Plan Review Details - Permit 08060091
Plan Review Stops For Permit 08060091
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-07-17 Cont ID  
Sent By mjacobs Date 2008-07-17 Time 09:48 Rev Time 0.00
Received By mjacobs Date 2008-07-17 Time 08:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-12 Cont ID  
Sent By mjacobs Date 2008-06-12 Time 15:45 Rev Time 0.00
Received By mjacobs Date 2008-06-12 Time 08:45 Sent To  
Notes
2008-06-12 15:45:22BUILDING PLAN REVIEW
 PERMIT: 08060091
 ADD: 1701 S. FLAGLER DR. #1802
 CONT: PROJECT ONE INTERIORS INC.
 TEL: (561)541-4555
 FL BLD CODE= 2004 FLORIDA BUILDING CODES. FLAGLER DR.
 #1802
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 4)PROVIDE A WALL DETAIL FOR THE NEW WALLS. THE DETAIL
 SHALL INCLUDE THE STUD SPACING, THE TYPE OF STUDS METAL
 OR WOOD AND THE TYPE OF DRYWALL OR SURFACE FINISH.
 ADDITIONAL INFORMATION REQUIRED 106.1.2*
  
 5)DUE TO THE FACT THAT THIS IS A HIGH-RISE BUILDING
 THE DESIGN PRESSURES FOR THE SLIDING GLASS DOOR SHALL
 BE DESIGN PER ASCE 7 AND CALCULATED BY A REGISTERED
 PROFESSIONAL FBC 1609.1.1. THE PRODUCT APPROVAL SHALL
 INDICATE BY CIRCLING OR HI-LIGHT THE TYPE OF GLASS AND
 THE DESIGN PRESSURES FOR THE NEW DOOR FROM THE TABLES
 PROVIDED IN THE INSTALLATION REPORT. PLEASE CHECK THE
 PRODUCT APPROVAL AND MAKE SURE THE DOOR CAN BE USED AT
 THIS LOCATION. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION AND NATURE
 AND EXTENT OF THE WORK PROPOSED 106.1.1
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-08-21 Cont ID  
Sent By btrobaug Date 2008-08-21 Time 08:38 Rev Time 0.00
Received By btrobaug Date 2008-08-18 Time 14:16 Sent To PC
Notes
2008-08-18 14:20:46 

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-06-11 Cont ID  
Sent By btrobaug Date 2008-06-11 Time 15:58 Rev Time 0.00
Received By btrobaug Date 2008-06-11 Time 15:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-07-21 Cont ID  
Sent By mwennerg Date 2008-07-21 Time 15:58 Rev Time 0.00
Received By mwennerg Date 2008-07-21 Time 15:58 Sent To  
Notes
2008-07-21 16:06:24PLANS ROUTED TO L. MARTINEZ FOR PROCESSING

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-16 Cont ID  
Sent By mawillia Date 2008-06-16 Time 11:02 Rev Time 0.00
Received By mawillia Date 2008-06-16 Time 10:43 Sent To  
Notes
2008-06-16 11:02:07*****UNSAT*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 ACCESS TO / EGRESS FROM THE OTHER UNITS ON THE SAID
 FLOOR OR THE BUILDING.
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6.SHOW AND/OR EXPLAIN HOW THE FIRE SPRINKLER HEADS
 AND SMOKE ALARMS WITHIN THE DWELLING UNIT WILL BE
 IMPACTED AS A RESULT OF THE REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-12 Cont ID  
Sent By adarroug Date 2008-08-12 Time 16:35 Rev Time 0.00
Received By adarroug Date 2008-08-12 Time 16:35 Sent To E
Notes
2008-08-12 16:35:37TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-03 Cont ID  
Sent By adarroug Date 2008-07-03 Time 08:41 Rev Time 0.00
Received By adarroug Date 2008-07-03 Time 08:41 Sent To  
Notes
2008-07-09 10:09:11TO "BOB"#5
2008-07-03 08:42:31WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-16 Cont ID  
Sent By mperson Date 2008-06-16 Time 16:08 Rev Time 0.00
Received By mperson Date 2008-06-05 Time 09:18 Sent To PC
Notes
2008-06-05 09:21:27TO "BOB"#1

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-07-10 Cont ID  
Sent By mperson Date 2008-07-10 Time 10:49 Rev Time 0.00
Received By mperson Date 2008-07-10 Time 10:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-06-16 Cont ID  
Sent By mperson Date 2008-06-16 Time 16:02 Rev Time 0.00
Received By mperson Date 2008-06-16 Time 16:02 Sent To I
Notes
2008-06-16 16:08:35PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. DECLARE THE GOVERNING CODE CYCLE. (FBC-2004 WITH
 2007 REVISIONS) PER (W.P.B. AS AMENDED) SECTION 106.5
 RETENTION OF CONSTRUCTION DOCUMENTS.
  
 2. DECLARE LEVEL OF ALTERATION. PER FBC-2004 EXISTING
 BUILDING CHAPTER 3.
  
 3. CLEARLY INDICATE IF THE KITCHEN SINK W/FAUCET WILL
 BE REPLACED WITH A NEW ONE OR IF THE EXISTING KITCHEN
 SINK W/FAUCET IS BEING REUSED. PER FBC-2004 PLUMBING
 SECTION 401.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-06-06 Cont ID  
Sent By choops Date 2008-06-06 Time 13:37 Rev Time 0.00
Received By choops Date 2008-06-06 Time 13:37 Sent To  
Notes
2008-06-06 13:38:08*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.