| 2008-05-30 14:23:19 | RESIDENTIAL (R3) RE-ROOFING BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1-VALUE OF STRUCTURE IS OVER $300,000, THEREFORE NEED |
| | TO COMPLY WITH THE STRENGTHENINGRETROFIT REQUIREMENTS |
| | REQUIRED BY FLORIDA STATES SEC. 553.844.CONTRACTOR |
| | NEEDSTO SPECIFYHOW COMPLYING WITH THIS SECTION. SEE |
| | ATTACHED COPY OF RULE 9B-3.0475. |
| | STRUCTURAL WORK REQUIRES SEPARATE BUILDING PERMIT. |
| | |
| | 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTES. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL FOR POLYFOAM TO BE USED AS |
| | REQUIRED BY DCA RULE 9B-72.SEE ROOF TILE PRODUCT |
| | APPROVAL FOR TYPE OF POLYFOAM LISTED. |
| | |
| | 4- FLAT ROOF PRODUCT APPROVAL SUBMITTED: |
| | A)THERE ARE TWO DIFFERENT BASE SHEET FASTENING |
| | OPTIONSSHOWN ON SELECTED ASSEMBLY.CLEARLY MARK |
| | WHICH FASTENING OPTION IS GOING TO BE USED FOR APPROVED |
| | ASSEMBLY SHOWN ON SHEET 16 OF 18 OF NOA 07-0730.03 |
| | SUBMITTED. |
| | |
| | B) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING |
| | AT PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL |
| | LIMITATION #7. |
| | ***NOTE:FOR RAS 117 CALCULATIONS KEEP IN MIND THAT |
| | HOUSE IS LOCATED ON EXPOSURE "C" AS REQUIRED BY SEC. |
| | R301.2.1.4(3) OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |