Plan Review Details - Permit 08060082
Plan Review Stops For Permit 08060082
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-08-12 Cont ID  
Sent By shill Date 2008-08-12 Time 08:24 Rev Time 0.00
Received By shill Date 2008-08-12 Time 08:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-07-16 Cont ID  
Sent By shill Date 2008-07-16 Time 11:12 Rev Time 0.00
Received By shill Date 2008-07-16 Time 11:12 Sent To  
Notes
2008-07-16 11:42:28****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.A PRESTORM PREPARATION PLAN WAS SUBMITTED.THE
 AMENDMENT PREPARED BY ALL AMERICAN ALUMINUM & SCREEN
 STATES THAT THE SHUTTERS WILL BE INSTALLED WITHIN 2
 DAYS OF HURRICANE WARNINGS.PLEASE SEE THE DEFINITIONS
 FOR HURRICANE WARNING AND HURRICANE WATCH FROM THE NOAA
 WEBSITE:
  
 HURRICANE WARNING:
 A WARNING THAT SUSTAINED WINDS 64 KT (74 MPH OR 119
 KM/HR) OR HIGHER ASSOCIATED WITH A HURRICANE ARE
 EXPECTED IN A SPECIFIED COASTAL AREA IN 24 HOURS OR
 LESS. A HURRICANE WARNING CAN REMAIN IN EFFECT WHEN
 DANGEROUSLY HIGH WATER OR A COMBINATION OF DANGEROUSLY
 HIGH WATER AND EXCEPTIONALLY HIGH WAVES CONTINUE, EVEN
 THOUGH WINDS MAY BE LESS THAN HURRICANE FORCE.
  
 HURRICANE WATCH:
 AN ANNOUNCEMENT FOR SPECIFIC COASTAL AREAS THAT
 HURRICANE CONDITIONS ARE POSSIBLE WITHIN 36 HOURS.
  
 BASED ON THE WAY THE PLAN IS WRITTEN, SHUTTERS WILL BE
 INSTALLED TWO DAYS AFTER HURRICANE WARNING.THIS WOULD
 BE A DAY AFTER THE STORM HAS HIT.NOTE THE THE POLICY,
 SEE ITEM 13, ATTACHED, REQUIRES SHUTTERS TO BE
 INSTALLED WITHIN 12 HOURS OF A HURRICANE WATCH.THE
 PRESTORM PREPARATION PLAN MUST MEET OR EXCEED THIS
 REQUIREMENT.
  
 PLEASE NOTE THAT THE PRESTORM PREPARATION PLAN CAN BE
 SUBMITTED VIA EMAIL FOR PRELIMINARY REVIEW.THE PLANS
 WILL BE HELD AT THE FRONT COUNTER PENDING RECEIPT AND
 APPROVAL OF PLAN.ORIGINALS SIGNATURES WILL BE
 REQUIRED AT TIME OF PERMIT PICKUP.PLEASE CONTACT ME
 IF YOU NEED ASSISTANCE REGARDING THIS PROCESS.
  
 AS DISCUSSED WITH EVE, THE AMENDMENT AND PAGE 2 OF THE
 MANUAL SHOULD BE REVISED TO REFLECT THE CORRECT TIME
 FRAME.THE MANUAL STATES THAT THEY WILL MEET "AS SOON
 AS POSSIBLE" AFTER HURRICANE WATCH.THE SHUTTERS ARE
 TO BE INSTALLED WITHIN 12 HOURS OF THE OFFICIAL
 HURRICANE WATCH.
  
 IN THE AMENDMENT (ALL AMERICAN), PLEASE STATE HOW MANY
 PEOPLE AND HOW LONG IS REQUIRED FOR THIS INSTALLATION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-25 Cont ID  
Sent By shill Date 2008-06-25 Time 15:45 Rev Time 0.00
Received By shill Date 2008-06-25 Time 15:45 Sent To  
Notes
2008-06-25 15:49:04****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.ADDRESSED.
  
 2.PHOTOCOPIES OF ENGINEERING WAS SUBMITTED (DESIGN
 PRESSURE REQUIREMENTS).ORIGINALS ARE REQUIRED WHEN
 SUBMITTED FOR PUBLIC RECORD, FS471, BUT PLEASE NOTE
 THAT ENGINEERING FOR BUILDINGS UNDER 60FEET IS NOT
 REQUIRED.
  
 NEW COMMENTS:
  
 3.MY APOLOGIES, BUT I DID NOT REALIZE THAT THIS WAS A
 COMMERCIAL JOB.PLEASE SEE ATTACHED POLICY REGARDING
 INSTALLATION OF REMOVABLE PANELS ON COMMERCIAL
 BUILDINGS, ESPECIALLY ON THE SECOND FLOOR.THIS MUST
 BE APPROVED BY THE BUILDING OFFICIAL.PLEASE SUBMIT A
 PRE STORM PREPARATION PLAN (SEE ITEM 13, HIGHLIGHTED).
 THIS MAY BE SUBMITTED VIA EMAIL FOR REVIEW.
 [email protected]
  
 4.PLEASE CLARIFY; ARE ALL PANELS TO BE INSTALLED ON
 THE SECOND FLOOR?WHEN SUBMITTING THE PLAN, PLEASE
 STATE WHAT EQUIPMENT WILL BE USED, WHERE THIS EQUIPMENT
 WILL BE STORED.IF ANY OPENINGS ARE ON THE FIRST
 FLOOR, PLEASE SHOW ALL REQUIRED EXITS.
  
 5.WHERE WILL THE PANELS BE STORED?THE PLAN SHOULD
 INCLUDE THIS INFORMATION.WILL THEY BE INSTALLED
 VERTICALLY OR STACKED ON THE FLOOR?IF STORED
 VERTICALLY, A DETAIL SHOWING HOW THEY WILL BE SECURED
 WILL BE REQUIRED.IF STORED ON THE GROUND, THE PLAN
 SHOULD INCLUDE DIMENSIONS OF THE STORAGE AREA SHOWING
 THAT IT IS LARGE ENOUGH TO ACCOMODATE THE PANELS STORED
 IN THIS MANNER.
  
 6.PLEASE READ ITEM 13 CAREFULLY AND ADDRESS ALL
 INFORMATION WHICH IS REQUIRED (NOT ONLY ITEMS 4 AND 5
 ABOVE).AN ORIGINAL SIGNED BY THE OWNER WILL BE
 REQUIRED BUT A PRELIMINARY REVIEW CAN BE DONE BY
 EMAIL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-11 Cont ID  
Sent By shill Date 2008-06-11 Time 10:14 Rev Time 0.00
Received By shill Date 2008-06-11 Time 10:14 Sent To  
Notes
2008-06-11 10:18:28****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE SHEET 1 OF THE PRODUCT APPROVAL DRAWINGS.THIS
 PRODUCT IS LIMITED TO 113X61, OPENING 7 IS 121X73.
  
 2.PHOTOCOPIES OF ENGINEERING WAS SUBMITTED (DESIGN
 PRESSURE REQUIREMENTS).ORIGINALS ARE REQUIRED WHEN
 SUBMITTED FOR PUBLIC RECORD, FS471, BUT PLEASE NOTE
 THAT ENGINEERING FOR BUILDINGS UNDER 60FEET IS NOT
 REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-09 Cont ID  
Sent By adarroug Date 2008-07-09 Time 17:03 Rev Time 0.00
Received By adarroug Date 2008-07-09 Time 17:03 Sent To B
Notes
2008-07-09 17:03:41TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-19 Cont ID  
Sent By adarroug Date 2008-06-19 Time 11:53 Rev Time 0.00
Received By adarroug Date 2008-06-19 Time 11:53 Sent To B
Notes
2008-06-19 11:53:21TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-11 Cont ID  
Sent By shill Date 2008-06-11 Time 10:18 Rev Time 0.00
Received By shill Date 2008-06-05 Time 08:50 Sent To  
Notes
2008-06-05 08:50:50TO "MISC" BOX#1