Plan Review Details - Permit 08060102
Plan Review Stops For Permit 08060102
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-06-09 Cont ID  
Sent By lursu Date 2008-06-09 Time 10:47 Rev Time 0.00
Received By lursu Date 2008-06-04 Time 12:30 Sent To  
Notes
2008-06-09 10:47:38PERMIT ATTACHED TO CORRECT PCN.
2008-06-04 12:30:40HOLD CAME UP TO SEND TO ADDRESSING

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-10-08 Cont ID  
Sent By shill Date 2009-10-08 Time 13:58 Rev Time 0.00
Received By shill Date 2009-10-08 Time 13:58 Sent To  
Notes
2009-10-08 13:59:10SHEET A2.1.1A
 OK TO ISSUE W/ARCHITECT'S EMAILED DIRECTION RE: CEILING
 ASSEMBLY (PER DW)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-10-06 Cont ID  
Sent By shill Date 2009-10-06 Time 18:19 Rev Time 0.00
Received By shill Date 2009-10-06 Time 18:19 Sent To  
Notes
2009-10-06 18:20:54REVISION, A2.1.1B

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2009-10-06 Cont ID  
Sent By shill Date 2009-10-06 Time 17:42 Rev Time 0.00
Received By shill Date 2009-10-06 Time 17:42 Sent To  
Notes
2009-10-06 17:50:17****CORRECTIONS****
 ****REVISION, A2.1.1A****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE ATTACHED, ULU499 IS FOR NON-BEARING WALLS. PLAN
 SHOWS U499 FOR A 1 HOUR CEILING. SEE ALSO UL FIRE
 RESISTANCE RATINGS DESIGN INFORMATION SECTION
 (ATTACHED). ALL ASSEMBLIES WITH THE "U" PREFIX ARE WALL
 AND PARTITION ASSEMBLIES; ROOF-CEILING HAVE A P, Q, OR
 R PREFIX.
  
 HTTP://DATABASE.UL.COM/CGI-BIN/XYV/TEMPLATE/LISEXT/1FRA
 ME/SHOWPAGE.HTML?&NAME=BXUV.GUIDEINFO&CCNSHORTTITLE=FIR
 E+RESISTANCE+RATINGS+-+ANSI/UL+263&OBJID=1074327030&CFG
 ID=1073741824&VERSION=VERSIONLESS&PARENT_ID=1073984818&
 SEQUENCE=1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-07-06 Cont ID  
Sent By shill Date 2009-07-06 Time 11:36 Rev Time 0.00
Received By shill Date 2009-07-06 Time 11:36 Sent To  
Notes
2009-07-06 11:40:02REVISION, A2.1.1A, 2.1.1B DATED 4/28/9

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-06-26 Cont ID  
Sent By shill Date 2009-06-26 Time 13:26 Rev Time 0.00
Received By shill Date 2009-06-26 Time 13:26 Sent To  
Notes
2009-06-26 13:29:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE PROVIDE AN UPDATED VALUATION AND REVISED
 DESCRIPTION OF WORK.
  
 2. THIS REVISION WILL BE ISSUED WITH PROVISO, PLUMBING
 PERMIT REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-03-02 Cont ID  
Sent By shill Date 2009-03-02 Time 10:33 Rev Time 0.00
Received By shill Date 2009-03-02 Time 10:33 Sent To  
Notes
2009-03-02 10:50:03**PROVISO**
 1. DP REQUIREMENT FOR THE DOOR IS-55.7. ONLY ONE OPTION
 ON THE PRODUCT APPROVAL COMPLIES (ND SERIES).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-01-21 Cont ID  
Sent By shill Date 2009-01-21 Time 11:14 Rev Time 0.00
Received By shill Date 2009-01-21 Time 11:14 Sent To  
Notes
2009-01-21 11:34:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. PLEASE PROVIDE UPDATED VALUE. SCOPE OF WORK HAS
 INCREASED (NOTE NEW PLANS DATED 12/2/08, NOT A PART OF
 FIRST REVIEW).
  
 2. PLEASE SPECIFY HEAD OF WALL DETAIL FOR THE NEW RATED
 WALL, FBC706.4, FBC 708.4.
  
 3. PROVIDE A DETAIL FOR UL465 ON THE PLAN.
  
 4. INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6, BUILDING
 HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, OCCUPANCY
 CLASSIFICATION FBC 3.
  
 5. PROVIDE DIMENSION BETWEEN THE PROPOSED NEW ELECTRIC
 ROOM SOUTH WALL AND THE EXISTING DRESSING ROOM DOOR
 (BETWEEN DRESSING ROOM AND CORRIDOR) TO SHOW
 MANEUVERING CLEARANCE REQUIRED, FBC FIGURE 11 25.
  
 6. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC*106.3.3.
  
 7. DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 8. THE PROPOSED ELECTRIC ROOM APPEARS TO EXIT DIRECTLY
 TO THE OUTSIDE, BUT DOUBLE LINES ARE SHOWN ON THE PLAN
 GOING TO THE PROPERTY LINE OUSTIDE THE DOOR. PLEASE
 PROVIDE A DESIGNATION FOR THIS AREA; IS IT INSIDE OR
 OUTSIDE? NOT ENOUGH INFORMATION PROVIDED TO DETERMINE
 USE OF THIS .
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-07-01 Cont ID  
Sent By shill Date 2008-07-01 Time 08:58 Rev Time 0.00
Received By shill Date 2008-07-01 Time 08:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2009-10-30 Cont ID  
Sent By dpalmer Date 2009-10-30 Time 07:55 Rev Time 0.00
Received By dpalmer Date 2009-10-08 Time 11:04 Sent To  
Notes
2009-10-30 08:18:35** TEMP FAILED. **
  
 1) NOTE: PLANS WERE PLACED INTO TEMPORARY FAILED STATUS
 ON OCTOBER 8H, 2009. RISER WAS REVISED REMOVING
 GROUNDING ELECTRODE BOND BETWEEN BOTH SERVICES. THE
 LETTER ATTACHED MENTIONS THE CITY OF WEST PALM BEACH
 CONSIDERS BOTH THE NEW ADDITION AND EXISTING BUILDINGS
 AS TWO SEPARATE BUILDINGS THEREFORE REMOVING THE
 GROUNDING ELECTRODE BONDING BOTH SERVICES.
 THE PREVIOUS CONVERSATIONS WERE THAT IT WAS THE DESIRE
 OF THE DESIGN TEAM TO HAVE TWO SEPARATE BUILDINGS
 ALLOWING TWO SEPARATE SERVICES. IN THOSE DISCUSSIONS
 AND PREVIOUS PLAN REVIEWS IT WAS GONE OVER THAT NO
 SYSTEMS OR METALLIC PATHS FROM EACH BUILDING COULD PASS
 THROUGH OR BE INTERCONNECTED FROM EACH BUILDING OTHER
 WISE SERVICES WOULD BE REQUIRED TO BE BONDED.
 THE RISER DIAGRAM HAS NOW BEEN REVISED TO REMOVE THE
 GROUNDING ELECTRODE BOND.
 THIS REVIEWER PLACED A CALL TO JOHN CHIRGWIN FROM KAMM
 CONSULTING TO GO OVER ANY POSSIBLE METALLIC PATHS. MR.
 CHIRGWIN DID NOT HAVE THE INFORMATION AND WAS GOING TO
 GET BACK TO THIS OFFICE.
 TO DATE OF THIS REVIEW ENTRY THIS HAS NO OCCURRED.
  
  
 THERE CAN BE NO METALLIC PATHS BETWEEN BUILDINGS. THE
 SEPARATION INFORMATION PROVIDED ON ARCHITECTURAL PLANS
 INDICATES A 4HR FIRE WALL FOR SEPARATION. PER THE
 DEFINITIONS IN THE FLORIDA BUILDING CODE THESE CAN BE
 CONSIDERED TWO SEPARATE BUILDINGS. SEPARATE BUILDINGS
 INCLUDE ALL SYSTEMS.
 THIS WAS GONE OVER ON NUMEROUS OCCASIONS BEFORE THIS
 REVIEW. IF A METALLIC PATH EXISTS, THEN SERVICES SHALL
 BE BONDED. SIZING PER 250.66
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2009-08-07 Cont ID  
Sent By dpalmer Date 2009-08-07 Time 13:31 Rev Time 0.00
Received By dpalmer Date 2009-08-07 Time 13:30 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2009-06-19 Cont ID  
Sent By dpalmer Date 2009-06-19 Time 15:41 Rev Time 0.00
Received By dpalmer Date 2009-06-19 Time 15:41 Sent To  
Notes
2009-06-19 15:42:17 
 ** DENIED PLANS *
  
