Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-07-24 Cont ID  
Sent By mwennerg Date 2008-07-24 Time 09:47 Rev Time 0.00
Received By mwennerg Date 2008-07-24 Time 09:47 Sent To  
Notes
2008-07-24 09:48:48PLANS APPROVED AND STAMPED: UL CERTIFICATION REQUIRED,
 SYSTEM TO BE CLASS A OR FULLY ADDRESSABLE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-10 Cont ID  
Sent By mwennerg Date 2008-06-10 Time 13:34 Rev Time 0.00
Received By mwennerg Date 2008-06-10 Time 13:34 Sent To  
Notes
2008-06-10 13:45:47***DENIED***
  
 1) PLANS SHALL MEET THE REQUIREMENTS OF SEC. 106.1.3 IN
 THE AMENDMENTS TO THE 2004 FBC, AND SHALL BE DRAWN TO A
 MINIMUM OF 1/8 INCH SCALE. SOME AREAS DIFFICULT TO
 READ.
  
 2) DOCUMENTS TO INCLUDE SPEC/CUT SHEETS, PRODUCT
 APPROVALS, CALCULATIONS ETC. SHALL NOT BE ATTACHED TO
 PLANS.
  
 3) FIRE ALARM SYSTEM TO BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE. UL CERTIFICATE WILL BE REQUIRED PRIOR
 TO FINAL INSPECTION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-10 Cont ID  
Sent By adarroug Date 2008-07-10 Time 11:44 Rev Time 0.00
Received By adarroug Date 2008-07-10 Time 11:44 Sent To FIRE
Notes
2008-07-10 11:44:31TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-10 Cont ID  
Sent By mwennerg Date 2008-06-10 Time 13:47 Rev Time 0.00
Received By mwennerg Date 2008-05-29 Time 10:53 Sent To  
Notes
2008-05-29 10:53:58TO "F" BOX