Plan Review Details - Permit 08050759
Plan Review Stops For Permit 08050759
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-04 Cont ID  
Sent By shill Date 2008-08-04 Time 16:54 Rev Time 0.00
Received By shill Date 2008-08-04 Time 16:54 Sent To  
Notes
2008-08-04 16:56:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 14.DECLARE GOVERNING CODE, INCLUDING 2007
 REVISIONS/SUPPLEMENTS.
  
 S1, "STANDARD BUILDING FBC 2001" DECLARED.PLEASE
 REVISE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-19 Cont ID  
Sent By shill Date 2008-06-19 Time 09:03 Rev Time  
Received By shill Date 2008-06-18 Time 14:44 Sent To  
Notes
2008-06-18 16:09:47****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 PLAN REVIEW IN PROGRESS
  
 1.SHEET A1, IDENTIFY THE PROPOSED SHED ON THE SITE
 PLAN.THE SITE PLAN SHOULD IDENTIFY ALL STRUCTURES AND
 PROPOSED STRUCTURES ("PROPOSED SHED" RATHER THAN "THIS
 PROJECT").
  
 2.SHEET S1, CLARIFY WINDOW / DOOR INSTALLATION
 CHARTS.PROVIDE CALCULATIONS; NOT CLEAR HOW YOU'VE
 ARRIVED AT THESE FASTENING PATTERNS.DOOR AND WINDOW
 FASTENING SHOULD BE INCLUDED IN THE PRODUCT APPROVAL
 AND SHOULD BE BASED ON TESTING.PROVIDE A BUCK DETAIL.
 BUCK ATTACHMENT IS SPECIFIED BUT IS THIS A 1IN OR 2IN
 BUCK?
  
 3.S1, PLAN STATES TO GROUT CELLS, SPECIFY CONCRETE
 STRENGTH.
  
 4.SEE DETAIL 7 A3; THIS DETAIL SPECIFIES INSULATION
 BASED ON ENERGY CALCS.NO ENERGY CALCS SUBMITTED.
  
 5.A2 STATES THAT SHOPS ARE TO BE PROVIDED TO OWNER /
 ARCHITECT.WHO IS THE ARCHITECT ON THIS PROJECT?
  
 6.S1 STATES THAT OWNER IS RESPONSIBLE TO "MAKE
 PROVISIONS" IF SOIL BEARING PRESSURE IS LESS THAN 2500.
 HOW WILL THIS BE ACCOMPLISHED?IF THIS IS AN AREA OF
 QUESTIONABLE SOILS, PROVIDE A SOILS INVESTIGATION
 REPORT. FBC1802.
  
 7.DETAIL 6-S1 SPECIFIES A RAKE BEAM.CLARIFY
 LOCATION.
  
 8.DETAIL 2 S1, ROOF FRAMING PLAN, PROVIDE MORE
 SPECIFIC DETAIL, SUCH AS MATERIAL USED.I DO NOT
 UNDERSTAND THE PLAN - IT STATES:
  
 4" DECK WITH 1 #5 EVERY 12" EACH WAY TOP
  
 THIS APPEARS TO BE A CONCRETE DECK, AND IN ANOTHER
 DETAIL SHOWN GRAPHICALLY AS A STEEL DECK POURED WITH
 CONCRETE, BUT IN ANOTHER DETAIL AN EMBEDDED WOOD TRUSS
 ANCHOR IS SHOWN.SEE FBC*106, PLANS ARE TO BE OF
 SUFFICIENT CLARITY AND DETAIL TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF WORK PROPOSED AND SHOW IN DETAIL
 THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE,
 ETC.
  
 9.DETAIL 5 S1, SPECIFY NUMBER OF #5 BARS.THERE ARE
 TWO OPTIONS, BUT NOT CLEAR WHAT DIMENSION THE OPTION
 REFERS TO (DEPTH, WIDTH. LENGTH?).
  
 10.DETAIL 1 A2 INCLUDES SECTION MARKER 1-A4, UNABLE TO
 LOCATE SHEET A4.
  
 11.DETAIL 7 A3 SPECIFIES FIRE RETARDANT TREATED LUMBER.
 PLEASE CLARIFY WHY THIS IS BEING REQUIRED FOR WHAT
 APPEARS TO BE AN R3 SHED.
  
 12.PROVIDE A CODE SUMMARY; DECLARE OCCUPANCY FBC
 CHAPTER 3.THE PLANS APPEAR TO SHOW A CONCRETE ROOF,
 FIRE RETARDANT TREATED LUMBER, THEREFORE APPEARS TO BE
 A COMMERCIAL APPLICATION.
  
 13. DECLARE WIND DESIGN CRITERIA FBC R 301 (WIND SPEED,
 EXPOSURE CLASSIFICATION, COMPONENT AND CLADDING
 PRESSURES).
  
 14.DECLARE GOVERNING CODE, INCLUDING 2007
 REVISIONS/SUPPLEMENTS.
  
 15.SHEET S1 NOTE 3, CLARIFY.NO "C1" IS SHOWN ON THE
 PLAN, ARE COLUMNS NECESSARY ON A STRUCTURE OF THIS
 SIZE?
  
 16.DETAIL 6-S1 SPECIFIES SIMPSON LPTA1.FLORIDA
 STATE OR LOCAL PRODUCT APPROVAL REQUIRED.I WAS UNABLE
 TO LOCATE THIS ANCHOR ON THE SIMPSON WEBSITE; USP MAKES
 AN LPTA (BUT NOT LPTA1).THE USP PRODUCT IS AN
 EMBEDDED WOOD TRUSS ANCHOR.OTHER DETAILS SHOW A
 CONCRETE ROOF DECK.
  
 17.SHEET S1, NOTE 4, REFERSZ TO TRUSSES BUT TRUSSES
 ARE NOT SPECIFIED IN ANY OF THE DETAILS ON THE PLAN.
  
 18.DETAILS 5 AND 6, SHEET S1, WALL SECTION SHOULD BE
 CONTINUOUS FROM FOOTING THROUGH THE ROOF.
  
 19.SHEET A2, DOOR SCHEDULE DOES NOT MAKE SENSE.FOR
 INSTANCE, NOTES COLUMN STATES 6'8", TYPE IS I.WHAT IS
 I?
  
 20.DETAIL 7-A3, THE ROOF DECK IS SHOWN AS CONCRETE;
 "CONCRETE SLAB/TIE BM SYSTEM".THIS WOULD REQUIRE
 ENGINEERING.
  
 21.BUILDING SECTION 5-A3, APPEARS TO SHOW A DRYWALL
 CEILING.PROVIDE A WALL SECTION, FOUNDATION THROUGH
 THE ROOF, AND INCLUDE ALL COMPONENTS.THE VARIOUS
 DETAILS PROVIDED ARE INCOMPLETE.A CEILING IS NOT
 SHOWN ANYWHERE ELSE ON THE PLAN.THIS SECTION ALSO
 APPEARS TO SHOW A METAL/CONCRETE DECK.SEE OTHER
 COMMENTS; ROOF DECK CONSTRUCTION IS NOT CLEAR.
  
 22.DECLARE ROOF LOADS, FBC*106.
  
 23.A SET HAS BEEN RETAINED.WHEN RESUBMITTING,
 PLEASE SUBMIT TWO COMPLETE SETS OF PLANS.
  
 24.A ROOF PERMIT HAS BEEN APPLIED FOR (OWNER/BUILDER
 SIGNED ROOFING CONTRACTOR LINE AND A PERMIT NUMBER HAS
 BEEN GENERATED).ALL INFORMATION REQURIED FOR ROOFING
 IS REQUIRED AT THIS TIME.INCLUDE PRODUCT APPROVAL,
 INDICATE APPROVED ASSEMBLY, SPECIFY ENHANCED FASTENING
 IF APPLICABLE FOR ZONES 2 AND 3.THIS CAN BE SUBMITTED
 UNDER SEPARATE PERMIT WITH SEPARATE FEES, AND THE ROOF
 PERMIT WILL BE VOIDED.IF THE ROOF PERMIT IS ISSUED AT
 THIS TIME, ALL INFORMATION REQUIRED TO SHOW CODE
 COMPLIANCE IS REQUIRED.
  
 23. SEE FBC R 704, STUCCO IS SHOWN TO GRADE.HOW WILL
 YOU ADDRESS TERMITE INFESTATION?
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-15 Cont ID  
Sent By adarroug Date 2008-07-15 Time 11:38 Rev Time 0.00
Received By adarroug Date 2008-07-15 Time 11:38 Sent To Z
Notes
2008-07-15 11:38:24TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-19 Cont ID  
Sent By shill Date 2008-06-19 Time 09:20 Rev Time 0.00
Received By shill Date 2008-05-30 Time 11:16 Sent To  
Notes
2008-05-30 11:16:25TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status F Date 2008-07-18 Cont ID  
Sent By mcruz Date 2008-07-18 Time 15:51 Rev Time 0.00
Received By mcruz Date 2008-07-18 Time 15:47 Sent To I
Notes
2008-07-18 15:45:48**ZONING FAILED - 2ND RESUB**
  
 ***REPEAT COMMENT***
  
 1.PLEASE PROVIDE ALL RESPONSES IN WRITING .
  
 2.PLEASE PROVIDE TWO COPIES OF SURVEY.
  
 3.INDICATE ON THE SITE PLAN THE DISTANCE OF
 SEPERATION FROM SHED TO HOUSE.PURSUANT TO SEC.
 94-304(B)(3) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS, THE BUILDING SEPARATION OF ACCESSORY
 STRUCTURES COVERED WITH A SOLID ROOF SHALL BE LOCATED
 NO CLOSER THAN SIX (6) FEET TO THE PRINCIPAL
 STRUCTURE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME REGARDING ANY QUESTIONS YOU MAY HAVE.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING
 (561) 822-1444 OR (561) 805-6720
 [email protected]
  
  
 \\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\
 \\\\\\\\\\\
  
 PREVIOUS COMMENT:
  
 REVIEWED AND FAILED ON 6/2/08
  
 ***FAILED***
  
 1) PROVIDE TWO (2) COPIES OF ALL SUBMITTED DOCUMENTS
 (SUVEY).
  
 2)ON THE SITE PLAN, INDICATE THE SEPARATION DISTANCE
 FROM THE PROPSED SHED TO THE EXISTING PRINCIPAL
 STRUCTURE.NOTE:MUST MAINTAIN A MINIMUM OF SIX (6)
 FEET.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-02 Cont ID  
Sent By choops Date 2008-06-02 Time 09:20 Rev Time 0.00
Received By choops Date 2008-06-02 Time 09:20 Sent To B
Notes
2008-06-02 09:23:02***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF ALL SUBMITTED DOCUMENTS
 (SURVEYS).
  
 2)ON THE SITE PLAN, INDICATE THE SEPARATION DISTANCE
 FROM THE PROPOSED SHED TO THE EXISTING PRINCIPAL
 STRUCTURE.NOTE:MUST MAINTAIN A MINIMUM OF SIX (6)
 FEET.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "B" - MISC. 2