 1) NOTE: PLEASE PROVIDE UPDATED DESCRIPTION FOR SCOPE
 OF WORK. THE APPLIED VALUE FOR THE ADDITIONAL SCOPE OF
 WORK ALSO NEEDS TO BE INCREASED PER FBC 108.3.
  
 2) NOTE: PLEASE SHOW THE LOCATION OF THE OVER RIDE AS
 STATED ON PLANS. WHAT TYPE OF OVER RIDE, TIMED? WITHIN
 SIGHT OF LIGHTING BEING CONTROLLED? OR MEET EXCEPTIONS.
 PLEASE ALSO SUBMIT INFORMATION ON THE EXISTING TIMED
 CONTROL AS STATED ON PLANS.
 13-415.AB.5, 13-415.AB.1.1,.1.2, .1.3, .1.4.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2009-02-18 Cont ID  
Sent By dpalmer Date 2009-02-18 Time 10:31 Rev Time 0.00
Received By dpalmer Date 2009-02-18 Time 10:31 Sent To  
Notes
2009-02-18 10:32:45EM PANEL IS NOT FED BY ANY GENERATOR, ALL EMERGENCY AND
 EXIT LIGHTS ARE TO BE VERIFIED AS BATTERY BACK UP AS
 STATED ON PLANS.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-12-26 Cont ID  
Sent By dpalmer Date 2008-12-26 Time 14:15 Rev Time 0.00
Received By dpalmer Date 2008-12-26 Time 14:14 Sent To  
Notes
2008-12-26 14:15:10** DENIED 6TH REVIEW **
  
 1) NOTE: PLANS AND RISER STILL NEED SOME COORDINATION.
 PLANS SHOW EXISTING PANEL *C* TO REMAIN HOWEVER THE
 RISER AND DPA DOES NOT INDICATE ANY FEED TO ANY PANEL
 *C*. WHERE IS THIS PANEL FED FROM?
 WHAT IS THE LOAD ON THIS PANEL?
 DPA SCHEDULE LIST SEVERAL PANELS AND EQUIPMENT HOWEVER
 NOT THIS PANEL.
 240.4,310.16,220,230,215.5 ETC.
 ON PREVIOUS REVIEW THE ELECTRICAL RISER WHICH HAD
 PROPOSED NEW DISCONNECT FOR A/C EQUIPMENT ONLY HAS NOT
 BEEN REMOVED. THE DISCONNECT STILL SHOWN AS EXISTING
 HAS NEVER BEEN PERMITTED. THE KEY NOTES ON SHEET E3.1
 STILL REFERS TO THIS EQUIPMENT AS NEW TO BE INSTALLED.
  
 2) NOTE: PLEASE REVISE THE APPLIED VALUE FOR THE NEW
 COMPLETE SCOPE OF WORK. THE NEW ROOM, MAIN ELECTRICAL
 DISTRIBUTION SYSTEM WAS NOT PART OF THE ORIGINAL SCOPE
 OF WORK WHICH WAS APPLIED FOR UNDER A MECHANICAL
 PRIMARY PERMIT.
 FBC 108.3
 THE PREVIOUS APPLICATION VALUES WERE BASED ON OLD SCOPE
 OF WORK WHICH HAS SUBSTANTIALLY INCREASED.
  
 3) NOTE: PLANS INDICATE NEW FACP. HOW IS THIS FED, FROM
 WHERE AND CIRCUIT?
 PLEASE SEE POSSIBLE FIRE MARSHAL REVIEW COMMENTS.
  
  
 *** NO FEE PER FS 553.80(2)(B) IS ASSESSED AS PLANS
 HAVE CHANGED OR BEEN REVISED IN ONE WAY AS TO NOT HAVE
 THE SAME SPECIFIC CODE DEFICIENCY THREE OR MORE TIMES.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-11-17 Cont ID  
Sent By dpalmer Date 2008-11-17 Time 08:48 Rev Time 0.00
Received By dpalmer Date 2008-11-17 Time 08:47 Sent To PC
Notes
2008-11-17 08:48:27 
  
  
 ** FAILED **
  
 1) NOTE: PLEASE SEE NOTES FROM THE PREVIOUS REVIEW. AS
 THE SCOPE OF WORKED HAS CHANGED FROM THE ORIGINAL
 REVIEW TO INCLUDE A NEW ELECTRICAL SERVICE, NEW
 ELECTRICAL ROOM ETC. AS STATED ON PREVIOUS REVIEW AS
 THE PRIMARY SCOPE OF WORK IS NO LONGER MECHANICAL THE
 MECHANICAL CONTRACTOR MAY NOT APPLY FOR THE MAIN SCOPE
 OF WORK. THE RESPONSE FROM THE DESIGNER MENTIONS THE
 MECHANICAL CONTRACTOR WILL APPLY. PLEASE SEE THE
 PREVIOUS REVIEW WHICH STATED TO SUBMIT COMPLETED PLANS
 FOR THE NEW ROOMS BEING CONSTRUCTED AND REMODELED.
 PLEASE ALSO BE SURE TO SUBMIT ANY PRODUCT APPROVALS FOR
 EXTERIOR.
 FBC 106.1.1, 105.1
  
  
 2) NOTE: THE DESIGN WATTAGE IS BEING SHOWN OVER THE
 ALLOWED WATTAGE AS SHOWN ON SHEET E2.1. PLEASE SEE
 13-415.2, 13-415.2.ABC.1.1, .1.2, TABLE 13-415.2.B.
 MAY NOT EXCEED SPECIFIC ALLOWANCES.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-10-03 Cont ID  
Sent By dpalmer Date 2008-10-03 Time 08:26 Rev Time 0.00
Received By dpalmer Date 2008-10-03 Time 08:26 Sent To PC
Notes
2008-10-03 08:27:32 
 ** DENIED 4TH REVIEW **
  
  
  
  
 1) NOTE: PLEASE SEE THE PLANS HAVE NOW BEEN REVISED TO
 INDICATE A COMPLETE NEW ELECTRICAL RISER CALLING THE
 DISCONNECT FOR AC EQUIPMENT AS EXISTING. HOW IS THIS
 POSSIBLE WHEN THIS PERMIT APPLICATION WAS TO INSTALL
 THIS SAME DISCONNECT WHICH IS NOW SHOWN AS EXISTING?
 IF THE SCOPE OF WORK IS NOW TO INCLUDE A NEW MDP,
 ELECTRICAL ROOMS, AND OTHER ROOMS AS SHOWN ON
 ELECTRICAL PLANS, THEN PLEASE REVISE THE ENTIRE SET OF
 PLANS. PLEASE REVISE PERMIT APPLICATION, PERMIT
 VALUATION ETC. THE APPLICATION AS SUBMITTED IS BY THE
 MECHANICAL CONTRACTOR THE SPECIFIED WORK OF: * THE
 ADDITION OF ONE ROOF MOUNTED OUTSIDE AIR PACKAGE UNIT*.
 THESE PLANS SUGGEST BUILDING A NEW SERVICE ETC IN A
 ROOM WHICH DOES NOT EXIST AT THIS TIME. THIS IS BASED
 ON PLANS WHICH WERE PREVIOUSLY SUBMITTED WHICH DID NOT
 CONTAIN THIS ROOM AND IT WAS BEING CREATED FOR NEW
 SERVICE.
 COORDINATION WITH ALL PARTIES INVOLVED NEEDS TO BE
 ACHIEVED BEFORE RE-SUBMITTING PLANS FOR REVIEW. A SITE
 VISIT MAY BE REQUESTED TO SEE WHAT EXISTS AND WHAT IS
 ACTUALLY ON-SITE. PLEASE CONTACT THIS OFFICE SO THIS
 MAY BE ARRANGED. NO FURTHER REVIEWS WILL BE DONE UNTIL
 EQUIPMENT AND CONDITIONS IN THE FIELD CAN BE CONFIRMED.
  
 2) NOTE: RISER SHOWS WHAT ONE WOULD ASSUME AS THE MDP
 AS DPA. PLEASE ADJUST THIS MISPRINT.
 408.4
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 3) NOTE: THE RISER NOW CALLS FOR A NEW PANEL *EM*.
 TYPICALLY EM DESIGNATION IS FOR EMERGENCY PANELS YET NO
 OTHER BACK UP SYSTEMS ARE SHOWN. IS THIS AN EMERGENCY
 PANEL OR JUST USING THIS DESIGNATION?
 700,701, 702 ETC
 FBC 106.1.1, FOR ADDITIONAL INFORMATION AND CLARITY OF
 PLANS.
  
 4) NOTE: IF THE WORK FOR ROOMS, LIGHTING ETC BECOMES
 PART OF THE SCOPE OF WORK PLEASE PROVIDE LIGHTING
 PERFORMANCE CALCULATIONS PER 13-415.2,
 13-415.2.ABC.1.1, .1.2.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-09-11 Cont ID  
Sent By dpalmer Date 2008-09-11 Time 10:11 Rev Time 0.00
Received By dpalmer Date 2008-09-11 Time 10:11 Sent To PC
Notes
2008-09-11 10:12:10** DENIED REVIEW **
  
  
  
 1) NOTE: AS NOTED ON PREVIOUS REVIEW AND ON MEETINGS
 HELD VIA PHONE. ALL PROPOSED SERVICE(S) FOR BUILDING
 NEED TO BE SHOWN IN ORDER TO SEE *IF* AN ADDITIONAL
 SERVICE CAN BE GRANTED FOR THE MECHANICAL EQUIPMENT
 ALONE. THERE IS NO INFORMATION SHOWN. THE PHONE MEETING
 CONSISTED INFORMING THIS OFFICE ANOTHER NEW SERVICE FOR
 THIS BUILDING IS PLANNED AND ON DRAWINGS HOWEVER HAVE
 NOT BEEN SUBMITTED AS OF YET.
 230.2
  
 ** PLEASE COMPLETE PLANS WITH ALL ELECTRICAL. FBC
 106.3.5.1.2, 106.1.1, 2005 NEC
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-07-30 Cont ID  
Sent By dpalmer Date 2008-07-30 Time 09:51 Rev Time 0.00
Received By dpalmer Date 2008-07-30 Time 09:51 Sent To M
Notes
2008-07-30 09:51:43 
 ** DENIEDREVIEW **
  
  
 1) NOTE:SERVICE AS SHOWN NOT PERMITTED PER 230.2. NO
 OTHER MAIN ARE SHOWN. THE PLANS ARE NOT COMPLETE
 SHOWING ALL ASPECTS OF THE ELECTRICAL SERVICE,
 LOCATIONS, SIZES, MAINS, GROUPING ETC
 110.9,230.2,230.70,230.71,230.72,230.76,230.79 ETC
 PLANS DO NOT SHOW COMPLETE SEPARATION FROM OTHER NEW
 STRUCTURE. THE NEW STRUCTURE CURRENTLY BEING BUILT WAS
 GOING TO FEED THIS BUILDING WITH ANOTHER SERVICE FROM
 ANOTHER FPL TRANSFORMER.
 PLEASE SEE THE FBC FOR DEFINITIONS OF A BUILDING AND
 REQUIRED SEPARATIONS. A FOUR RATED WALL IS NOT THE ONLY
 REQUIREMENT.
 THE PLANS ARE NOT COMPLETE WITH MUCH INFORMATION NEEDED
 TO BE SHOWN. A CALL WAS PLACED TO THE ENGINEERS OFFICE
 ON TWO OCCASIONS.
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-30 Cont ID  
Sent By btrobaug Date 2008-06-30 Time 16:43 Rev Time 0.00
Received By btrobaug Date 2008-06-30 Time 15:25 Sent To B
Notes
2008-06-30 15:57:58 
  
  
 DENIED
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE DISCONNECT IS SHOWN AS A SEPARATE SERVICE (MAIN
 1 OF 1, SHEET EO.1 AND E3.1) AND IN VIOLATION OF
 ARTICLE 230.2, 2005 NEC.THE DISCONNECT FOR THE NEW
 MECHANICAL UNIT MUST BE FEED FROM THE EXISTING
 SERVICE.
  
  
 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO
 BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5
 NEC 2005.
  
 3} 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT OUTLET
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET
 SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING MEANS.**THE RECEPTACLE MOUNTING
 TO THE UNIT ON SHEET E3.1APPEARS AS THOUGH THE CONDUIT
 IS GOING INTO THE UNIT AND NOTE #3 INDICATES EXISTING
 POWER, PLEASE CLARIFY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-08-10 Cont ID  
Sent By mawillia Date 2009-08-10 Time 13:10 Rev Time 0.00
Received By mawillia Date 2009-08-10 Time 12:52 Sent To  
Notes
2009-08-10 13:10:27*****REVISION, DATED 7/09/09, APPROVED
  
  
 REVISED PLAN SHEETS E2.1 AND E2.2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-06-26 Cont ID  
Sent By mawillia Date 2009-06-26 Time 11:34 Rev Time 0.00
Received By mawillia Date 2009-06-26 Time 10:56 Sent To  
Notes
2009-06-26 11:34:20*****REVISION, DATED 4/28/09, APPROVED*****
  
  
 REVISED PLAN SHEET A2.1.1A AND NEWLY ADDED SHEET
 A2.1.1.1B WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-03-06 Cont ID  
Sent By mawillia Date 2009-03-06 Time 12:45 Rev Time 0.00
Received By mawillia Date 2009-03-06 Time 12:33 Sent To  
Notes
2009-03-06 12:40:29*****APPROVED*****
  
  
 PLAN SHEETS A2.1.1A AND E2.1 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-01-27 Cont ID  
Sent By mcarsill Date 2009-01-27 Time 09:08 Rev Time 0.00
Received By mcarsill Date 2009-01-27 Time 09:05 Sent To  
Notes
2009-01-27 09:08:18APPROVED PROVISO
  
 1. THE NEW ELECTRICAL CLOSET OR ROOM SHALL BE PROPERLY
 PROTECTED WITH FIRE SPRINKLERS IF THE REMAINDER OF THE
 BUILDING IS PROTECTED.
  
 2. THE NEW LAY IN ACCOUSTICAL CEILING IS TO COMPLY WITH
 APPLICABLE FLAME SPREAD REQUIREMENTS.
  
 3. THE NEW FIRE ALARM CONTROL PANEL IS TO BE TESTED
 AFTER INSTALLATION. APPROPRIATE PLANS AND PERMITS WILL
 BE REQUIRED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2010-01-21 Cont ID  
Sent By jwitmer Date 2010-01-21 Time 10:32 Rev Time 0.00
Received By jwitmer Date 2010-01-21 Time 10:32 Sent To M
Notes
2010-01-21 10:33:11INCOMING SENT TO R.R.

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2009-10-06 Cont ID  
Sent By lmartine Date 2009-10-06 Time 16:11 Rev Time 0.00
Received By lmartine Date 2009-10-06 Time 16:10 Sent To  
Notes
2009-10-06 16:12:51***********EXPEDITED************
2009-10-06 16:11:31GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-09-29 Cont ID  
Sent By shill Date 2009-09-29 Time 10:34 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2009-09-29 10:35:06REVISION SUBMITTED 9/28 TO DVP DESK (E0.1)

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-08-04 Cont ID  
Sent By lmartine Date 2009-08-04 Time 17:16 Rev Time 0.00
Received By lmartine Date 2009-08-04 Time 17:16 Sent To  
Notes
2009-08-04 17:17:12GAVE TO
 RON------------------EXPEDITED----------------------

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-06-02 Cont ID  
Sent By btrobaug Date 2009-06-02 Time 15:40 Rev Time 0.00
Received By btrobaug Date 2009-06-02 Time 15:23 Sent To  
Notes
2009-06-02 15:40:06C-19
2009-06-02 15:27:07 
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-02-09 Cont ID  
Sent By adarroug Date 2009-02-09 Time 09:36 Rev Time 0.00
Received By adarroug Date 2009-02-09 Time 09:36 Sent To  
Notes
2009-02-09 09:39:00TO "COMM" BD#48

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-12-18 Cont ID  
Sent By adarroug Date 2008-12-18 Time 08:06 Rev Time 0.00
Received By adarroug Date 2008-12-18 Time 08:06 Sent To  
Notes
2008-12-18 08:09:39TO "COMM" BD#28--PER "DPALMER"

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-12-11 Cont ID  
Sent By adarroug Date 2008-12-11 Time 10:46 Rev Time 0.00
Received By adarroug Date 2008-12-11 Time 10:46 Sent To E
Notes
2008-12-11 10:47:08TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-11-06 Cont ID  
Sent By adarroug Date 2008-11-06 Time 16:31 Rev Time 0.00
Received By adarroug Date 2008-11-06 Time 16:31 Sent To E
Notes
2008-11-06 16:31:57TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-15 Cont ID  
Sent By adarroug Date 2008-09-15 Time 14:43 Rev Time 0.00
Received By adarroug Date 2008-09-15 Time 14:43 Sent To E
Notes
2008-09-15 14:44:07TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 16:11 Rev Time 0.00
Received By tgordon Date 2008-08-26 Time 16:11 Sent To E
Notes
2008-08-26 16:11:53TO "ELECT" D.P.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-07-22 Cont ID  
Sent By adarroug Date 2008-07-22 Time 10:49 Rev Time 0.00
Received By adarroug Date 2008-07-22 Time 10:49 Sent To E
Notes
2008-07-22 10:50:04TO "BTROBAUG" DESK/RESUB

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-08-05 Cont ID  
Sent By rregueir Date 2009-08-05 Time 17:58 Rev Time 0.00
Received By rregueir Date 2009-08-05 Time 17:57 Sent To PC
Notes
2009-08-05 17:58:17MECH "AS-BUILT' PLANS DATED 7/22/09

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-03-25 Cont ID  
Sent By rregueir Date 2009-03-25 Time 15:47 Rev Time 0.00
Received By rregueir Date 2009-03-25 Time 15:47 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2009-01-20 Cont ID  
Sent By rregueir Date 2009-01-20 Time 08:07 Rev Time 0.00
Received By rregueir Date 2009-01-20 Time 08:07 Sent To  
Notes
2009-01-20 08:11:14NO CHANGES T PREVIOUSLY PASSED MECH PLANS. NO NEW
 EQUIPMENT SHOWN ON PLANS. ONE DISCONNECT FOR NEW
 EQUIPMENT MISTAKENLY IDENTIFIED AS "EXISTING," TO BE
 CORRECTED ON ELECTRICAL PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-08-07 Cont ID  
Sent By rregueir Date 2008-08-07 Time 13:58 Rev Time 0.00
Received By rregueir Date 2008-08-07 Time 13:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-30 Cont ID  
Sent By rregueir Date 2008-06-30 Time 14:39 Rev Time 0.00
Received By rregueir Date 2008-06-30 Time 14:39 Sent To E
Notes
2008-06-30 14:40:31PLANS OK. NEEDS CHANGE TO MECH PERMIT TYPE. NEEDS MECH
 OR A/C CONTRACTOR AS PRIME CONTRACTOR WITH BUILDING AND
 ELECTRICAL AS SUBS. WILL REMIAN IN FAILED STATUS
 PENDING CORRECTED CONTRACTOR INFO.

Review Stop Z ZONING
Rev No 2 Status N Date 2009-02-19 Cont ID  
Sent By mflis Date 2009-02-19 Time 15:40 Rev Time 0.00
Received By mflis Date 2009-02-19 Time 15:40 Sent To  
Notes
2009-02-19 15:41:22ZONING REVIEW: NOT REQUIRED
  
 * INTERIOR REVISIONS ONLY
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status N Date 2008-07-01 Cont ID  
Sent By lmartine Date 2008-07-01 Time 14:25 Rev Time 0.00
Received By lmartine Date 2008-07-01 Time 14:25 Sent To  
Notes
2008-07-01 14:26:40REVIEW NOT REQUIRED PER MATT FLISS