Plan Review Details - Permit 08060067
Plan Review Stops For Permit 08060067
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-10-01 Cont ID  
Sent By shill Date 2008-10-01 Time 11:54 Rev Time 0.00
Received By shill Date 2008-10-01 Time 11:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-09-02 Cont ID  
Sent By shill Date 2008-09-02 Time 15:24 Rev Time 0.00
Received By shill Date 2008-09-02 Time 15:24 Sent To  
Notes
2008-09-02 15:26:10****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
  
 1. SEE FIRST CORRECTION LIST. SHEET 11, ANCHOR SPACING
 OF 2 1/2" REQUIRES A FACTOR OF .66. TWO SETS REQUIRED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-10 Cont ID  
Sent By shill Date 2008-06-10 Time 15:35 Rev Time 0.00
Received By shill Date 2008-06-10 Time 15:35 Sent To  
Notes
2008-06-10 15:38:52****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. DESIGN PRESSURES FOR BUILDINGS OVER 60FEET ARE
 REQUIRED TO BE DESIGNED USING ASCE7, FBC1609.1.1 AND
 MUST BE DONE BY A DESIGN PROFESSIONAL. DOCUMENTS
 PREPARED BY AN ARCHITECT OR ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15, FAC61G1 16.
  
 ENGINEERING IS REQUIRED AS DISCUSSED.PLEASE NOTE THAT
 YOUR COMPUTERIZED ENGINEERING (WHICH IS NOT THE SAME AS
 CERTIFICATION BY A PE) WAS GENERATED FOR A BUILDING
 HEIGHT OF 60, BUT THIS BUILDING IS 200FEET TALL.THE
 UNIT'S LOCATION AFFECTS POSITIVE PRESSURE BUT NOT THE
 NEGATIVE PRESSURES.I BELIEVE THAT I HAD A TELEPHONE
 CONVERSATION WITH YOU AND STATED THAT IF YOU USED A
 VERY CONSERVATIVE DESIGN PRESSURE, SUCH AS -100PSF,
 THEN NO ENGINEERING WOULD BE REQUIRED.YOU HAVE
 DESIGNED TO -60PSF; THIS IS NOT WHAT I WOULD CONSIDER
 "VERY CONSERVATIVE"; THEREFORE, ENGINEERING IS
 REQUIRED.
  
 2.PROVIDE A COPY OF THE CONDO ASSOCIATION APPROVAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-04 Cont ID  
Sent By shill Date 2008-06-04 Time 14:03 Rev Time 0.00
Received By shill Date 2008-06-04 Time 14:03 Sent To  
Notes
2008-06-04 14:03:53****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
  
 1. DESIGN PRESSURES FOR BUILDINGS OVER 60FEET ARE
 REQUIRED TO BE DESIGNED USING ASCE7, FBC1609.1.1 AND
 MUST BE DONE BY A DESIGN PROFESSIONAL. DOCUMENTS
 PREPARED BY AN ARCHITECT OR ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15, FAC61G1 16.
  
 2.PROVIDE A COPY OF THE CONDO ASSOCIATION APPROVAL.
  
  
 3. TWO COMPLETE COLLATED SETS OF PERMIT DOCUMENTS
 REQUIRED.
  
 4.SEE SHEET 11. EDGE DISTANCE OF 2 1/2" REQUIRES A
 FACTOR OF .66.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-27 Cont ID  
Sent By tgordon Date 2008-08-27 Time 09:37 Rev Time 0.00
Received By tgordon Date 2008-08-27 Time 09:37 Sent To B
Notes
2008-08-27 09:38:32TO "BUILD" SAMANTHA H.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-04 Cont ID  
Sent By shill Date 2008-06-04 Time 14:04 Rev Time 0.00
Received By shill Date 2008-06-04 Time 14:04 Sent To  
Notes
***NONE***