Plan Review Details - Permit 08050795
Plan Review Stops For Permit 08050795
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-07-30 Cont ID  
Sent By lursu Date 2008-07-30 Time 09:36 Rev Time 0.00
Received By lursu Date 2008-07-30 Time 09:36 Sent To  
Notes
2008-07-30 09:37:39THE SITE ADDRESS OF 706 8TH ST REMAINS AS IT IS FOR THE
 NEW STRUCTURE .
  
 QUESTIONS/COMMENTS:
 LACRAMIOARA URSU, MA ,GISP
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-07-21 Cont ID  
Sent By mjacobs Date 2008-07-21 Time 13:36 Rev Time 0.00
Received By mjacobs Date 2008-06-30 Time 07:04 Sent To PC
Notes
2008-07-02 10:21:53REVIEW IN PROGRESS.
  
 BUILDING PLAN REVIEW
 PERMIT: 08050795
 ADD: 706 8TH STREET
 CONT: YOUCHAK & YOUCHAK INC.
 TEL: (561)832-3800
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)WHAT IS THE CORRECT ADDRESS FOR THE PROJECT IS IT
 814 DIVISION AVE OR IS IT 706 8TH STREET. THE ADDRESS
 ON THE APPLICATION IS DIFFERENT FROM THE ONE ON THE
 DRAWINGS. CLARIFY. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED. 106.1.1.
  
 3) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS
 & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 4)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5)109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAIL TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 6)THE DRAWINGS INDICATE THE MAJORITY OF THE ROOMS FOR
 THIS BUILDING AS EDUCATIONAL ROOMS, BUT DID NOT CLEARLY
 INDICATE THE LEVEL OF EDUCATION. ARE THE EDUCATIONAL
 ROOMS USED FOR STUDENTS BELOW THE 12TH GRADE OR ABOVE?
 FBC 304 - 305 CLASSROOMS AND LABORATORIES FOR STUDENTS
 ABOVE THE 12TH GRADE LEVEL ARE CLASSIFIED IN GROUP B.
 THE AGE OF THE STUDENTS WHO WILL BE USING THIS FACILITY
 SHALL BE STATED ON THE PLANS FOR A BETTER UNDERSTANDING
 OF THE BUILDING USE. INFORMATIONAL: THERE IS NO VB
 (PROTECTED) BUILDING PER CH 6 AND TABLE 601. THE
 BUILDING CAN HAVE A FIRE SPRINKLER SYSTEM WHICH WILL
 MAKE IT A SPRINKLER BUILDING.
  
 7) SHEET 2 OF 4 ADA RAMP DETAIL SHOWS A 5? LANDING
 AT THE BOTTOM OF THE RAMP. FBC 11-4.8.4 (2) THE BOTTOM
 OF EACH RAMP SHALL NOT LESS THAN 72 INCHES OF STRAIGHT
 AND LEVEL CLEARANCE. THE PLANS SHOW 60 INCHES.
  
 8) 106.3.3* PRODUCT APPROVALS- 2004. THOSE PRODUCTS
 THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR (A) DOORS (B) WINDOWS (C) ROOF SYSTEM
 METAL AND BUILT-UP ROOF (D) STRUCTURAL CONNECTORS (E)
 FIXED LOUVERS (F) ROOF SCUTTLE (SEE ATTACHED
 INFORMATION). PROVIDE THE SPEC SHEETS FOR THE ?CORIAN?
 SOLID SURFACE SHEETS FOR THE BATHROOMS. SHEET A-5 AND
 A-6 MAKE REFERENCE TO SPRAY ON INSULATION; PROVIDE THE
 SPEC SHEETS SHOWING HOW THE R-19 VALUE WILL BE ACHIEVED
 WITH THE SPRAY ON INSULATION. THE PRODUCT APPROVAL FOR
 THE FLAT ROOM SHALL INDICATE THE FOLLOWING
 INFORMATION.
 1)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY:
 MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF
 EACH ROOF TYPE
  
 2)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE EVALUATION REPORT SUBMITTED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
  
 3)FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY
 YOU ARE USING.ALSO INDICATE WHICH FASTENER IF THE
 OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
  
 4)FOR THE FLAT DECK, SPECIFY THE ENHANCED FASTENING
 FOR CORNER AND PERIMETER ZONES.
  
 5)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.
  
 6)SEE PRODUCT LIMITATION #7.CALCULATIONS PREPARED
 BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  
  
 9)SHEET A-1 INDICATE THE TYPE OF WALL SEPARATING THE
 MAIN ELECTRICAL ROOM #111 AND THE SHOWER #110. THE
 DIMENSIONS FOR THE SHOWER CONTROLS SHALL BE INDICATED
 ON THE DETAIL DRAWING OF THE SHOWER SHEET A2 DETAIL ?
 SEE FBC 11-4.21.4 AND 11-4.21.5
  
 11)FBC 1802.6.PROVIDE THE ENGINEER SOIL REPORT IN
 ACCORDANCE WITH THIS SECTION OF THE CODE SHOWING THE
 REQUIREMENTS OF 1-9.
  
 12)SHEET A1 ROOM #112 THE KITCHEN, IS THIS A
 COMMERCIAL KITCHEN AND WILL GOODS BE SOLD FROM THIS
 KITCHEN? ADDITIONAL INFORMATION REQUIRED.
  
 13)1209.2 INDICATE THE ATTIC ACCESS ON THE PLANS. AN
 OPENING NOT LESS THAN 20 INCHES BY 30 INCHES SHALL BE
 PROVIDED TO ANY ATTIC AREA HAVING A CLEAR HEIGHT OF
 OVER 30 INCHES.
  
 14)FBC 1203.2ENCLOSED ATTICS AND ENCLOSED RAFTER
 SPACES FORMED WHERE CEILINGS ARE APPLIED DIRECTLYTO
 THE UNDER SIDE SHALL HAVE CROSS VENTILATION. PROVIDE
 THE NECESSARY INFORMATION MEETING THE REQUIREMENTS OF
 THIS SECTION. SHEET A-6 HAS LITTLE INFORMATION ON THE
 SCREEN VENT STRIP. THE STATEMENT REFERS TO A DETAIL BUT
 DOES NOT SAY WHICH PAGE THE DETAIL IS ON.
  
 14)1503.3.6 PROTECTION AGAINST DECAY & TERMITES.
 CONDENSATE LINES & ROOF DOWN SPOUTS SHALL DISCHARGE AT
 LEAST 1 FT. AWAY FROM THE STRUCTURE SIDEWALL, WHETHER
 BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR SPLASH
 BLOCKS. SHEET A-5 DETAIL #3 REFERS TO THE MEP SHEETS
 FOR ADDITIONAL INFORMATION WHICH CANNOT BE FOUND. SHOW
 ON THE DRAWINGS HOW THE DOWNSPOUTS WILL DISCHARGE THE
 WATER AWAY FROM THE BUILDING.
  
 15)SHEET A-3 SCUPPER DETAIL. INDICATE ON THE DETAIL
 DRAWING THE DISTANCE FROM THE FINISH ROOF TO THE BOTTOM
 OF THE OVERFLOW SCUPPER. OVERFLOW SCUPPERS SHALL BE
 PLACED IN WALLS OR PARAPETS NOT LESS THAN 2 INCHES NOR
 MORE THAN 4 INCHES ABOVE THE FINISHED ROOF COVERING.
 FBC 1503.4.3.
  
 16)2210.3 TRUSSES. THE DESIGN, QUALITY ASSURANCE,
 INSTALLATION AND TESTING OF COLD-FORMED STEEL TRUSSES
 SHALL BE IN ACCORDANCE WITH THE STANDARD FOR
 COLD-FORMED STEEL FRAMING?TRUSSES , AMERICAN IRON AND
 STEEL INSTITUTE, SUBJECT TO THE LIMITATIONS THEREIN.
 THE ENGINEER OF RECORD SHALL REVIEW AND APPROVE ALL
 SHOP DRAWINGS INCLUDING THE METAL TRUSSES PRIOR TO
 SUBMITTAL.
  
 17)SHEET A-6 INDICATES SPRAYING FIREPROOFING ON THE
 BEANS AND COLUMNS, WHAT WILL BE THE FIRE RATING AND
 THICKNESS OF THE FIREPROOFING TO ACHIEVE THE RATING?
  
 18)NOTE: 1013.2 AN EXIT ACCESS SHALL NOT PASS THROUGH
 A ROOM THAN CAN BE LOCKED TO PREVENT EGRESS. INDICATE
 THE TYPE OF LOCKS FOR THE EACH DOOR LOCATED IN THE PATH
 OF EGRESS TRAVEL. THIS INFORMATION CAN BE SHOWN ON THE
 DOOR SCHEDULE.
  
 19)SHEET A-3 PROVIDE A DETAIL SHOWING HOW THE FOAM
 CAP WILL BE FASTENS TO THE EXTERIOR OF THE BUILDING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-26 Cont ID  
Sent By dpalmer Date 2008-06-26 Time 12:36 Rev Time 0.00
Received By dpalmer Date 2008-06-25 Time 13:52 Sent To  
Notes
2008-06-26 12:36:56** DENIEDREVIEW **
  
 *** IT IS IMPORTANT TO UNDERSTAND AS SOME THINGS HAVE
 NOT YET BEEN SUBMITTED FOR MINIMUM CODE COMPLIANCE
 THERE MAY VERY WELL BE NEW COMMENTS ON THE NEXT REVIEW
 WHICH CAN NOT BE MADE AT THIS TIME.
  
 1)NOTE: PLEASE SEE THE ADDRESS ON PLANS AND
 SUPPORTING DOCUMENTS ARE STATING 814 DIVISION AVE YET
 THE APPLIED LOCATION IS 706 8TH ST. PLEASE ADJUST TITLE
 BLOCKS ON ALL PLANS AND ALL SUPPORTING DOCUMENTS.
 FBC 106.5 ADMIN SECTION.
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE SEE THE SUBMITTED SURVEY IS REQUIRED TO
 CONTAIN AN ORIGINAL SIGNATURE. PER FS 472.025 MAY NOT
 PLACE RAISED SEAL OVER RUBBER STAMP SIGNATURE.
 STATEMENT PER FAC 61G17 AND AS STATED ON THE TITLE
 BLOCK FOR SAME SAID SHEETS STATE THE SHEET IS NOT VALID
 WITHOUT ORIGINAL SIGNATURE.
 PLEASE ADJUST. THIS IS A FLORIDA STATUTE AND REQUIRED
 WHETHER OR NOT COMMENT IS MADE BY ANY OTHER REVIEWER.
  
 3) NOTE: PLEASE SEE THE LANDSCAPE PLANS ARE MISSING THE
 REQUIRED CERTIFICATION OF AUTHORIZATION NUMBER AS
 REQUIRED PER FS 481.219, FAC 61G1-16.004.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE REVIEW.
  
 4) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 DO NOT CONTAIN ANY ORIGINAL SIGNATURES. IN FACT BOTH
 COPIES SUBMITTED CONTAIN A RAISED SEAL OVER A COLOR
 PHOTO-COPIED SIGNATURE BY THE ENGINEER. PLEASE SEE FAC
 61G15-23.002 AND FS 471.025 AS AN ORIGINAL SIGNATURE IS
 REQUIRED ON ALL DOCUMENTS DONE BY THE ENGINEER. THIS
 COMMENT HAS BEEN MADE BEFORE FOR THIS DESIGNER OF
 RECORD. PLEASE KNOW BOTH SETS OF CALCULATIONS SUBMITTED
 ARE BEING RETAINED BY THIS OFFICE.
  
 5) NOTE: PLEASE KNOW THE SUBMITTED ENERGY CALCULATIONS
 ARE NOT COMPLETE. NO INPUT DATA REPORT WAS SUBMITTED.
 PAGE TWO OF NINE STATES THE INPUT DATA REPORT MUST BE
 SUBMITTED ALONG WITH THE SUMMARY SHEETS. IN ANY CASE
 PLEASE KNOW THAT SOME OF THE INFORMATION ON THE
 SUBMITTED CALCULATIONS DOES NOT MATCH WITH THE PLANS.
 AN EXAMPLE OF THIS IS THE LIGHTING IN THE SUMMARY WHICH
 SHOWS A TOTAL OF 574 WATTS OF LIGHTING. HOW IS THIS
 POSSIBLE WHEN THE WSA FIXTURES ALONE EXCEED THE
 574WATTS? THERE ARE SEVERAL OTHER FIXTURES ON PLANS
 WHICH ARE NOT ACCOUNTED FOR.
 PLEASE BE SURE ALL INFORMATION ON THE INPUT DATA
 REPORTS COORDINATES WITH PLANS. PLEASE BE SURE ALL
 INTERIOR LIGHTING SUCH AS THE WATTAGE OF FIXTURES, THE
 TYPES OF FIXTURES, THE METHOD OF CONTROLS AND THE
 NUMBER OF FIXTURES. THIS OFFICE CAN NOT EMPHASIZE
 ENOUGH THAT ALL INFORMATION ON PLANS FOR ALL COMPONENTS
 OF THE BUILDING WILL NEED TO COORDINATE WITH THE
 SUBMITTED CALCULATIONS. ONE EXAMPLE ABOVE WAS GIVEN
 WITH RESPECT TO THE EXTERIOR LIGHTING EVEN AS SHOWN ON
 THE SUMMARY SHEETS DID NOT COORDINATE WITH THE
 SUBMITTED PLANS.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-400.3.A AS SUBMITTED.
 ** PLEASE BE SURE TO SEE TRACK LIGHTING AS NOTED IN
 SECTIONS ABOVE.
 ** PLEASE BE SURE ALL LUMINAIRES SHOWN ON THE FIXTURE
 LEGEND AND ALL PLANS COORDINATE WITH THE TYPES. THERE
 WILL BE OTHER COMMENTS BELOW AS THERE ARE SEVERAL
 FIXTURES ON THE PLANS WHICH DO NOT APPEAR IN THE
 FIXTURE LEGEND.
 ** PLEASE BE SURE TO USE THE FIXTURE RATED OUTPUT
 WHETHER OR NOT IT IS INCANDESCENT, FLUORESCENT, OR HID
 ETC.
 ** PLEASE BE SURE TO SEE THE USE OF ANY LOW VOLTAGE
 SYSTEMS.
  
 6) NOTE: PLEASE SEE THE SUBMITTED CALCULATIONS STATE
 SCHOOL AS THE OCCUPANCY HOWEVER THE OCCUPANCY AS STATED
 BY THE ARCHITECT IS NOT EDUCATIONAL AND IN FACT IS
 STATED AS A3.
 PLEASE BE SURE THE *INDIVIDUAL* NOT THE FIRM IS LISTED
 AT THE PREPARER. THE CERTIFICATION SHEETS ARE SET UP
 FOR THE INDIVIDUAL CERTIFYING NOT A FIRM.
 PLEASE BE SURE TO ADJUST.
 13-415.2, 13-400.3.A, 13-103.1
  
 7) NOTE: PLEASE COORDINATE ALL ELECTRICAL PLANS. PLEASE
 SEE THE ELECTRICAL SITE PLANS SHOWN ON ES101 DO NOT
 MATCH WITH THE FIXTURES ETC ON ES102.
 PLEASE SEE OTHER SHEETS WHICH INDICATE SITE LIGHTING
 POLES YET THE ELECTRICAL SITE PLANS DO NOT INDICATE ANY
 SITE LIGHTING POLES.
 PLEASE SEE THE LUMINAIRE SCHEDULE ON ES 102 WHICH DOES
 NOT INCLUDE THE S32 FIXTURE AT ALL.
 PLEASE SEE TIME CLOCK SITE/EXTERIOR LIGHTING SCHEDULE
 WHICH ALSO INDICATES OTHER LIGHTING YET THE SITE PLANS
 ARE NOT COMPLETE AND DO NOT COORDINATE. THERE ARE
 SEVERAL ITEMS.
 NEC 220, 240,310,408 ETC
 FBC 13-415.2.ABC.1.3
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 8) NOTE: PLEASE BE SURE TO INDICATE THE REQUIRED
 ASTRONOMICAL TIME CLOCK AS REQUIRED PER
 13-415.1.ABC.1.4 WITH THE REQUIRED BACK UP OF
 PROGRAMMING.
  
