Plan Review Details - Permit 08050796
Plan Review Stops For Permit 08050796
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-02 Cont ID  
Sent By mperson Date 2008-06-02 Time 10:44 Rev Time 0.00
Received By mperson Date 2008-05-30 Time 09:58 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-06-02 Cont ID  
Sent By mperson Date 2008-06-02 Time 09:58 Rev Time 0.00
Received By mperson Date 2008-06-02 Time 09:58 Sent To I
Notes
2008-06-02 10:44:27PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. FROM THE
 INFORMATION ON THE PERMIT APPLICATION IT APPEARS THAT
 THIS IS A LEVEL 2 ALTERATION AND THAT A BUILDING PERMIT
 IS ALSO REQUIRED.
 NOTE: THE PERMIT APPLIED FOR IS FOR PLUMBING ONLY.
  
 1. PER (W.P.B. AS AMENDED) SECTION 106.1 SUBMITTAL
 DOCUMENTS. CONSTRUCTION DOCUMENTS, SPECIAL INSPECTION
 AND STRUCTURAL OBSERVATION PROGRAMS, AND OTHER DATA
 SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH
 APPLICATION FOR A PERMIT.
 NOTE: ONLY ONE SET OF CONSTRUCTION DOCUMENTS WAS
 SUBMITTED.
  
 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 3. MORE INFORMATION IS REQUIRED DUE TO THE FACT THAT A
 PLUMBING PERMIT IS BEING APPLIED FOR. PLEASE PROVIDE
 THE FOLLOWING INFORMATION.
 IF THE NEW PROPOSED PLUMBING LAYOUT IS DIFFERENT FROM
 THE EXISTING PLEASE SUBMIT THE FOLLOWING ON SEPERATE
 DRAWINGS.
  
 A) EXISTING FLOOR PLAN LAYOUT OF RESIDENCE. PLEASE
 CLEARLY INDICATE WHICH FIXTURES ARE TO BE REMOVED OR
 REPLACED.
  
 B) NEW PROPOSED FLOOR PLAN LAYOUT OF RESIDENCE AND
 PLEASE FOLLOW WHAT IS REQUIRED IN COMMENT #4.
  
 4. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) (9) PLUMBING: PLEASE
 SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM
 INDICATING ALL WASTE, VENTS, TRAPS AND SIZES WITH
 CLEANOUT LOCATIONS.
  
 5. PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN
 THE INSTALLATION OR REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM (SHOWER), DEAD ENDS SHALL BE PROHIBITED. A
 PLUMBING PERMIT IS REQUIRED AND AN INSPECTION IS
 REQUIRED OF PLUMBING DEMO WORK PRIOR TO COVERING DEMO
 WORK WITH FINNISH WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 6. PER FS 713.13 (1) THRU (6): A NOTICE OF
 COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY
 COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE
 HWY., BEFORE A PERMIT CAN BE ISSUED. PER FS 713.13 (2):
 IF THE IMPROVEMENT DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS VOID AND OF
 NO FURTHER EFFECT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]