Plan Review Details - Permit 08060015
Plan Review Stops For Permit 08060015
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-01-09 Cont ID  
Sent By btrobaug Date 2009-01-09 Time 14:28 Rev Time 0.00
Received By btrobaug Date 2009-01-09 Time 14:21 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-12-19 Cont ID  
Sent By btrobaug Date 2008-12-19 Time 12:21 Rev Time 0.00
Received By btrobaug Date 2008-12-19 Time 12:12 Sent To PC
Notes
2008-12-19 12:21:47 
  
 PER 308.2 AND 308.3 FBC FOR 5 OR FEWER PERSONS THIS
 OCCUPANCY IS R-3 THEREFORE PROVISIONS OF 313.1.1 FOR
 SMOKE ALARMS IS REQUIRED. PROVISO ON PLAN./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-10 Cont ID  
Sent By btrobaug Date 2008-12-10 Time 16:30 Rev Time 0.00
Received By btrobaug Date 2008-12-10 Time 15:43 Sent To FIRE
Notes
2008-12-10 16:30:11 
  
 SENT TO FIRE PER CAPTAIN WILLIAMS./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-08-06 Cont ID  
Sent By btrobaug Date 2008-08-06 Time 12:04 Rev Time 0.00
Received By btrobaug Date 2008-08-06 Time 10:51 Sent To PC
Notes
2008-08-06 11:51:42 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC CHAPTER 1 AS AMENDED AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
  
 1} THE REFERENCE TO NFPA72. 1-5.2.6 IN THE BATTERY
 CALCULATION, SHEET FA-1, IS INCORRECT. PER NFPA-72,
 2002 (REFERENCED STANDARD FBC, RFBC), THE FOLLOWING
 SHOULD BE REFERENCED.
  
 11.6.2 HOUSEHOLD FIRE ALARM SYSTEMS. POWER FOR
 HOUSEHOLD FIRE ALARM SYSTEMS SHALL COMPLY WITH THE
 FOLLOWING REQUIREMENTS:
 (1) HOUSEHOLD FIRE ALARM SYSTEMS SHALL HAVE TWO
 INDEPENDENT POWER SOURCES CONSISTING OF A PRIMARY
 SOURCE THAT USES COMMERCIAL LIGHT AND POWER AND A
 SECONDARY SOURCE THAT CONSISTS OF A RECHARGEABLE
 BATTERY.
 (2) THE SECONDARY SOURCE SHALL BE CAPABLE OF OPERATING
 THE SYSTEM FOR AT LEAST 24 HOURS IN THE NORMAL
 CONDITION FOLLOWED BY 4 MINUTES OF ALARM.
 (3) LOW-POWER WIRELESS SYSTEMS SHALL COMPLY WITH THE
 PERFORMANCE CRITERIA OF SECTION6.16.
  
 2} 11.8.3.5 SPECIFIC LOCATION REQUIREMENTS. THE
 INSTALLATION OF SMOKE ALARMS AND SMOKE DETECTORS SHALL
 COMPLY WITH THE FOLLOWING REQUIREMENTS:
  
 (5) SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN A 914-MM (36-IN.) HORIZONTAL PATH FROM
 A DOOR TO A KITCHEN OR A BATHROOM CONTAINING A SHOWER
 OR TUB.
  
 3} IDENTIFY THE MANUFACTURER'S NAME AND MODEL NUMBER OF
 THE BATTERY TO BE USED , ON THE BATTERY CALCULATIONS.
 106.1.1FBC.
  
 4} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 NOTE: THE OWNER BUILDER DISCLOSURE STATEMENT SUBMITTED
 WITH THE PLANS IS NOT APPLICABLE AS A LICENSED
 CONTRACTOR FILED THE APPLICATION. PLEASE BE ADVISED
 THAT AN OWNER/ BUILDER WOULD NOT BE ALLOWED TO APPLY
 FOR THIS WORK AS THE EXCEPTION IN489.103.7(B) IS NOT
 MET BECAUSE THE PROPERTY IS OWNED BY A CORPORATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-01-12 Cont ID  
Sent By mawillia Date 2009-01-12 Time 15:03 Rev Time 0.00
Received By mawillia Date 2009-01-12 Time 14:21 Sent To  
Notes
2009-01-12 14:38:44*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED. SINGLE PLAN SHEET FA1.01 STAMPED, INITIALED,
 AND DATED; READY FOR PERMIT ISSUANCE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-12-18 Cont ID  
Sent By mawillia Date 2008-12-18 Time 15:58 Rev Time 0.00
Received By mawillia Date 2008-12-18 Time 14:07 Sent To E
Notes
2008-12-18 15:55:54*****UNSAT*****
  
 PLEASE BE ADVISED THAT THE FIRE REVIEW WAS BASED UPON
 NFPA 101 - LIFE SAFETY CODE - 2003 EDITION, CHAPTER 32
 (NEW RESIDENTIAL BOARD AND CARE FACILITIES) SECTION 2
 (SMALL FACILITIES - THAT IS, SLEEPING ACCOMODATIONS FOR
 NOT MORE THAN 16 RESIDENTS)
  
  
 1. THE ALARM SYSTEM LAYOUT APPEARS TO BE MORE
 APPROPIATE FOR A LARGE FACILITY. PLEASE VERIFY AND/OR
 EXPLAIN.
  
 2. IN THE FIRE ALARM SYMBOL LEGEND, REGARDING THE SMOKE
 DETECTORS, IT INDICATES TO SEE ELECTRIC NOTES. NO SUCH
 ELECTRICAL NOTES COULD BE FOUND.
  
 3. PLEASE REFERENCE NFPA 101 (LIFE SAFETY CODE)
 32.2.3.4.3 SMOKE ALARMS
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-17 Cont ID  
Sent By mawillia Date 2008-06-17 Time 12:14 Rev Time 0.00
Received By mawillia Date 2008-06-17 Time 12:04 Sent To  
Notes
2008-06-17 12:08:42*****NO REVIEW AT THIS TIME*****
  
 NO FIRE REVIEW TO BE CONDUCTED AT 226 ALHAMBRA PLACE
 UNTIL THE CHANGE OF OCCUPANCY ISSUE HAS BEEN
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-07 Cont ID  
Sent By adarroug Date 2009-01-07 Time 13:51 Rev Time 0.00
Received By adarroug Date 2009-01-07 Time 13:51 Sent To E
Notes
2009-01-07 13:51:34TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-10 Cont ID  
Sent By adarroug Date 2008-12-10 Time 11:10 Rev Time 0.00
Received By adarroug Date 2008-12-10 Time 11:09 Sent To E
Notes
2008-12-10 11:10:24TO " BTROBAUG" DESK/RESUB