 9) NOTE: PLEASE SEE THE TIME CLOCK SCHEDULE AS THE
 CIRCUITING SHOWN ON THIS SCHEDULE NEEDS TO COORDINATE
 WITH PLANS.
 PARKING LOT LTS, GAZEBO LTS ETC
 NEC 240, 220, 310.16
 FBC 13-415.2.ABC.1.3
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 10) NOTE: PLEASE SEE THERE ARE MISSING LIGHTING
 CONTROLS FOR 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE ONE EXAMPLE OF THIS IS THE STANDARD SINGLE
 POLE LIGHT SWITCH SHOWN FOR THE TRACK LIGHTS.
 THESE ARE ALSO REQUIRED TO BE CONTROLLED WITH SOME
 SORT OF AUTOMATED CONTROLS.
 ANOTHER EXAMPLE WOULD BE THE KITCHEN LIGHTING WHICH
 INDICATE STANDARD 3-WAY SWITCHES.
 ** SOME EXAMPLES ARE GIVEN ONLY. PLEASE BE SURE TO SEE
 OTHER COMMENTS WHICH MAY AFFECT LIGHTING AND CONTROLS.
 PLEASE BE SURE TO ADJUST SHOWING ALL MAXIMUM TIMES FOR
 ALL CONTROLS AND ALL DEVICES.
 MANY ARE OK, HOWEVER NOT ALL.
  
 11) NOTE: PLEASE SEE ANY ZONING COMMENTS WITH RESPECT
 TO THE AMOUNT OF LIGHTING PERMITTED OVER THE PROPERTY
 LINES. EVEN IF THERE HAVE BEEN NO COMMENTS FROM THE
 REVIEW PLEASE BE SURE TO CALL ZONING OFFICE TO VERIFY
 THE LIGHTING LEVELS OVER THE PROPERTY LINES. THIS IS
 NOTED FOR INFORMATION ONLY AND AS A BENEFIT SO THERE
 ARE NO ISSUES WITH FIXTURES AT A LATER DATE.
 SOME LEVELS APPEAR TO BE OVER THE ALLOWANCES IN SOME
 AREAS ONLY. THIS IS ONLY GIVEN FOR INFORMATION AND IS
 NOT AN ELECTRICAL REVIEW COMMENT WHICH NEEDS TO BE
 ADDRESSED. NO RESPONSE NEEDED.
  
 12) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL
 DESIGNATED EGRESS PATHS OUT FROM BUILDING. PLEASE BE
 SURE TO INCLUDE THE LIGHTING LEVELS UNDER NORMAL AND
 UNDER EMERGENCY CONDITIONS.
 PLEASE BE SURE TO SEENFPA-101 2003, 7.8.1.3 AND
 7.9.2.2 WHICH REQUIRES A MINIMUM OF 10FT CANDLESON
 ALL WALKING SURFACES OF STAIRS AND IS PERMITTED TO GO
 DOWN TO 1FT CANDLE UNDER EMERGENCY.
 PLEASE SEE 7.8.1.2.2 FOR TYPES OF OCCUPANCY SENSORS
 REQUIRED. THESE SHALL BE FAIL SAFE *ON*. THIS IS ALSO
 NOTED IN FBC 1016.1
  
 13) NOTE: AS NOTED ABOVE IN PREVIOUS NOTES WITH RESPECT
 TO FIXTURES AND COORDINATION AND NOTE #12 ABOVE PLEASE
 BE SURE TO COORDINATE ALL LIGHTING FIXTURES.
 PLEASE SEE MISSING SOME AS EXAMPLE: WS3E, B3E, WSA, TL1
 ETC
 PLEASE SEE FOR EXAMPLE MANY OF THE LIGHTING FIXTURES
 IN THE STAIRS AND OTHER LOCATIONS WHICH INDICATE AN *E*
 NEXT TO FIXTURE DESIGNATION. THIS FIXTURE IS NOT LISTED
 ON THE FIXTURE LEGEND WITH EMERGENCY BALLAST ETC.THE
 STAIR FIXTURES AND OTHER FIXTURES WHICH ARE ASSUMED TO
 CONTAIN BATTERY BACK UP BALLAST ARE IN NEED OF ALSO
 COORDINATING WITH THE PHOTO-METRICS TO BE SUBMITTED.
 NFPA-1017.8, 7.9
 FBC 13-415.2.ABC.1.1, .1.2
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 14) NOTE: PLEASE SEE THE MULTI-GANG BATHROOMS. THE
 PLANS INDICATE FOR LIGHTING CONTROLS A SINGLE POLE
 SWITCH DEVICE *AFTER* THEOCCUPANCY SENSING.
 PLEASE KNOW DUE TO THE LIFE SAFETY EGRESS SITUATION AS
 SHOWN THIS WOULD ALLOW AN OCCUPANT TO TURN OFF LIGHTING
 ON THE BATHROOMS WHILE AN OCCUPANT IS STILL IN ANY
 LOCATION THEREFORE LEAVING ANY ONE EGRESS AREA IN TOTAL
 DARKNESS.
 PLEASE ADJUST DESIGN SO THAT THIS DOES NOT OCCUR.
 NFPA-101 7.8, 13-415.1.ABC.1.2.
  
 15) NOTE: PLEASE SEE THAT MANY ROOMS AND AREAS OF THE
 PLANS HAVE DESIGNATIONS HOWEVER MANY AREAS OF THE PLANS
 IN FACT MOST ROOMS THE PRINT ON PLANS FOR THESE ROOMS
 AND AREAS ARE VERY FAINT AND NOT READABLE. THE REVIEW
 OF SEVERAL ITEMS FOR COORDINATION ON PLANS IS NEEDED
 AND PLEASE BE SURE TO ADJUST PRINT SO THESE CAN BE
 READ.
 FBC ADMIN SECTION 106.1, 106.1.1, 106.1.3 FOR CLARITY.
  
 16) NOTE: PLEASE PROVIDE DISCONNECTING MEANS AT GAZEBO
 PER 225.31-225.39
  
 17) NOTE: PLEASE PROVIDE THE REQUIRED GROUNDING
 ELECTRODE AT GAZEBO PER 250.32, 250.50 OR MEET THE
 EXCEPTION OF THE CODE.
  
 18) NOTE: PLEASE BE SURE TO COMPLETE ALL CIRCUITING ON
 PLANS. PLEASE SEE FOR EXAMPLE THE STAIRS WHICH NO
 CIRCUITING IS SHOWN.
 PLEASE SEE 700.12F.
 PLEASE SEE THERE ARE OTHER ITEMS ON PLANS AS WELL WHICH
 DO NOT INDICATE CIRCUITS AND/OR DO NOT CORRELATE WITH
 THE SUBMITTED PANEL SCHEDULES.
 PLEASE BE SURE TO COORDINATE ALL.
 NEC 240.4, 310.16, 220, 408.4
 FBC 106.1.2, 106.1.1, 106.3.5.1.2 FOR MINIMUM
 INFORMATION REQUIRED AND CLARITY.
  
 19) NOTE: PLEASE BE SURE TO SUBMIT MINIMUM WIND LOAD
 CALCULATIONS FOR LIGHT POLES. THE STRUCTURAL DESIGN
 REVIEW WILL BE DONE BY THE STRUCTURAL REVIEWER.
 THIS MAY BE DONE AS A PROVISO HOWEVER NEEDS BASIC
 DESIGN ON PLANS FOR OTHER TRADES.
 ** (SHOWS 140MPH ON ELECTRICAL ONLY)
  
 20) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW PROPOSED MTS.
 NEC 110.3,90.7, 702.6
 FBC 106.1.2
  
 21) NOTE: PLEASE BE SURE THE MINIMUM LEVELS FOR HORNS,
 STROBES AND HORN/STROBES ARE ON PLANS FOR ADA
 COMPLIANCE PER FBC 11-4.28.1, .2 AND .3..
  
 22) NOTE: PLEASE SEE RISER WHICH SHOWS THE SERVICE MAIN
 DISCONNECT YET THE PLANS DO NOT SHOW THIS LOCATED ON
 THE OUTSIDE OF THE BUILDING ON SITE PLANS, POWER ETC.
 PLEASE BE SURE TO INCLUDE ON PLANS.
 230.70, 230.71, 230.72, 110.26, 240.24 ETC
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 23) NOTE: PLEASE SEE THE MAIN SERVICE DISCONNECT IS NOT
 RATED FOR THE SERVICE AS SHOWN. THE MAIN DISTRIBUTION
 PANEL IS SHOWN AS 1000AMPS, WITH A LOAD IN THE 900AMP
 RANGE YET THE SERVICE MAIN DISCONNECT IS SHOWN AT
 600AMPS.ALL EQUIPMENT SHALL BE RATED FOR THE LOAD
 SERVED.
 THIS IS NOT PERMITTED.
 230.70, 230.76, 230.79
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 24) NOTE: PLEASE SEE THE NOTE TO SEE THE GROUNDING
 ELECTRODE SYSTEM DETAILS FOR SERVICE NOTES TO SEE E201
 YET E201 DOES NOT CONTAIN ANY GROUNDING ELECTRODE
 SYSTEM DETAILS.
 ** CHECK SHEET NUMBERS.
  
 25) NOTE: PLEASE KNOW AS NOTED ABOVE FOR ENERGY
 CALCULATIONS. THE *FUTURE* LIGHT FIXTURE SHALL HAVE AN
 ASSUMPTION IN THE CALCULATIONS FOR ENERGY COMPLIANCE AS
 WELL AS ASSUMPTIONS IN THE LOAD CALCULATIONS.
 NEC 220.12, 220.42, FBC 13-415.2.ABC.1.1, .1.2 AND
 .1.3.
  
 26) NOTE:THE PLANS NOTES THE KITCHEN EQUIPMENT WILL
 NOT BE PART OF THE SCOPE HOWEVER WHAT ABOUT THE
 ELECTRICAL FOR WALLS ETC?
 PLEASE CLARIFY AS IF ANY RECEPTACLES ETC WILL BE
 INSTALLED BEFORE THE PROJECT IS ENDED MUST BE SHOWN IN
 CALCULATIONS, ON PLANS ETC.
 310.16, 240, 220, ETC
 FBC 106.1.1, 106.1.2, 106.3.5.1.2
  
 27) NOTE: PLEASE SEE 422.13 AS ANY STORAGE TYPE WATER
 HEATER IS CONSIDERED A*CONTINUOUS LOAD* UNDER THE 2005
 NEC. THIS REQUIRES THE LOAD TO BE SHOWN AND FIGURED AT
 125%.
  
 28) NOTE: PLEASE SEE THE PLANS ARE MISSING THE REQUIRED
 DEDICATE CIRCUITS FOR THE ELEVATOR EQUIPMENT ROOM. THE
 PLANS SHOW THE LIGHTING BEING CIRCUITED TO OTHER LIGHTS
 INSIDE THE BUILDING WHICH IS NOT PERMITTED PER
 620.23(A)(B).
 PLEASE ALSO INDICATE THAT THE MINIMUM LEVEL OF LIGHTING
 IN THE PIT MEETS THE 5FT CANDLES MINIMUM.
 ASME A17.1-2004, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX)
 AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE
 EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.
  
 29) NOTE: PLEASE SEE FBC 3006.2 AS DEDICATE AIR
 CONDITIONING IS REQUIRED IN THE ELEVATOR EQUIPMENT
 ROOMS. THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE
 BY OTHER TRADE REVIEWERS.
  
 30) NOTE: PLEASE SEE 620.23C AS THE ELEVATOR EQUIPMENT
 ROOM IS ALSO MISSING THE REQUIRED DEDICATE GFI
 RECEPTACLE. THIS MAY BE ONE THE SAME CIRCUIT AS THE
 LIGHTS IN THIS ROOM.
  
 31) NOTE: AS NOTED ABOVE WITH RESPECT TO ALL FIXTURES
 ON PLANS NEEDING TO COORDINATE WITH THE FIXTURE LEGEND.
 THE LIGHT FIXTURE SHOWN ON THE LIGHTING PLANS INDICATES
 THE LIGHT AS AN *T2E* FIXTURE YET THE LEGEND DOES NOT
 INCLUDE THIS.
 PLEASE BE SURE THE FIXTURE IN THE ELEVATOR EQUIPMENT
 ROOM CONTAINS SOME SORT OF BATTERY BACK UP LIGHT
 FIXTURE AS WELL AS OTHER ELECTRICAL ROOMS. IT IS
 ASSUMED THE *E* ON THE PLANS IS FOR AN EMERGENCY BACK
 UP BALLAST HOWEVER CAN NOT CONFIRM.
 NEC 700.12F, 700.16, LS 101, 7.8, 7.9
  
 32) NOTE: PLEASE BE SURE TO COORDINATE THE ELECTRICAL
 CONDUITS SHOWN ON ES101 AS THESE ARE SHOWN TO GO FROM
 THE FPL TRANSFORMER TO THE INSIDE ELECTRICAL ROOM AND
 NOT TO THE MAIN DISCONNECT AS SHOWN ON RISER. THIS WAS
 ALSO NOTED ON NOTE #22ABOVE WITH RESPECT TO SHOWING
 LOCATION.
 230.70, 300.5 ETC
 FBC 106.1.1 FOR CLARITY.
  
 33) NOTE: PLEASE SEE PANEL 2LA WHICH SHOWS ON RISER A
 40AMP FEED YET THE PANEL BASED ON THE PANEL SCHEDULE
 AND BASED ON THE LOADS EXCEEDS THIS OVER CURRENT
 PROTECTION. LOAD IS 70 PLUS AMPS.
 PLEASE SEE THAT ALL EQUIPMENT SHALL BE RATED FOR LOAD
 SERVED.
 PLEASE ALSO SEE AS BASED ON RISER THESE ARE SHOWN AS
 1/0 CONDUCTORS ON A 40AMP BREAKER.
 THIS SEEMS TO BE A MISPRINT OF OVER CURRENT PROTECTION
 NEED
 240, 408, 310, ETC
 PLEASE BE SURE TO SEE MDP SCHEDULE AS BREAKER IS SHOWN
 AS 125AMPS.
 FBC 106.1.1 FOR COORDINATION AND CLARITY
  
 34) NOTE: PLEASE SEE MDP SHOWS A PANEL 1KA YET RISER
 DOES NOT SHOW ANY 1KA PANEL.
 PLEASE SEE RISER SHOWS A1LK, YET NOT LISTED ON THE
 MDP. ARE THESE PANELS THE SAME BUT MISLABLED?
 408.4
 FBC 106.1.1.
  
 35) NOTE: PLEASE VERIFY THE LINEAR FT SHOWN ON THE
 PANELS FOR VOLTAGE DROP. IT IS UNCLEAR HOW THE TVSS
 BREAKERS ARE SHOWING 10816FT, AND OTHERS SHOWS 1082 FT
 AND 541 FT.
 PLEASE BE SURE TO SEE FBC 13-413.1.ABC.1.1 AND .1.2 AND
 PROVIDE ACTUAL WORST CASE VOLTAGE DROP.
  
 36) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2. PLEASE
 PROVIDE THE WORDING AS STATED IN THE FBC ON PLANS IN
 NOTES.
 THIS WAS CONFIRMED ON A STATE LEVEL THE INTENT OF THE
 CODE IS FOR THE PLANS CONTAIN THE WORDING AS STATED IN
 THE SECTIONS.
  
 37) NOTE: PLEASE COMPLETE CIRCUITS ON DETAIL 2 ON
 E301.
 408.4, 240.4, 310.16ETC
 FBC 106.1.1
  
 38) NOTE: PLEASE SEE E402 WHICH STATES THE FPL
 TRANSFORMER AS 225KVA YET THE SITE PLAN SHOWS 100KVA.
 PLEASE COORDINATE.
 FBC 106.1.1 FOR CLARITY OF PLANS.
  
 39) NOTE: PLEASE SEE THE ELEVATORCAB LIGHTS WHICH
 SHOWS 2-#8 AWG ON A 1-POLE 20AMP BREAKER. HOW IS THIS
 POSSIBLE?
 PLEASE SEE 430, 310.16, 240.4 ETC 110.3.
  
 40) NOTE: PLEASE SEE THE RISER AS THIS SHOWS A 125AMP
 BREAKER/OVER CURRENT PROTECTION FEEDING A 100AMP RATED
 DISCONNECT.
 110.3, 90.7 ETC
 FBC 106.1.1 FOR CLARITY.
  
 41) NOTE: PLEASE SEE RISER NOTES THE CONTRACTOR IS
 RESPONSIBLE TO OBTAIN THE ACTUAL AVAILABLE FAULT
 CURRENT AND MAKE ADJUSTMENTS.
 PLEASE KNOW THIS IS THE RESPONSIBILITY OF THE DESIGNER
 OF THE ELECTRICAL SYSTEM NOT THE CONTRACTOR FOR BASE
 DESIGN. THE CONTRACTOR MOST CERTAINLY WILL NEED TO
 VERIFY THE TRANSFORMER ETC FROM THE UTILITY IS
 INSTALLED BASED ON INFORMATION FROM THE UTILITY. ANY
 CHANGE IN THE ACTUAL SIZE, AND IMPEDANCE RATING OF THE
 UNIT WILL NEED TO BE GIVEN TO THE ENGINEER IN CASE ANY
 EQUIPMENT NEEDS TO BE ADJUSTED.
 PLEASE SEE 110.9 AND ADJUST NOTES.
 FAC 61G15-33.001, .003 FOR THE ENGINEER.
  
  
 42) NOTE: BASED ON THE TYPE OF COMMENTS AND THE AMOUNT
 OF COMMENTS ABOVE ONE SET OF ELECTRICAL PLANS ALONG
 WITH THE PARTIAL ENERGY CALCULATIONS MAY BE RETAINED BY
 THIS OFFICE.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-06-26 Cont ID  
Sent By rchokshi Date 2008-06-26 Time 14:09 Rev Time 0.00
Received By rchokshi Date 2008-06-26 Time 13:54 Sent To  
Notes
2008-06-26 14:09:14FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. PLEASE SHOW ON DRAWINGS THE TUBIDITY DETAILS OF
 POLLUTION PREVENTION FOR CATCH BASINS. THE TURBIDITY
 SHOULD BE AROUND EACH CATCH BASIN DURING CONSTRUCTION
 AND ALL DEMOLITION PHASE.HEIGHT OF TURBIDITY SHOULD
 BE HIGH ENOUGH PER FDEP.
  
 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 5. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 6. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 7. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE.
  
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT, ENVIRONMENTAL REPORT&STORM WATER QUALITY
 CALCULATIONS TO 100045TH STREET ENGINEERING SERVICES
 FOR THEIR APPROVAL BEFORE WE APPROVE.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-07-17 Cont ID  
Sent By mwennerg Date 2008-07-17 Time 16:06 Rev Time 0.00
Received By mwennerg Date 2008-07-17 Time 15:07 Sent To  
Notes
2008-07-17 16:06:01***DENIED***
  
 1) PLEASE VERIFY CORRECT ADDRESS. PLANS INDICATE 814
 DIVISION AVE. AND PERMIT APPLICATION SHOWS 706 8TH ST.
  
 2) FIRE DEPARTMENT CONNECTION TO BE PROVIDED WITH KNOX
 LOCKING CAPS. CONTACT WEST PALM BEACH BUREAU OF FIRE
 PREVENTION AT (561( 804-4724 FOR APPLICATION.
  
 3) KNOX BOX REQUIRED ON BUILDING FOR AFTER NORMAL
 BUSINESS HOURS ACCESS FOR EMERGENCIES. CONTACT WEST
 PALM BEACH BUREAU OF FIRE PREVENTION AT (561) 804-4724
 FOR APPLICATION.
  
 4) IN ADDITION TO ELECTRONIC SUPERVISION, DOUBLE CHECK
 DETECTOR ASSEMBLY TO BE SECURED WITH LOCK AND CHAIN.
  
 5) PLEASE ADD NFPA 13, 2002 AND NFPA 72, 2002 TO
 BUILDING CODE ANALYSIS ON SHEET LS-1.
  
 6) PROVIDE CALCULATION FOR TOTAL BUILDING OCCUPANT LOAD
 USING NFPA 101, TABLE 7.3.1.2.
  
 7) CLARIFY DETECTION DEVICES SHOWN ON SHEET LS-1. ARE
 DEVICES AREA SMOKE DETECTORS OR DUCT SMOKE DETECTORS AS
 INDICATED IN LS SYMBOL LEGEND? NONE OF THESE DEVICES
 ARE INDICATED ON FIRE ALARM DRAWINGS.
  
 8) SMOKE DETECTORS NOT SHOWN IN AREA OF FACP OR
 ELEVATOR LOBBY FIRST FLOOR ON LS-1. OK ON FIRE ALARM
 PLANS. PLEASE CORRELATE INFORMATION.
  
 9) NO FIRE ALARM DEVICES ARE SHOWN IN MEETING ROOMS A
 AND B SECOND FLOOR ON SHEET LS-1.
  
 10) STAIR #2 SHOULD BE CORRECTED TO READ FIRE SPRINKLER
 RISER.
  
 11) PROVIDE MINIMUM STRENGTH REQUIREMENTS FOR GUARDS
 AND HANDRAILS.
  
 12) ADDRESS IS REQUIRED ON BUILDING THAT SHALL BE A
 MINIMUM OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH
 BACKGROUND. PLEASE ADD TO ELEVATIONS.
  
 13) STAIRS TO COMPLY WITH NFPA 101 SEC. 7.2.2. PLEASE
 CLARIFY WIDTH OF TREADS.
  
 14) HANDRAILS ARE REQUIRED ON BOTH SIDES OF STAIRS.
 NFPA 101, SEC. 7.2.2.4.1.1.
  
 15) THE DOOR SCHEDULE INDICATES CLOSERS ON SOME OF THE
 DOORS. SOME OF THE RATED DOORS ARE LISTED WITH NO
 CLOSERS. PLEASE EXPLAIN OR ADD TO SCHEDULE.
  
 16) EQUIPMENT THAT COOKS FOOD CAPABLE OF PRODUCING
 GREASE LADEN VAPORS SHALL BE PROTECTED BY AN APPROVED
 HOOD/SUPPRESSION SYSTEM. THE SYSTEM SHALL BE TIED INTO
 THE FIRE ALARM AND SEPARATE SHOP DRAWINGS AND PERMITS
 FOR BOTH HOOD AND SUPPRESSION ARE REQUIRED PRIOR TO
 INSTALLATION.
  
 17) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. OK ON
 SHEET E401. PLEASE ADD NOTE TO FIRE ALARM DRAWINGS.
  
 18) FIRE DAMPERS TO BE TESTED FOR CLOSURE IN ACCORDANCE
 WITH UL 555 STANDARDS PRIOR TO FINAL INSPECTION.
  
 19) FIRE ALARM SYSTEM SHALL BE UL CERTIFICATED FOR
 CENTRAL STATION SERVICE. CERTIFICATE REQUIRED AT TIME
 OF OR PRIOR TO FINAL FIRE ALARM INSPECTION.
  
 20) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 ALARM SYSTEM IN ADDITION TO FIRE SPRINKLER SYSTEM.
  
 21) SHEET LS-1 ILLUSTRATES AN EXIT SIGN IN EDUCATION
 ROOM 109 THAT IS NOT SHOWN ON SHEET EL-101. PLEASE
 CORRELATE INFORMATION.
  
 22) SHEET LS-1 ILLUSTRATES AN EXIT SIGN IN SECOND FLOOR
 LOBBY THAT IS NOT SHOWN ON SHEET EL-102 LIGHTING PLAN.
  
 23) THERE ARE NO SMOKE DETECTION DEVICES SHOWN IN
 ELECTRICAL ROOMS FIRST AND SECOND FLOORS ON FIRE ALARM
 PLANS.
  
 24) FIRE ALARM DRAWINGS, SHEETS EF-101 AND EF-102 DON'T
 ILLUSTRATE TAMPER AND FLOW SWITCH EQUIPMENT EXCEPT FOR
 THE LEGEND.
  
 25) ELEVATOR SHALL COMPLY WITH ASME A17.1. WARNING
 SIGNS REQUIRED IN ELEVATOR LOBBIES.
  
 26) FIRE ALARM SYSTEM SHALL BE CLASS A OR FULLY
 ADDRESSABLE.
  
 27) SHEET E-401 INDICATES DOOR HOLDERS, NOTE 10A BUT NO
 SUCH DEVICES ARE SHOWN ON FA SHEETS EF-101 AND EF-102.
 PLEASE CLARIFY.
  
 28) SHEET FP-101 GENERAL NOTES 6,8 AND 11 REFERENCE PBC
 FIRE RESCUE. THE CORRECT AGENCY AND AHJ FOR REFERENCES
 PROJECT IS WEST PALM BEACH FIRE RESCUE.
  
 29) IN ADDITION TO MULTI-PURPOSE FIRE EXTINGUISHERS,
 "K" TYPE EXTINGUISHER IS REQUIRED IN KITCHEN.
  
 30) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 A RESPONSE LETTER INDICATING HOW AND WHERE ON THE PLANS
 EACH ITEM HAS BEEN ADDRESSED WOULD HELP EXPEDITE THE
 PLAN REVIEW PROCESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-05-30 Cont ID  
Sent By swurafti Date 2008-05-30 Time 08:50 Rev Time 0.00
Received By swurafti Date 2008-05-30 Time 08:50 Sent To  
Notes
2008-05-30 09:00:54HISTORIC APPROVED BY FMITTNER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-07-21 Time   Rev Time 0.00
Received By adarroug Date 2008-06-02 Time 11:29 Sent To  
Notes
2008-06-02 11:30:07TO "COMM" BD#4/PLANS ON RACK/1 ROLL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-25 Cont ID  
Sent By rregueir Date 2008-06-25 Time 09:49 Rev Time 0.00
Received By rregueir Date 2008-06-20 Time 16:40 Sent To  
Notes
2008-06-25 09:49:35REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG LS-1: ACCORDING TO THE LIFE SAFETY SYMBOL LEGEND,
 THIS FLOOR PLAN SHOWS DUCT MOUNTED SMOKE DETECTORS
 THROUGHOUT THE BUILDING (INDICATED BY THE SMALL ?S?
 NEXT TO THE SMOKE DETECTOR SYMBOL). NO SUCH DETECTORS
 ARE SHOWN ON MECHANICAL FLOOR PLANS. PLEASE CLARIFY AND
 COORDINATE DRAWINGS, SHOWING COMPLIANCE WITH FBCM
 606.3.
 NOTE: THIS COMMENT IS NOT INTENDED TO DETERMINE WHETHER
 OR NOT DUCT DETECTORS ARE REQUIRED. SEE FBCM 606.2 FOR
 REQUIREMENTS.
  
 2. PAGE LS-1 USES SYMBOLS SUCH AS SR AND 1F TO LABEL
 SOME WALLS. THERE IS NO INDICATION ON THE SYMBOL LEGEND
 WHAT THESE SYMBOLS REPRESENT. IF IT IS ASSUMED THAT 1F
 INDICATES A 1-HOUR FIRE RESISTANT WALL, THIS CAN NOT BE
 CONFIRMED WITH ARCHITECTURAL FLOOR PLANS AS SOME OF THE
 WALLS WITH THE 1F DESIGNATION ARE NOT SHOWN TO BE FIRE
 RESISTANCE RATED ON ARCHITECTURAL FLOOR PLANS. EXAMPLE:
 THE WALLS OF CORRIDOR 205 ARE MARKED WITH THE 1F
 DESIGNATION BUT ARE SHOWN AS WALL TYPE P4. ACCORDING TO
 WALL SCHEDULE ON A-12 THIS WALL TYPE CARRIES NO RATING.
 AS A RESULT, THE APPROPRIATE REQUIRED PROTECTION OF
 DUCT PENETRATIONS AT WALL ASSEMBLIES CAN NOT BE
 DETERMINED. A THOROUGH REVIEW OF DUCT PLANS CAN NOT BE
 PERFORMED AT THIS TIME.
  
 3. PAGE M101: 1FC:# SHOWS A DUCT SMOKE DETECTOR ON THE
 RETURN AIR SIDE. DUCT SMOKE DETECTORS SHALL BE
 INSTALLED ON THE SUPPLY SIDE IN ACCORDANCE WITH FBCM
 606.2.1.
  
 4. PAGES M101 AND M102: KEY NOTE #3 CALLS FOR CO2
 DETECTORS TO CONTROL MODULATING DAMPERS, BUT KEY NOTE
 #4 CALLS FOR THE CO2 DETECTORS TO CONTROL THE FCUS.
 PLEASE CLARIFY DESIGN INTENT AND NOTES TO ELIMINATE
 CONFLICTING INFORMATION AND SHOW COMPLIANCE WITH FBCM
 401.3 AND 403.4.
  
 5. PAGE M101: OUTSIDE AIR INTAKES FOR ERVS DO NOT SHOW
 MOTORIZED DAMPERS ON PLAN. OUTDOOR AIR SUPPLY SYSTEMS
 SHALL BE EQUIPPED WITH MOTORIZED DAMPERS THAT WILL
 AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES SERVED
 ARE NOT IN USE IN ACCORDANCE WITH FBCB
 13-409.1.ABC.3.3.
  
 6. PAGE M102: THIS BUILDING IS DECLARED AS AN A-3
 OCCUPANCY ON PAGE LS-1. EXIT ACCESS CORRIDORS ARE
 REQIRED TO BE MINIMUM 1-HOUR FIRE RESISTANCE RATED IN
 ACCORDANCE WITH FBCB TABLE 1016.1. DUCTS AND AIR
 TRANSFER OPENINGS WHICH PENETRATE THE WALLS OF CORRIDOR
 205 SHALL BE PROTECTED WITH FIRE AND SMOKE DAMPERS IN
 ACCORDANCE WITH FBCM 607.5 AND 607.5.4. SEE ALSO FBCB
 715.3.3. CHECK ALL DUCT PENETRATIONS IN THIS AREA FOR
 COMPLIANCE. ALSO, SHOW HOW SMOKE DAMPERS ARE TO BE
 ACTUATED IN ACCORDANCE WITH FBCM 607.5.4.1.
  
 7. PAGE M102: KITCHEN EXHAUST GREASE DUCT IS SHOWN
 PENETRATING FLOOR/CEILING ASSEMBLY. WHILE PLANS CALL
 FOR THE GREASE DUCT TO BE FIRE-WRAPPED, THERE IS NO
 INDICATION ON PLANS AS TO HOW THE FLOOR/CEILING
 PENETRATION IS TO BE PROTECTED. ARCHITECTURAL PLANS
 SHOW AN ENCLOSURE AROUND THE DUCT ON 2ND FLOOR BUT NO
 RATING OF THE ENCLOSURE. PLEASE SHOW HOW THIS
 PENETRATION IS TO BE PROTECTED IN ACCORDANCE WITH FBCM
 607.6.
  
 8. PAGE M102: THE 12X12 SUPPLY DUCT FROM 2FC:1 IS SHOWN
 PENETRATING A 1-HOUR FIRE RESISTANCE RATED WALL WITHOUT
 ANY PROTECTION OF THE PENETRATION. SHOW HOW THIS DUCT
 PENETRATION IS TO BE PROTECTED IN ACCORDANCE WITH FBCM
 607.5. SEE ALSO COMMENT #6 ABOVE.
  
 9. PAGE M102: THE SIZE OF THE RETURN DUCT SERVING ROOM
 218 IS MISSING SIZE AND GRILL DESIGNATION. PLEASE
 CLARIFY. AN AIR DISTRIBUTION SYSTEM SHALL BE DESIGNED
 AND INSTALLED TO SUPPLY THE REQUIRED DISTRIBUTION OF
 AIR IN ACCORDANCE WITH FBCM 603.1.
  
 10. PAGE M202 DETAILS FOR ALL ROOF MOUNTED AND OUTDOOR
 EQUIPMENT AND APPLIANCES: NO INFORMATION WAS PROVIDED
 IN STRUCTURAL OR MECHANICAL PLANS REGARDING WIND
 RESISTANCE. PROVIDE SPECIFIC ATTACHMENT DETAIL FOR ROOF
 CURBS AND A/C STANDS TO THE BUILDING STRUCTURE AS WELL
 AS FOR APPLIANCE ATTACHMENT TO CURBS AND STANDS WITH
 SUPPORTING WIND LOAD CALCULATIONS IN ACCORDANCE WITH
 FBCM 301.13 AND FBCB SECTION 1609. ALSO, PROVIDE
 DOCUMENTATION SHOWING APPLIANCES (SUCH AS THE GREASE
 EXHAUST FAN, FOR EXAMPLE) ARE DESIGNED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH THESE SECTIONS.
  
 11. PAGE M202 FAN COIL CONDENSATE DRAIN DETAIL:
 AUXILIARY OR SECONDARY DRAIN PROTECTION IS REQUIRED AT
 ALL COILS WHICH PRODUCE CONDENSATE IN ACCORDANCE WITH
 FBCM 307.2.3. THE DETAIL SHOWS A FLOAT SWITCH INSTALLED
 IN THE PRIMARY CONDENSATE DRAIN LINE. THIS IS NOT ONE
 OF THE METHODS ACCEPTED UNDER THIS SECTION. THE FLOAT
 SWITCH MAY BE INSTALLED IN AN AUXILIARY DRAIN PAN, ON A
 SECONDARY DRAIN LINE OR INSIDE THE FAN COIL ON THE
 PRIMARY DRAIN PAN TO SHOW COMPLIANCE WITH THE
 REQUIREMENTS OF THIS SECTION.
  
 12. PAGE M202 FIRE DAMPER DETAIL: FIRE AND SMOKE
 DAMPERS SHALL BE INSTALLED IN ACCORDANCE WITH THEIR
 LISTING AND MANUFACTURER?S INSTALLATION INSTRUCTIONS
 PER FBCM 607.2. PROVIDE A DETAIL WHICH CORRESPONDS WITH
 THE DAMPERS BEING USED OR PROVIDE MANUFACTURER?S
 INSTRUCTIONS.
  
 13. PAGE M301. WHAT IS THE HEIGHT OF KEF-1 IN RELATION
 TO THE PARAPET WALLS SURROUNDING THIS ROOF AREA?
 ACCORDING TO THE ELEVATIONS SHOWN ON PAGE A-3, THE
 PARAPET IS APPROXIMATELY 8 FEET ABOVE THE MECHANICAL
 ROOF LEVEL. EXHAUST OUTLETS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) HORIZONTALLY FROM PARTS OF THE
 SAME OR CONTIGUOUS BUILDINGS (INCLUDING PARAPETS) IN
 ACCORDANCE WITH FBCM 506.3.12.3. EXHAUST FANS SHALL BE
 POSITIONED SO THAT THE DISCHARGE WILL NOT IMPINGE ON
 THE ROOF, OTHER EQUIPMENT OR APPLIANCES OR PARTS OF THE
 STRUCTURE IN ACCORDANCE WITH FBCM 506.5.2. THE MINIMUM
 HORIZONTAL DISTANCE BETWEEN VERTICAL DISCHARGE FANS AND
 PARAPET-TYPE BUILDING STRUCTURES SHALL BE 2 FEET
 PROVIDED THAT SUCH STRUCTURES ARE NOT HIGHER THAN THE
 TOP OF THE FAN DISCHARGE OPENING IN ACCORDANCE WITH
 FBCM 506.5.5. PROVIDE SUFFICIENT DETAILS IN PLAN AND
 ELEVATION VIEW TO SHOW COMPLIANCE WITH THESE SECTIONS.
  
 14. ENERGY CALCULATIONS CAN NOT BE REVIEWED AT THIS
 TIME AS THE INPUT DATA REPORT WAS NOT INCLUDED WITH THE
 COMPLIANCE REPORT. PLEASE SEE PAGE TWO OF THE
 COMPLIANCE REPORT WHICH STATES: IMPORTANT NOTE: AN
 INPUT REPORT OF THIS DESIGN BUILDING MUST BE SUBMITTED
 ALONG WITH THIS COMPLIANCE REPORT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-07-10 Cont ID  
Sent By kstevens Date 2008-07-10 Time 07:57 Rev Time 0.00
Received By kstevens Date 2008-07-09 Time 18:29 Sent To  
Notes
2008-07-10 10:20:09DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH URBAN DESIGN STUDIO TITLE BLOCKS
 SHALL HAVE THE BUSINESS LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION NUMBER) INCLUDED IN THE TITLE BLOCK OF
 EACH SHEET. FAC 61G1-16.002(2) & FS 481.219.
  
 2. SHTS 1 OF 1 SITE PLAN & SHTS 1 THRU 4 OF 4 HARDSCAPE
 ARE NOT SIGNED, SEALED & DATED AS REQUIRED. SECTION
 106.1, FAC 61G1-16.003 & FS 481.306.
  
 3. SHTS 1 OF 2 IRRIGATION SHOW THE LOCATION OF THE
 CONTROLLER AND THE RAIN SENSOR. SECTION 106.1.2 & FS
 373.62.
  
 4. SHTS 1 & 2 OF 2 IRRIGATION THE PRINTED NAME OF THE
 LANDSCAPE ARCHITECT IS REQUIRED IN THE TITLE BLOCK OF
 EACH SHEET. FAC 61G1-16.002(6) & FS 481.306.
  
 5. SHT 1 OF 1 UPLIGHTING PLAN IS NOT SIGNED, SEALED AND
 DATED AS REQUIRED IN SECTION 106.1, FAC 61G1-16.003 &
 FS 481.306.
  
 6. SHT 1 OF 15 SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLES 1004.1.2 & 403.1. INDICATE IF
 EACH SPACE IS CONSENTRATED, STANDING SPACE OR
 UNCONSENTRATED. (EDUCATIONAL - MEETING ROOMS - WORKROOM
 - MULTIPURPOSE COMMUNITY ROOM). THE OCCUPANCY INDICATED
 372 & 216 SHALL BE VERIFIED.
  
 7. PER OCCUPANT LOAD INDICATED, (588 FOR BOTH FLOORS),
 3 DRINKING FOUNTAINS ARE REQUIRED. TABLE 403.1. ONLY
 TWO ARE SHOWN, (IF THE HIGH LOW HAS SEPARATE TRAPS AND
 WATER SUPPLIES). PLEASE SHOW THE LOCATION OF THE THIRD
 DRINKING FOUNTAIN. (ALSO SEE SECTION 410.1). AT LEAST
 50% OF ALL DRINKING FOUNTAINS PROVIDED SHALL BE
 ACCESSIBLE PER SECTION 11-4.1.3(10)(B).
  
 8. A GREASE INTERCEPTOR IS INDICATED. THE SIZING OF THE
 GREASE INTERCEPTOR SHALL BE BY THE UTILITY DEPT. PLEASE
 CONTACT RODNEY COMPO, ENVIRONMENTAL COMPLIANCE AT (561)
 644-1821, FAX (561) 822-2287 OR E-MAIL [email protected].
 ARTICLE III SECTION 90-124(7)
  
 9. SHT P101 SHOWS TYP 3/P201 FOR CONDENSATE. PLEASE
 INDICATE WHERE THE CONDENSATE DRAINS TO AS IT CAN NOT
 CAUSE A NUISANCE AND CAN NOT DRAIN ON TO A SIDEWALK,
 DRIVEWAY ETC. SECTIONS 106.1.2 & 314.2.1.
  
 10. SHT P301 EQUIPMENT & FIXTURES UTILIZED FOR THE
 STORAGE, PREP & HANDLING OF FOOD SHALL DISCHARGE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
 SECTION 802.1.1. A FLOOR SINK WILL BE REQUIRED PER
 SECTION 802.3.2.
  
 11. SHT P401 SANITARY RISER DIAGRAM, THE FLOOR DRAIN IN
 TOILET ROOM 223 IS NOT VENTED. SECTION 901.2.1.
  
 12. SHT P401 SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN AS THERE ARE OFFSETS IN THE PIPING SHOWN
 ON THE FLOOR PLAN THAT ARE NOT SHOWN ON THE RISER
 DIAGRAM AS WELL ASTHE BASE OF THE STACK TO TOILET
 ROOMS 223 & 224 DOES NOT REFLECT THE FLOOR PLAN. (RISER
 TURNS SOUTH & FLOOR PLAN TURNS NORTH). SECTION 106.1.1.
 PLEASE CORRELATE.
  
 13. SHT P401 CONDENSATE RISER DIAGRAM THE PIPE SIZES DO
 NOT REFLECT THE FLOOR PLAN IN MANY AREAS. PLEASE
 CORRELATE AND SHOW ALL PIPE SIZES. ALSO THE CONDENSATE
 LINE DOWNSTREAM OF UNIT 1FC:6 IS SHOWN CONNECTING TO
 THE 2ND FLOOR CONDENSATE RISER ON THE RISER BUT NOT ON
 THE FLOOR PLAN. SECTION 106.1.1 & 314.
  
 14. SHT P401 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN IN ABOUT 7 OR 8 AREAS. THE STUB-OUTS FOR THE
 FIXTURES IN THE GANG BATHS ARE SHOWN TURNING THE WRONG
 WAY, (AWAY FROM THE FIXTURES), AND PIPING THE THE
 CEILING FOR BRANCH CONNECTIONS TO THE WATER MAINS DOES
 NOT RELFECT IN SOME AREAS. THE DRINKING FOUNTAIN
 SUPPLIES ARE NOT SHOWN ON THE RISER AS WELL AS THE
 SUPPLY LINES TO THE SHOWER AND A "BS" FOR THE SECOND
 FLOOR. SECTIONS 106.1.1 & 601.1.
  
 15. SHT P401 WATER RISER DIAGRAM WATER HAMMER ARRESTORS
 ARE REQUIRED AT THE DISHWASHER & ICE MACHINE. SECTION
 604.9.
  
 16. SHT P401 WATER RISER DIAGRAM SHUT OFF VALVES ARE
 REQUIRED ON THE SUPPLY LINES TO EACH HOSE BIBB. SECTION
 606.2(2)
  
 17. SHT P401 WATER RISER DIAGRAM FULL OPEN VALVES ARE
 REQUIRED ON THE SUPPLY LINES TO EACH WATER HEATER.
 SECTION 606.1(7).
  
 18. SHT P401 WATER RISER DIAGRAM SHOW ALL PIPE SIZES.
 SECTION 604.1.
  
 19.SHT KP101 SANITARY FLOOR PLAN AND RISER DIAGRAM DOES
 NOT REFLECT THE PLUMBING LAYOUT AND RISER DIAGRAM ON
 SHTS P301 & P401. PLEASE CORRELATE. SECTION 106.1.1
  
 20 SHT KP102 KITCHEN WATER RISER WATER HAMMER ARRESTORS
 ARE REQUIRED AT THE DISHWASHER. SECTION 604.9. A SHUT
 OFF VALVE ARE REQUIRED AT THE HOSE BIBB SUPPLYLINE
 AND A FULL OPEN VALVE IS REQUIRED ON THE SUPPLY LINE TO
 THE WATER HEATER. SECTIONS 606.2(2) & 606.1(7).
  
 21. SHT KP103 A SEPARATE GAS PERMIT IS REQUIRED. PLEASE
 SUPPLY THE FOLLOWING INFORMATION FOR GAS PERMIT
 APPROVAL:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (CUT SECTIONS FROM THE METER TO THE
 FIRST RISER, AND THE DROP WITH THE VALVES AND UNIONS DO
 NOT INDICATE THE LENGTHS).
  
 B. TYPE OF GAS, (LP OR NATURAL).
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). (NOT ALL BTU LOADS ARE INDICATED ON THE
 RISER OR IN THE GAS REQUIREMENTS CHART).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN
 COMMENT "21-A" ADDRESSED).
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 H. GAS REQUIREMENT CHART DOES NOT REFLECT THE GAS RISER
 DIAGRAM. ONLY 4 APPLIANCES ARE SHOWN ON THE CHART, A,
 C, D & ONE NON DESIGNATED APPLIANCE. THE RISER SHOWS 5
 APPLIANCES, A, B, D, S & ONE NON DESIGNATED APPLIANCE
 WITH NO BTU LOAD INDICATED. PLEASE CORRELATE AND SHOW
 ALL BTU LOADS THAT REFLECT THE MANUF. SPECIFICATION
 SHEETS SUBMITTED. SECTIONS 106.1.1 & 402.
  
 I. GAS RISER DELETE THE UNION UPSTREAM OF THE MANUAL
 SHUT OFF VALVE AS IT IS NOT REQUIRED OR MOVE IT
 DOWNSTREAM OF THE MANUAL SHUT OFF VALVE.--MINIMUM
 1" STUB OUT AND SHUT OFF VALVE IS REQUIRED TO THE
 RANGE, APPLIANCE "A".--INDICATE THE MATERIAL FOR
 THE VENT FOR THE SECOND STAGE REGULATOR. (SHALL BE NON
 COMBUSTABLE).
 SECTION 403.6. (SEE NFPA 54 SECTIONS 5.8.5.1 & 6.4).
  
 22. SHT KD101 DETAIL 8 WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASH MACHINE. SECTION 604.9.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-18 Cont ID  
Sent By astelly Date 2008-06-18 Time 18:10 Rev Time 0.00
Received By astelly Date 2008-06-18 Time 18:10 Sent To  
Notes
2008-06-20 08:02:38AMY STELLY
 URBAN DESIGN
 822-1440
  
 PLEASE REMOVE PAVING FROM RIGHT-OF-WAY.