOTS) TO
 VERIFY COMPLIANCE WITH SEC. R302 OF 2004 FLORIDA
 RESIDENTIAL CODE REGARDING WALLS FIRE RATING AND
 PERCENTAGE OF OPENINGS.
  
 8- SPECIFY FIREBLOCKING IN WALL SECTIONS AS REQUIRED BY
 SEC. R602.1.2 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES ) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) ROOF SHINGLES.
 B) GARAGE OVERHEAD DOOR. SEE PLAN FOR SIZE.
 C) GARAGE SIDE DOOR.
 D) FRENCH DOORS ON SECOND FLOOR.
 E) PRECAST LINTELS.
 F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS.
 G) SINGLE HUNG WINDOWS. NOA 03-0910.03 WAS SUPERSEDED.
 SEE ATTACHED COPY FROM DADE COUNTY WEBSITE. NEED TO
 PROVIDE CURRENT NOA.
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 11- PROVIDE COMPLETE SPECIFICATIONS FOR GARAGE
 SEPARATION AS REQUIRED BY SEC. R309.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 12- PLEASE BRING REVISED PLANS FOR HISTORIC RE-STAMP
 PRIOR TO SUBMITTAL TO THIS OFFICE TO AVOID DELAYS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-03 Cont ID  
Sent By mcruz Date 2008-12-03 Time 15:42 Rev Time 0.00
Received By btrobaug Date 2008-12-03 Time 15:19 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-06-13 Cont ID  
Sent By btrobaug Date 2008-06-13 Time 11:09 Rev Time 0.00
Received By btrobaug Date 2008-06-13 Time 11:00 Sent To P
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-06-05 Cont ID  
Sent By ssherman Date 2008-06-05 Time 13:26 Rev Time 0.00
Received By ssherman Date 2008-06-05 Time 13:26 Sent To  
Notes
2008-06-05 13:26:22HISTORICAL APPROVAL PER GALINA JUDGE NO FEE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-21 Cont ID  
Sent By adarroug Date 2008-11-21 Time 11:11 Rev Time 0.00
Received By adarroug Date 2008-11-21 Time 11:11 Sent To Z
Notes
2008-11-21 11:11:17TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-26 Cont ID  
Sent By jgomez Date 2008-06-26 Time 17:56 Rev Time 0.00
Received By jgomez Date 2008-06-06 Time 09:35 Sent To  
Notes
2008-06-06 09:35:17TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-06-09 Cont ID  
Sent By tgordon Date 2008-06-09 Time 13:43 Rev Time 0.25
Received By tgordon Date 2008-06-09 Time 13:43 Sent To E
Notes
2008-06-09 13:44:36COLTHES DRYER VENT ONLY.

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-06-18 Cont ID  
Sent By mperson Date 2008-06-18 Time 13:36 Rev Time 0.00
Received By mperson Date 2008-06-18 Time 13:36 Sent To B
Notes
2008-06-18 13:39:03****************PROVISO****************
 PER FBC- PLUMBING SECTION 708.3.5 BUILDING DRAIN AND
 BUILDING SEWER JUNCTION. THERE SHALL BE EITHER A
 TWO-WAY CLEANOUT NEAR THE JUNCTION OF THE BUILDING
 DRAIN AND THE BUILDING SEWER OR PROVIDE A 3 INCH
 CLEANOUT IN THE DRAINAGE STACK TO BE LOCATED AT 4 FEET
 ABOVE FINNISH FLOOR. PER SECTION 708.9 ACCESS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-12-03 Cont ID  
Sent By mcruz Date 2008-12-03 Time 15:41 Rev Time 0.00
Received By mcruz Date 2008-12-03 Time 15:40 Sent To P
Notes
2008-12-02 11:18:37NO A/C UNIT OR KITCHEN AND BATHROOM IN 2 STORY GARAGE.
 PROPERTY OWNER WAS ADVISED THAT RENTAL LICENSE CANNOT
 BE APPLIED FPR OR GRANTED FOR THIS STRUCTURE.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-06 Cont ID  
Sent By choops Date 2008-06-06 Time 16:36 Rev Time 0.00
Received By choops Date 2008-06-06 Time 16:36 Sent To E
Notes
2008-06-06 16:41:02***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT (IF ANY) TO ALL PROPERTY LINES.AS PER
 SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.
  
 2)INDICATE SEPARATION DISTANCE FROM PROPOSED
 STRUCTURE TO THE EXISTING PRINCIPAL STRUCTURE.NOTE:
 MUST MAINTAIN A MINIMUM 6 FOOT SEPARATION.
  
  
 NOTE:THE SINGLE FAMILY LOW-DENSITY (SF7) RESIDENTIAL
 ZONING DISTRICT DOES NOT ALLOW FOR THE USE OF ACCESSORY
 APARTMENTS.THIS STRUCTURE SHALL NOT BE USED AS A
 DWELLING UNIT NOW OR IN THE FUTURE.NO RENTAL LICENSE
 SHALL BE ISSUED FOR THIS STRUCTURE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - SF RACK