Plan Review Details - Permit 08050812
Plan Review Stops For Permit 08050812
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-06-09 Cont ID  
Sent By rmcdouga Date 2008-06-09 Time 08:37 Rev Time 0.00
Received By rmcdouga Date 2008-06-09 Time 08:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-04 Cont ID  
Sent By rmcdouga Date 2008-06-04 Time 07:20 Rev Time 0.00
Received By rmcdouga Date 2008-06-04 Time 07:20 Sent To  
Notes
2008-06-04 07:35:072004 FBC W/2007 REVISIONS
 INSTALL NEW WINDOWS AND SHUTTERS
  
 DENIED BY BUILDING
  
 1) THE NOA SUBMITTED FOR THE TRACO 2100 WINDOWS IS
 EXPIRED. PLEASE SUBMIT A CURRENT NOA FOR THE WINDOWS.
 DCA RULE 9B-72.
  
 2) THE NEGATIVE WIND LOAD PRESSURE FOR THE 37 X 50
 WINDOW IS SPECIFIED ON THE PLANS AS -55.81 PSF. THE
 WINDOW THAT IS HIGHLITED ON THE NOA HAS A NEGATIVE
 DESIGN PRESSURE OF -54.12 FOR THIS WINDOW, WHICH IS TOO
 LOW. PLEASE CORRECT.
  
 3) THE STORM SHUTTER INSTALLATION SCHEDULE LISTS A
 SHUTTER SPAN OF 720" FOR OPENING W3, WHICH APPEARS TO
 BE INCORRECT. PLEASE REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-06 Cont ID  
Sent By adarroug Date 2008-06-06 Time 11:01 Rev Time 0.00
Received By adarroug Date 2008-06-06 Time 11:01 Sent To B
Notes
2008-06-06 11:02:13TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-04 Cont ID  
Sent By rmcdouga Date 2008-06-04 Time 07:20 Rev Time 0.00
Received By rmcdouga Date 2008-06-04 Time 07:20 Sent To  
Notes
***NONE***