| 2008-06-26 12:36:56 | ** DENIEDREVIEW ** |
| | |
| | *** IT IS IMPORTANT TO UNDERSTAND AS SOME THINGS HAVE |
| | NOT YET BEEN SUBMITTED FOR MINIMUM CODE COMPLIANCE |
| | THERE MAY VERY WELL BE NEW COMMENTS ON THE NEXT REVIEW |
| | WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | 1)NOTE: PLEASE SEE THE ADDRESS ON PLANS AND |
| | SUPPORTING DOCUMENTS ARE STATING 814 DIVISION AVE YET |
| | THE APPLIED LOCATION IS 706 8TH ST. PLEASE ADJUST TITLE |
| | BLOCKS ON ALL PLANS AND ALL SUPPORTING DOCUMENTS. |
| | FBC 106.5 ADMIN SECTION. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE THE SUBMITTED SURVEY IS REQUIRED TO |
| | CONTAIN AN ORIGINAL SIGNATURE. PER FS 472.025 MAY NOT |
| | PLACE RAISED SEAL OVER RUBBER STAMP SIGNATURE. |
| | STATEMENT PER FAC 61G17 AND AS STATED ON THE TITLE |
| | BLOCK FOR SAME SAID SHEETS STATE THE SHEET IS NOT VALID |
| | WITHOUT ORIGINAL SIGNATURE. |
| | PLEASE ADJUST. THIS IS A FLORIDA STATUTE AND REQUIRED |
| | WHETHER OR NOT COMMENT IS MADE BY ANY OTHER REVIEWER. |
| | |
| | 3) NOTE: PLEASE SEE THE LANDSCAPE PLANS ARE MISSING THE |
| | REQUIRED CERTIFICATION OF AUTHORIZATION NUMBER AS |
| | REQUIRED PER FS 481.219, FAC 61G1-16.004. |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADE REVIEW. |
| | |
| | 4) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | DO NOT CONTAIN ANY ORIGINAL SIGNATURES. IN FACT BOTH |
| | COPIES SUBMITTED CONTAIN A RAISED SEAL OVER A COLOR |
| | PHOTO-COPIED SIGNATURE BY THE ENGINEER. PLEASE SEE FAC |
| | 61G15-23.002 AND FS 471.025 AS AN ORIGINAL SIGNATURE IS |
| | REQUIRED ON ALL DOCUMENTS DONE BY THE ENGINEER. THIS |
| | COMMENT HAS BEEN MADE BEFORE FOR THIS DESIGNER OF |
| | RECORD. PLEASE KNOW BOTH SETS OF CALCULATIONS SUBMITTED |
| | ARE BEING RETAINED BY THIS OFFICE. |
| | |
| | 5) NOTE: PLEASE KNOW THE SUBMITTED ENERGY CALCULATIONS |
| | ARE NOT COMPLETE. NO INPUT DATA REPORT WAS SUBMITTED. |
| | PAGE TWO OF NINE STATES THE INPUT DATA REPORT MUST BE |
| | SUBMITTED ALONG WITH THE SUMMARY SHEETS. IN ANY CASE |
| | PLEASE KNOW THAT SOME OF THE INFORMATION ON THE |
| | SUBMITTED CALCULATIONS DOES NOT MATCH WITH THE PLANS. |
| | AN EXAMPLE OF THIS IS THE LIGHTING IN THE SUMMARY WHICH |
| | SHOWS A TOTAL OF 574 WATTS OF LIGHTING. HOW IS THIS |
| | POSSIBLE WHEN THE WSA FIXTURES ALONE EXCEED THE |
| | 574WATTS? THERE ARE SEVERAL OTHER FIXTURES ON PLANS |
| | WHICH ARE NOT ACCOUNTED FOR. |
| | PLEASE BE SURE ALL INFORMATION ON THE INPUT DATA |
| | REPORTS COORDINATES WITH PLANS. PLEASE BE SURE ALL |
| | INTERIOR LIGHTING SUCH AS THE WATTAGE OF FIXTURES, THE |
| | TYPES OF FIXTURES, THE METHOD OF CONTROLS AND THE |
| | NUMBER OF FIXTURES. THIS OFFICE CAN NOT EMPHASIZE |
| | ENOUGH THAT ALL INFORMATION ON PLANS FOR ALL COMPONENTS |
| | OF THE BUILDING WILL NEED TO COORDINATE WITH THE |
| | SUBMITTED CALCULATIONS. ONE EXAMPLE ABOVE WAS GIVEN |
| | WITH RESPECT TO THE EXTERIOR LIGHTING EVEN AS SHOWN ON |
| | THE SUMMARY SHEETS DID NOT COORDINATE WITH THE |
| | SUBMITTED PLANS. |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE 13-400.3.A AS SUBMITTED. |
| | ** PLEASE BE SURE TO SEE TRACK LIGHTING AS NOTED IN |
| | SECTIONS ABOVE. |
| | ** PLEASE BE SURE ALL LUMINAIRES SHOWN ON THE FIXTURE |
| | LEGEND AND ALL PLANS COORDINATE WITH THE TYPES. THERE |
| | WILL BE OTHER COMMENTS BELOW AS THERE ARE SEVERAL |
| | FIXTURES ON THE PLANS WHICH DO NOT APPEAR IN THE |
| | FIXTURE LEGEND. |
| | ** PLEASE BE SURE TO USE THE FIXTURE RATED OUTPUT |
| | WHETHER OR NOT IT IS INCANDESCENT, FLUORESCENT, OR HID |
| | ETC. |
| | ** PLEASE BE SURE TO SEE THE USE OF ANY LOW VOLTAGE |
| | SYSTEMS. |
| | |
| | 6) NOTE: PLEASE SEE THE SUBMITTED CALCULATIONS STATE |
| | SCHOOL AS THE OCCUPANCY HOWEVER THE OCCUPANCY AS STATED |
| | BY THE ARCHITECT IS NOT EDUCATIONAL AND IN FACT IS |
| | STATED AS A3. |
| | PLEASE BE SURE THE *INDIVIDUAL* NOT THE FIRM IS LISTED |
| | AT THE PREPARER. THE CERTIFICATION SHEETS ARE SET UP |
| | FOR THE INDIVIDUAL CERTIFYING NOT A FIRM. |
| | PLEASE BE SURE TO ADJUST. |
| | 13-415.2, 13-400.3.A, 13-103.1 |
| | |
| | 7) NOTE: PLEASE COORDINATE ALL ELECTRICAL PLANS. PLEASE |
| | SEE THE ELECTRICAL SITE PLANS SHOWN ON ES101 DO NOT |
| | MATCH WITH THE FIXTURES ETC ON ES102. |
| | PLEASE SEE OTHER SHEETS WHICH INDICATE SITE LIGHTING |
| | POLES YET THE ELECTRICAL SITE PLANS DO NOT INDICATE ANY |
| | SITE LIGHTING POLES. |
| | PLEASE SEE THE LUMINAIRE SCHEDULE ON ES 102 WHICH DOES |
| | NOT INCLUDE THE S32 FIXTURE AT ALL. |
| | PLEASE SEE TIME CLOCK SITE/EXTERIOR LIGHTING SCHEDULE |
| | WHICH ALSO INDICATES OTHER LIGHTING YET THE SITE PLANS |
| | ARE NOT COMPLETE AND DO NOT COORDINATE. THERE ARE |
| | SEVERAL ITEMS. |
| | NEC 220, 240,310,408 ETC |
| | FBC 13-415.2.ABC.1.3 |
| | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | CLARITY. |
| | |
| | 8) NOTE: PLEASE BE SURE TO INDICATE THE REQUIRED |
| | ASTRONOMICAL TIME CLOCK AS REQUIRED PER |
| | 13-415.1.ABC.1.4 WITH THE REQUIRED BACK UP OF |
| | PROGRAMMING. |
| | |
| | 9) NOTE: PLEASE SEE THE TIME CLOCK SCHEDULE AS THE |
| | CIRCUITING SHOWN ON THIS SCHEDULE NEEDS TO COORDINATE |
| | WITH PLANS. |
| | PARKING LOT LTS, GAZEBO LTS ETC |
| | NEC 240, 220, 310.16 |
| | FBC 13-415.2.ABC.1.3 |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| | |
| | 10) NOTE: PLEASE SEE THERE ARE MISSING LIGHTING |
| | CONTROLS FOR 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE ONE EXAMPLE OF THIS IS THE STANDARD SINGLE |
| | POLE LIGHT SWITCH SHOWN FOR THE TRACK LIGHTS. |
| | THESE ARE ALSO REQUIRED TO BE CONTROLLED WITH SOME |
| | SORT OF AUTOMATED CONTROLS. |
| | ANOTHER EXAMPLE WOULD BE THE KITCHEN LIGHTING WHICH |
| | INDICATE STANDARD 3-WAY SWITCHES. |
| | ** SOME EXAMPLES ARE GIVEN ONLY. PLEASE BE SURE TO SEE |
| | OTHER COMMENTS WHICH MAY AFFECT LIGHTING AND CONTROLS. |
| | PLEASE BE SURE TO ADJUST SHOWING ALL MAXIMUM TIMES FOR |
| | ALL CONTROLS AND ALL DEVICES. |
| | MANY ARE OK, HOWEVER NOT ALL. |
| | |
| | 11) NOTE: PLEASE SEE ANY ZONING COMMENTS WITH RESPECT |
| | TO THE AMOUNT OF LIGHTING PERMITTED OVER THE PROPERTY |
| | LINES. EVEN IF THERE HAVE BEEN NO COMMENTS FROM THE |
| | REVIEW PLEASE BE SURE TO CALL ZONING OFFICE TO VERIFY |
| | THE LIGHTING LEVELS OVER THE PROPERTY LINES. THIS IS |
| | NOTED FOR INFORMATION ONLY AND AS A BENEFIT SO THERE |
| | ARE NO ISSUES WITH FIXTURES AT A LATER DATE. |
| | SOME LEVELS APPEAR TO BE OVER THE ALLOWANCES IN SOME |
| | AREAS ONLY. THIS IS ONLY GIVEN FOR INFORMATION AND IS |
| | NOT AN ELECTRICAL REVIEW COMMENT WHICH NEEDS TO BE |
| | ADDRESSED. NO RESPONSE NEEDED. |
| | |
| | 12) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL |
| | DESIGNATED EGRESS PATHS OUT FROM BUILDING. PLEASE BE |
| | SURE TO INCLUDE THE LIGHTING LEVELS UNDER NORMAL AND |
| | UNDER EMERGENCY CONDITIONS. |
| | PLEASE BE SURE TO SEENFPA-101 2003, 7.8.1.3 AND |
| | 7.9.2.2 WHICH REQUIRES A MINIMUM OF 10FT CANDLESON |
| | ALL WALKING SURFACES OF STAIRS AND IS PERMITTED TO GO |
| | DOWN TO 1FT CANDLE UNDER EMERGENCY. |
| | PLEASE SEE 7.8.1.2.2 FOR TYPES OF OCCUPANCY SENSORS |
| | REQUIRED. THESE SHALL BE FAIL SAFE *ON*. THIS IS ALSO |
| | NOTED IN FBC 1016.1 |
| | |
| | 13) NOTE: AS NOTED ABOVE IN PREVIOUS NOTES WITH RESPECT |
| | TO FIXTURES AND COORDINATION AND NOTE #12 ABOVE PLEASE |
| | BE SURE TO COORDINATE ALL LIGHTING FIXTURES. |
| | PLEASE SEE MISSING SOME AS EXAMPLE: WS3E, B3E, WSA, TL1 |
| | ETC |
| | PLEASE SEE FOR EXAMPLE MANY OF THE LIGHTING FIXTURES |
| | IN THE STAIRS AND OTHER LOCATIONS WHICH INDICATE AN *E* |
| | NEXT TO FIXTURE DESIGNATION. THIS FIXTURE IS NOT LISTED |
| | ON THE FIXTURE LEGEND WITH EMERGENCY BALLAST ETC.THE |
| | STAIR FIXTURES AND OTHER FIXTURES WHICH ARE ASSUMED TO |
| | CONTAIN BATTERY BACK UP BALLAST ARE IN NEED OF ALSO |
| | COORDINATING WITH THE PHOTO-METRICS TO BE SUBMITTED. |
| | NFPA-1017.8, 7.9 |
| | FBC 13-415.2.ABC.1.1, .1.2 |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| | |
| | 14) NOTE: PLEASE SEE THE MULTI-GANG BATHROOMS. THE |
| | PLANS INDICATE FOR LIGHTING CONTROLS A SINGLE POLE |
| | SWITCH DEVICE *AFTER* THEOCCUPANCY SENSING. |
| | PLEASE KNOW DUE TO THE LIFE SAFETY EGRESS SITUATION AS |
| | SHOWN THIS WOULD ALLOW AN OCCUPANT TO TURN OFF LIGHTING |
| | ON THE BATHROOMS WHILE AN OCCUPANT IS STILL IN ANY |
| | LOCATION THEREFORE LEAVING ANY ONE EGRESS AREA IN TOTAL |
| | DARKNESS. |
| | PLEASE ADJUST DESIGN SO THAT THIS DOES NOT OCCUR. |
| | NFPA-101 7.8, 13-415.1.ABC.1.2. |
| | |
| | 15) NOTE: PLEASE SEE THAT MANY ROOMS AND AREAS OF THE |
| | PLANS HAVE DESIGNATIONS HOWEVER MANY AREAS OF THE PLANS |
| | IN FACT MOST ROOMS THE PRINT ON PLANS FOR THESE ROOMS |
| | AND AREAS ARE VERY FAINT AND NOT READABLE. THE REVIEW |
| | OF SEVERAL ITEMS FOR COORDINATION ON PLANS IS NEEDED |
| | AND PLEASE BE SURE TO ADJUST PRINT SO THESE CAN BE |
| | READ. |
| | FBC ADMIN SECTION 106.1, 106.1.1, 106.1.3 FOR CLARITY. |
| | |
| | 16) NOTE: PLEASE PROVIDE DISCONNECTING MEANS AT GAZEBO |
| | PER 225.31-225.39 |
| | |
| | 17) NOTE: PLEASE PROVIDE THE REQUIRED GROUNDING |
| | ELECTRODE AT GAZEBO PER 250.32, 250.50 OR MEET THE |
| | EXCEPTION OF THE CODE. |
| | |
| | 18) NOTE: PLEASE BE SURE TO COMPLETE ALL CIRCUITING ON |
| | PLANS. PLEASE SEE FOR EXAMPLE THE STAIRS WHICH NO |
| | CIRCUITING IS SHOWN. |
| | PLEASE SEE 700.12F. |
| | PLEASE SEE THERE ARE OTHER ITEMS ON PLANS AS WELL WHICH |
| | DO NOT INDICATE CIRCUITS AND/OR DO NOT CORRELATE WITH |
| | THE SUBMITTED PANEL SCHEDULES. |
| | PLEASE BE SURE TO COORDINATE ALL. |
| | NEC 240.4, 310.16, 220, 408.4 |
| | FBC 106.1.2, 106.1.1, 106.3.5.1.2 FOR MINIMUM |
| | INFORMATION REQUIRED AND CLARITY. |
| | |
| | 19) NOTE: PLEASE BE SURE TO SUBMIT MINIMUM WIND LOAD |
| | CALCULATIONS FOR LIGHT POLES. THE STRUCTURAL DESIGN |
| | REVIEW WILL BE DONE BY THE STRUCTURAL REVIEWER. |
| | THIS MAY BE DONE AS A PROVISO HOWEVER NEEDS BASIC |
| | DESIGN ON PLANS FOR OTHER TRADES. |
| | ** (SHOWS 140MPH ON ELECTRICAL ONLY) |
| | |
| | 20) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE NEW PROPOSED MTS. |
| | NEC 110.3,90.7, 702.6 |
| | FBC 106.1.2 |
| | |
| | 21) NOTE: PLEASE BE SURE THE MINIMUM LEVELS FOR HORNS, |
| | STROBES AND HORN/STROBES ARE ON PLANS FOR ADA |
| | COMPLIANCE PER FBC 11-4.28.1, .2 AND .3.. |
| | |
| | 22) NOTE: PLEASE SEE RISER WHICH SHOWS THE SERVICE MAIN |
| | DISCONNECT YET THE PLANS DO NOT SHOW THIS LOCATED ON |
| | THE OUTSIDE OF THE BUILDING ON SITE PLANS, POWER ETC. |
| | PLEASE BE SURE TO INCLUDE ON PLANS. |
| | 230.70, 230.71, 230.72, 110.26, 240.24 ETC |
| | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | CLARITY. |
| | |
| | 23) NOTE: PLEASE SEE THE MAIN SERVICE DISCONNECT IS NOT |
| | RATED FOR THE SERVICE AS SHOWN. THE MAIN DISTRIBUTION |
| | PANEL IS SHOWN AS 1000AMPS, WITH A LOAD IN THE 900AMP |
| | RANGE YET THE SERVICE MAIN DISCONNECT IS SHOWN AT |
| | 600AMPS.ALL EQUIPMENT SHALL BE RATED FOR THE LOAD |
| | SERVED. |
| | THIS IS NOT PERMITTED. |
| | 230.70, 230.76, 230.79 |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| | |
| | 24) NOTE: PLEASE SEE THE NOTE TO SEE THE GROUNDING |
| | ELECTRODE SYSTEM DETAILS FOR SERVICE NOTES TO SEE E201 |
| | YET E201 DOES NOT CONTAIN ANY GROUNDING ELECTRODE |
| | SYSTEM DETAILS. |
| | ** CHECK SHEET NUMBERS. |
| | |
| | 25) NOTE: PLEASE KNOW AS NOTED ABOVE FOR ENERGY |
| | CALCULATIONS. THE *FUTURE* LIGHT FIXTURE SHALL HAVE AN |
| | ASSUMPTION IN THE CALCULATIONS FOR ENERGY COMPLIANCE AS |
| | WELL AS ASSUMPTIONS IN THE LOAD CALCULATIONS. |
| | NEC 220.12, 220.42, FBC 13-415.2.ABC.1.1, .1.2 AND |
| | .1.3. |
| | |
| | 26) NOTE:THE PLANS NOTES THE KITCHEN EQUIPMENT WILL |
| | NOT BE PART OF THE SCOPE HOWEVER WHAT ABOUT THE |
| | ELECTRICAL FOR WALLS ETC? |
| | PLEASE CLARIFY AS IF ANY RECEPTACLES ETC WILL BE |
| | INSTALLED BEFORE THE PROJECT IS ENDED MUST BE SHOWN IN |
| | CALCULATIONS, ON PLANS ETC. |
| | 310.16, 240, 220, ETC |
| | FBC 106.1.1, 106.1.2, 106.3.5.1.2 |
| | |
| | 27) NOTE: PLEASE SEE 422.13 AS ANY STORAGE TYPE WATER |
| | HEATER IS CONSIDERED A*CONTINUOUS LOAD* UNDER THE 2005 |
| | NEC. THIS REQUIRES THE LOAD TO BE SHOWN AND FIGURED AT |
| | 125%. |
| | |
| | 28) NOTE: PLEASE SEE THE PLANS ARE MISSING THE REQUIRED |
| | DEDICATE CIRCUITS FOR THE ELEVATOR EQUIPMENT ROOM. THE |
| | PLANS SHOW THE LIGHTING BEING CIRCUITED TO OTHER LIGHTS |
| | INSIDE THE BUILDING WHICH IS NOT PERMITTED PER |
| | 620.23(A)(B). |
| | PLEASE ALSO INDICATE THAT THE MINIMUM LEVEL OF LIGHTING |
| | IN THE PIT MEETS THE 5FT CANDLES MINIMUM. |
| | ASME A17.1-2004, SAFETY CODE FOR ELEVATORS AND |
| | ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX) |
| | AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE |
| | EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE. |
| | |
| | 29) NOTE: PLEASE SEE FBC 3006.2 AS DEDICATE AIR |
| | CONDITIONING IS REQUIRED IN THE ELEVATOR EQUIPMENT |
| | ROOMS. THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE |
| | BY OTHER TRADE REVIEWERS. |
| | |
| | 30) NOTE: PLEASE SEE 620.23C AS THE ELEVATOR EQUIPMENT |
| | ROOM IS ALSO MISSING THE REQUIRED DEDICATE GFI |
| | RECEPTACLE. THIS MAY BE ONE THE SAME CIRCUIT AS THE |
| | LIGHTS IN THIS ROOM. |
| | |
| | 31) NOTE: AS NOTED ABOVE WITH RESPECT TO ALL FIXTURES |
| | ON PLANS NEEDING TO COORDINATE WITH THE FIXTURE LEGEND. |
| | THE LIGHT FIXTURE SHOWN ON THE LIGHTING PLANS INDICATES |
| | THE LIGHT AS AN *T2E* FIXTURE YET THE LEGEND DOES NOT |
| | INCLUDE THIS. |
| | PLEASE BE SURE THE FIXTURE IN THE ELEVATOR EQUIPMENT |
| | ROOM CONTAINS SOME SORT OF BATTERY BACK UP LIGHT |
| | FIXTURE AS WELL AS OTHER ELECTRICAL ROOMS. IT IS |
| | ASSUMED THE *E* ON THE PLANS IS FOR AN EMERGENCY BACK |
| | UP BALLAST HOWEVER CAN NOT CONFIRM. |
| | NEC 700.12F, 700.16, LS 101, 7.8, 7.9 |
| | |
| | 32) NOTE: PLEASE BE SURE TO COORDINATE THE ELECTRICAL |
| | CONDUITS SHOWN ON ES101 AS THESE ARE SHOWN TO GO FROM |
| | THE FPL TRANSFORMER TO THE INSIDE ELECTRICAL ROOM AND |
| | NOT TO THE MAIN DISCONNECT AS SHOWN ON RISER. THIS WAS |
| | ALSO NOTED ON NOTE #22ABOVE WITH RESPECT TO SHOWING |
| | LOCATION. |
| | 230.70, 300.5 ETC |
| | FBC 106.1.1 FOR CLARITY. |
| | |
| | 33) NOTE: PLEASE SEE PANEL 2LA WHICH SHOWS ON RISER A |
| | 40AMP FEED YET THE PANEL BASED ON THE PANEL SCHEDULE |
| | AND BASED ON THE LOADS EXCEEDS THIS OVER CURRENT |
| | PROTECTION. LOAD IS 70 PLUS AMPS. |
| | PLEASE SEE THAT ALL EQUIPMENT SHALL BE RATED FOR LOAD |
| | SERVED. |
| | PLEASE ALSO SEE AS BASED ON RISER THESE ARE SHOWN AS |
| | 1/0 CONDUCTORS ON A 40AMP BREAKER. |
| | THIS SEEMS TO BE A MISPRINT OF OVER CURRENT PROTECTION |
| | NEED |
| | 240, 408, 310, ETC |
| | PLEASE BE SURE TO SEE MDP SCHEDULE AS BREAKER IS SHOWN |
| | AS 125AMPS. |
| | FBC 106.1.1 FOR COORDINATION AND CLARITY |
| | |
| | 34) NOTE: PLEASE SEE MDP SHOWS A PANEL 1KA YET RISER |
| | DOES NOT SHOW ANY 1KA PANEL. |
| | PLEASE SEE RISER SHOWS A1LK, YET NOT LISTED ON THE |
| | MDP. ARE THESE PANELS THE SAME BUT MISLABLED? |
| | 408.4 |
| | FBC 106.1.1. |
| | |
| | 35) NOTE: PLEASE VERIFY THE LINEAR FT SHOWN ON THE |
| | PANELS FOR VOLTAGE DROP. IT IS UNCLEAR HOW THE TVSS |
| | BREAKERS ARE SHOWING 10816FT, AND OTHERS SHOWS 1082 FT |
| | AND 541 FT. |
| | PLEASE BE SURE TO SEE FBC 13-413.1.ABC.1.1 AND .1.2 AND |
| | PROVIDE ACTUAL WORST CASE VOLTAGE DROP. |
| | |
| | 36) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2. PLEASE |
| | PROVIDE THE WORDING AS STATED IN THE FBC ON PLANS IN |
| | NOTES. |
| | THIS WAS CONFIRMED ON A STATE LEVEL THE INTENT OF THE |
| | CODE IS FOR THE PLANS CONTAIN THE WORDING AS STATED IN |
| | THE SECTIONS. |
| | |
| | 37) NOTE: PLEASE COMPLETE CIRCUITS ON DETAIL 2 ON |
| | E301. |
| | 408.4, 240.4, 310.16ETC |
| | FBC 106.1.1 |
| | |
| | 38) NOTE: PLEASE SEE E402 WHICH STATES THE FPL |
| | TRANSFORMER AS 225KVA YET THE SITE PLAN SHOWS 100KVA. |
| | PLEASE COORDINATE. |
| | FBC 106.1.1 FOR CLARITY OF PLANS. |
| | |
| | 39) NOTE: PLEASE SEE THE ELEVATORCAB LIGHTS WHICH |
| | SHOWS 2-#8 AWG ON A 1-POLE 20AMP BREAKER. HOW IS THIS |
| | POSSIBLE? |
| | PLEASE SEE 430, 310.16, 240.4 ETC 110.3. |
| | |
| | 40) NOTE: PLEASE SEE THE RISER AS THIS SHOWS A 125AMP |
| | BREAKER/OVER CURRENT PROTECTION FEEDING A 100AMP RATED |
| | DISCONNECT. |
| | 110.3, 90.7 ETC |
| | FBC 106.1.1 FOR CLARITY. |
| | |
| | 41) NOTE: PLEASE SEE RISER NOTES THE CONTRACTOR IS |
| | RESPONSIBLE TO OBTAIN THE ACTUAL AVAILABLE FAULT |
| | CURRENT AND MAKE ADJUSTMENTS. |
| | PLEASE KNOW THIS IS THE RESPONSIBILITY OF THE DESIGNER |
| | OF THE ELECTRICAL SYSTEM NOT THE CONTRACTOR FOR BASE |
| | DESIGN. THE CONTRACTOR MOST CERTAINLY WILL NEED TO |
| | VERIFY THE TRANSFORMER ETC FROM THE UTILITY IS |
| | INSTALLED BASED ON INFORMATION FROM THE UTILITY. ANY |
| | CHANGE IN THE ACTUAL SIZE, AND IMPEDANCE RATING OF THE |
| | UNIT WILL NEED TO BE GIVEN TO THE ENGINEER IN CASE ANY |
| | EQUIPMENT NEEDS TO BE ADJUSTED. |
| | PLEASE SEE 110.9 AND ADJUST NOTES. |
| | FAC 61G15-33.001, .003 FOR THE ENGINEER. |
| | |
| | |
| | 42) NOTE: BASED ON THE TYPE OF COMMENTS AND THE AMOUNT |
| | OF COMMENTS ABOVE ONE SET OF ELECTRICAL PLANS ALONG |
| | WITH THE PARTIAL ENERGY CALCULATIONS MAY BE RETAINED BY |
| | THIS OFFICE. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |