| 2008-07-02 14:56:33 | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | THE FOLLOWING IS FOR THE REVIEW OF ALL UNITS *A*,*B* |
| | AND*C*. |
| | |
| | 1) NOTE: PLEASE KNOW BASED ON PERMIT APPLICATION AND |
| | PLANS IT IS UNCLEAR SHOW THESE UNITS WILL ACTUALLY BE |
| | APPLIED. SOME ITEMS ON PLANS LEND TO A MULTI-FAMILY |
| | BUILDING AS THERE ARE REFERENCES TO ONE SERVICE, |
| | DE-RATING OF LOADS FOR MULTIPLE UNITS AND ALL AS |
| | APPLIED UNDER ONE ADDRESS. |
| | IF THESE ARE EACH A FEE SIMPLE TOWN HOUSE WITH PROPERTY |
| | LINES SEPARATING UNITS THIS WILL AFFECT PLANS AND |
| | REVIEWS. |
| | IF ONE BUILDING AND DONE AS A CONDO OR MULTI-FAMILY |
| | BUILDING THEN THE REVIEW COMMENTS WILL ALSO BE |
| | DIFFERENT. |
| | |
| | ** PLEASE COORDINATE APPLICATIONS, TYPES OF BUILDINGS |
| | ETC. PLEASE SEE COMMENTS BELOW AS THIS WILL AFFECT HOW |
| | THE REVIEWS/DESIGN IS CORRECTED. |
| | |
| | 2) NOTE: PLEASE SEE THE APPLIED ADDRESS FOR EACH |
| | LOCATION ON THE TITLE BLOCKS ON PLANS NEEDS TO BE |
| | ACCURATE ONCE DETERMINED. |
| | PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES SUCH |
| | AS FIRE, BUILDING AND THE ADDRESSING REVIEWER. |
| | PLEASE ADJUST TITLE BLOCKS FOR CORRECT ADDRESS. THIS IS |
| | REQUIRED FOR ALL SHEETS AND FOR ALL TRADES WHETHER OR |
| | NOT COMMENT IS MADE BY OTHER REVIEWERS. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | FBC 106.1.1, 106.5 FOR ADDITIONAL CLARITY AND RECORD |
| | PLANS. |
| | |
| | 3) NOTE: PLEASE BE SURE THE FOLLOWING CODE IS REFLECTED |
| | ON PLANS. THE STATE IS CURRENTLY UNDER THE 2002 |
| | NFPA-72. PLEASE ADJUST. |
| | PLEASE ALSO KNOW CODE SECTIONS SUCH AS THE NOTE ON E |
| | SHEETS WHICH REFERENCE SMOKE DETECTION DEVICES PER |
| | CHAPTER 8 ARE NO LONGER CORRECT AS THE CHAPTER UNDER |
| | THE CURRENT NFPA-72 HAS CHANGED. |
| | PLEASE SEE THE FOLLOWING COMMENTS. |
| | ** PLEASE KEEP IN MIND APPLICATION DATE AFFECT THE |
| | CODES AND CODE CHANGES WILL BE COMING THIS YEAR IN THE |
| | STATE OF FLORIDA. |
| | FS 553.73 |
| | FBC 106.1.1, 106.5 |
| | |
| | 4) NOTE: PLEASE SEE NFPA-72 DEFINITIONS AS THE PLANS |
| | STATE THERE WILL BE SMOKE DETECTORS INSTALLED HOWEVER |
| | NO FIRE ALARM PANEL, HORN ETC ARE SHOWN. |
| | PLEASE KNOW THAT *SMOKE DETECTORS* ARE DEVICES WHICH |
| | ONLY *DETECT* AND DO NOT SOUND AN ALARM. SMOKE ALARMS |
| | ARE DEVICES WHICH DETECT AND SOUND. PLEASE VERIFY WHICH |
| | DEVICES ARE ACTUALLY GOING TO BE INSTALLED. |
| | IF THESE ARE GOING TO INDEED BE SMOKE ALARMS, PLEASE BE |
| | SURE TO ADJUST ALL NOTES ON PLANS WHICH INDICATE SMOKE |
| | DETECTORS. |
| | PLEASE SEE NFPA72 11.5.1.1, 11.8.3 |
| | |
| | 5) NOTE: PLANS MISSING REQUIRED LIGHT FIXTURE OF SOME |
| | SORT ON UNITS A AND B AT THE COVERED PATIO. |
| | PLEASE ALSO SEE THE GREAT ROOMS IN ALL THREE UNITS WILL |
| | REQUIRE A LIGHT FIXTURE OF SOME SORT ON THE J-BOXES |
| | SHOWN OR HALF SWITCHED RECEPTACLES IN SAID ROOM. |
| | PLEASE ALSO SEE MISSING LIGHT FIXTURE OF SOME SORT |
| | INSIDE UNIT *A* LAUNDRY ROOM. |
| | 210.70 |
| | LS101 7.8 |
| | |
| | 6) NOTE: PLEASE SEE THE SERVICE CALCULATIONS INDICATE A |
| | 600AMP MAIN YET PLANS DO NOT CONTAIN ANY OTHER |
| | INFORMATION ON THE INDICATED SERVICE. |
| | 230.70, 215.5, 230.76, 230.72, 230.79 ETC |
| | |
| | 7) NOTE: PLEASE SEE LOAD CALCULATIONS INDICATE |
| | DE-RATING FOR 8 UNITS HOWEVER THE BUILDING DOES NOT |
| | CONTAIN 8 UNITS. |
| | PLEASE SEE OTHER COMMENTS LIKE #1 AND #6 AS THE LOAD |
| | CALCULATIONS INFORMATION ALONG WITH SERVICE DOES NOT |
| | COORDINATE. |
| | PLEASE SEE NEC 220 WHEN ACTUAL FINAL SERVICE IS |
| | DETERMINED. |
| | PLEASE COORDINATE ALL PLANS, RISER, EQUIPMENT AND LOAD |
| | CALCULATIONS. |
| | FBC 106.1.1, 106.1.2 FOR CLARITY AND ADDITIONAL |
| | INFORMATION. |
| | |
| | 8) NOTE: PLANS INDICATE A MAIN DISCONNECT OUTSIDE OF |
| | EACH UNIT HOWEVER THE RISER SUBMITTED IS MISSING THE |
| | MAIN DISCONNECT. |
| | 230.70, 230.71, 230.76 230.79 ETC |
| | |
| | 9) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR AFTER THE FIRST MEANS OF DISCONNECT PER |
| | 250.122, 250.24, 250.110 ETC IF MAIN IS OUTSIDE AS |
| | SHOWN. |
| | |
| | 10) NOTE: PLEASE BE SURE TO INDICATE THE REQUIRED |
| | *FOOTER STEEL* AS PART OF THE GROUND ELECTRODE SYSTEM. |
| | THE RISER SHOWS BUILDING STEEL HOWEVER MANY TIMES AND |
| | PER DEFINITIONS BUILDING STEEL IS NOT FOOTER STEEL. |
| | PLEASE ALSO CLARIFY COLD WATER SYSTEMS IN BUILDING. IF |
| | METALLIC, THEN PLEASE INCLUDE ON THE RISER. |
| | 250.50 |
| | |
| | 11) NOTE: PLEASE SEE 210.52B1 FOR CIRCUITING OF DINING |
| | ROOMS/AREAS AND OTHER AREAS OF THE LIKE. |
| | PLEASE SEE UNIT *A* AS THE AREA OFF KITCHEN WHICH |
| | APPEARS AS BREAKFAST/BAR AREA DOES FALL UNDER THE AREAS |
| | LISTED IN 210.52B1. |
| | PLEASE ADJUST PLANS AND ANY CALCULATIONS ACCORDINGLY TO |
| | 210.11C1, 220.52 |
| | |
| | 12) NOTE: PLEASE SEE UNIT *A* WHICH SHOWS THE WASHER |
| | CIRCUITED ON WITH LIGHTS AND GARAGE RECEPTACLES WHICH |
| | IS NOT PERMITTED. |
| | PLEASE SEE 210.11C2, 220.52B |
| | |
| | 13) NOTE: PLEASE SEE ALL WATER HEATER LOCATIONS PER |
| | 422.30, 422.31 REQUIRE DISCONNECTING MEANS. A |
| | RECEPTACLE IS NOT PERMITTED AS SHOWN ON PLANS. THIS |
| | CHANGED MANY CODE CYCLES AGO IN WHICH A CORD AND PLUG |
| | IS NOT PERMITTED ON WATER HEATERS. |
| | PLEASE ADJUST PLANS FOR ALL UNITS. |
| | |
| | 14) NOTE: PLEASE SEE 422.13 AS WATER HEATERS ARE NOW |
| | CONSIDERED A CONTINUOUS LOAD UNDER THE 2005 NEC WHICH |
| | REQUIRES LOADS TO BE FIGURED AT 125%. |
| | |
| | 15) NOTE: PLEASE KNOW ANY ITEMS WHICH ARE SHOWN ON |
| | PANELS OR PLANS AS *OPTIONAL* WILL BE REQUIRED TO BE |
| | REVISED ON EACH AND EVERY UNIT BEFORE ROUGH ELECTRICAL |
| | INSPECTION ON WHETHER OR NOT THAT UNIT WILL ACTUALLY |
| | RECEIVE THAT OPTION. |
| | ** THIS IS NOTED FOR INFORMATION AT THIS TIME AS THIS |
| | MAY HELP WITH THE DECISION OF EACH UNIT BEFORE |
| | APPLICATION IS MADE. |
| | NEC 408.4, 310.16, 220 ETC |
| | FBC 106.1.1, 106.5 FOR CLARITY AND RECORD PLANS |
| | COORDINATION. |
| | |
| | 16) NOTE: PLEASE SEE KITCHEN WALL IN UNIT *B* WHICH IS |
| | MISSING WALL RECEPTACLE PER 210.52 |
| | |
| | 17) NOTE: PLEASE INDICATEAIC RATINGS FOR ALL SERVICE |
| | EQUIPMENT.110.9 |
| | PLEASE COMPLETE INFORMATION ON ELECTRICAL PANELS. |
| | INFORMATION ON PANELS ARE VERY VAGUE AT THIS TIME. |
| | 110.9, 110.3, 90.7 |
| | FBC 106.1.1, 106.1.2 FOR CLARITY AND ADDITIONAL |
| | INFORMATION. |
| | |
| | 18) NOTE: IT IS IMPORTANT TO UNDERSTAND COMPLETION OF |
| | THE BUILDING NEEDS TO TAKE PLACE FOR WALLS ETC ON |
| | ENERGYCALCULATIONS. PLEASE SEE NOTES FROM OTHER |
| | TRADES AS THIS WILL AFFECT THE ENTIRE APPLICATION |
| | PROCESS. |
| | ** IT IS ALSO IMPORTANT TO UNDERSTAND AS THE RISER, |
| | PLANS, CALCULATIONS ETC FOR ACTUAL TYPE OF BUILDING IS |
| | NOT CLEAR AND THERE IS INFORMATION NOT YET SUBMITTED OR |
| | SHOWN IN DESIGN FOR REVIEW THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW. THERE MAY BE SOME |
| | COMMENTS WHICH COULD NOT POSSIBLY BE MADE AT THIS |
| | TIME. |
| | |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |