Plan Review Details - Permit 08050701
Plan Review Stops For Permit 08050701
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-06 Cont ID  
Sent By adarroug Date 2008-06-06 Time 11:12 Rev Time 0.00
Received By adarroug Date 2008-06-06 Time 11:12 Sent To P
Notes
2008-06-06 11:13:13TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-30 Cont ID  
Sent By mperson Date 2008-05-30 Time 14:34 Rev Time 0.00
Received By mperson Date 2008-05-29 Time 10:29 Sent To PC
Notes
2008-05-29 10:29:44TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-06-09 Cont ID  
Sent By mperson Date 2008-06-09 Time 10:50 Rev Time 0.00
Received By mperson Date 2008-06-09 Time 10:50 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-05-30 Cont ID  
Sent By mperson Date 2008-05-30 Time 14:11 Rev Time 0.00
Received By mperson Date 2008-05-30 Time 14:11 Sent To I
Notes
2008-05-30 14:34:12PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE VALUE ON THE PERMIT APPLICATION IS LOW. THE
 VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIALS. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF A NATIONAL
 CONSTRUCTION COST ANALYSIS (MARSHALL-SWIFT, MEANS,
 ECT...) ADJUST THE VALUE AT THE PERMIT CLERK'S DESK AND
 PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. THE
 SUBMITTEDCOPY OF THE SIGNED CONRACT BY BOTH PARTIES
 (CONTRACTOR AND CUSTOMER) IS $10,800.00 AND THE PERMIT
 APPLICATION SHOULD REFLECT THAT VALUE. PER (W.P.B. AS
 AMENDED) SECTION 108.3 BUILDING PERMIT VALUATION. NOTE:
 CONTRACTOR CAN CHOOSE TO "DONATE" HIS TIME AND
 MATERIAL, HOWEVER THE PERMIT VALUE SHALL REFLECT THE
 TOTAL COST OF THE JOB.
  
 2. THE SUBMITTED DRAWING IS NOT INDICATING THE
 REQUIRED AUTOMATIC IRRIGATION CONTROLLER AND RAIN
 SENSOR. PLEASE DO THIS ON THE RESUBMITTAL. PER FLORIDA
 STATUTES, SECTION 373.62.
  
 3. THE PLANS ARE INDICATING THE IRRIGATION WATER
 SOURCE AS BEING CLEAR LAKE. NOTE: A "REVOCABLE PERMIT
 AND LICENSE TO USE PUBLIC PROPERTY FOR LAKE WATER
 IRRIGATION ONLY" IS REQUIRED. PLEASE REFERENCE THE
 ATTACHED COPIES OF THE "REVOCABLE PERMIT PROCEDURES"
 AND CONTACT VICKY GALTON @ (561) 822-1285 FOR
 ASSISTANCE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]