Plan Review Details - Permit 08050665
Plan Review Stops For Permit 08050665
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-05-29 Cont ID  
Sent By lursu Date 2008-05-29 Time 13:39 Rev Time 0.00
Received By lursu Date 2008-05-29 Time 13:39 Sent To  
Notes
2008-05-29 13:40:20THIS PERMIT IS ATTACHED TO THE MAIN ADDRESS SINCE THE
 WORK IS TO DIVIDE THE SPACE INTO TWO SPACES.
  
 QUESTIONS/COMMENTS:
 LACRAMIOARA URSU, MA ,GISP
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
2008-05-23 14:33:39PLEASECREATE ADDR OR UNITFOR 2ND SPACE, (WILL BE
 RENTED OUT TO A FUTURE UNKNOWN TENANT). 1ST SPACE IS
 ALREADY OCCUPIED BY ANOTHER TENANT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2009-06-04 Cont ID  
Sent By shill Date 2009-06-04 Time 09:05 Rev Time 0.00
Received By shill Date 2009-06-04 Time 09:05 Sent To E
Notes
2009-06-04 09:07:25PROVISO - AT CONTRACTOR'S RISK (SUBJECT TO REVIEW OF
 ENERGY CALCS, OTHER TRADES)
  
 ENERGY CALCS
  
 PANELS (4" RATHER THAN 5")
  
 SHEETS S.03, S.04, S.05, S.12A
  
 BUILDING PLANS SENT TO CONTRACTOR (@ CONTR RISK PENDING
 REMAINING REVIEW BY OTHER TRADES, EN CALCS)
 ENERGY CALCS ROUTED TO ELECTRIC
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2009-05-07 Cont ID  
Sent By shill Date 2009-05-07 Time 11:36 Rev Time 0.00
Received By shill Date 2009-05-07 Time 11:36 Sent To  
Notes
2009-05-07 11:40:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. ALL CHANGES TO THE PLANS/SPECS ARE REVISIONS; PLEASE
 PAY FEE.
  
 2. HOW HAS ENERGY EFFICIENCY BEEN AFFECTED BY THIS
 CHANGE? WEREN'T ENERGY CALCS PREPARED WHICH SPECIFIED
 AN R VALUE BASED ON 5" THICK PANELS?
  
 AS DISCUSSED, THIS REVISION CAN BE ISSUED WITH PROVISOS
 [SUBMIT REVISED ENERGY CALCS (IF NECESSARY), AT
 CONTRACTOR'S RISK] IF THIS ISSUE IS INVESTIGATED BY DOR
 AND DETERMINED THAT ENERGY EFFICIENCY MEETS MINIMUM
 REQUIREMENTS OF FBC13.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-02-23 Cont ID  
Sent By shill Date 2009-02-23 Time 09:52 Rev Time 0.00
Received By shill Date 2009-02-23 Time 09:52 Sent To  
Notes
2009-02-23 09:54:37REVISION, INCREASE SCOPE OF WORK (FEES ADJUSTED)
 S00, S01, S02, S03, S04, S05, S06, S07, S08, S09, S10,
 S11,S12,S12A, S13, S14 DATED 2/12/9
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2009-02-19 Cont ID  
Sent By shill Date 2009-02-19 Time 06:56 Rev Time 0.00
Received By shill Date 2009-02-19 Time 06:56 Sent To  
Notes
2009-02-19 07:47:52****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. AS THIS IS A THRESHOLD BUILDING, PLEASE INCLUDE THE
 STATEMENT REQUIRED BY FBC*109.3.6.4.4 AND
 FS553.79(7)(D).
  
 2. INCORRECT ASCE REFERENCE WAS PROVIDED ON THE
 DECORATIVE BAHAMA SHUTTER CALCULATIONS, FBC35. PLEASE
 EITHER REVISE OR PROVIDE A LETTER ADDRESSING THIS
 ISSUE. THIS CAN BE A PROVISO ITEM (AT CONTRACTOR'S
 RISK).
  
 3. PLEASE NOTE THAT THE PRODUCT APPROVALS FOR THE METAL
 DOORS (SINGLE AND DOUBLE) DO NOT PROVIDE WATER
 INFILTRATION. THIS IS INFORMATIONAL ONLY.
  
 4. THE DOUBLE DOOR PRODUCT APPROVAL SUBMITTED COMPLIES
 WITH PRESSURES FOR ZONE 4 ONLY. THIS REVISION WILL BE
 ISSUED WITH THE PROVISO THAT PRODUCT APPROVALS ARE
 REQUIRED FOR DOUBLE DOORS WHICH MEET THE DP REQUIREMENT
 OF +61.63/-80.23.
  
 5. SHEET S02, ONE SET, HAS NOT BEEN SEALED.
  
 IF POSSIBLE, PLEASE HAVE THE EOR CONTACT ME TO MAKE AN
 APPOINTMENT TO RESOLVE ISSUES #1 AND #5. ONCE THESE
 STATUTORY REQUIREMENTS ARE ADDRESSED, OTHER ITEM(S) CAN
 BE PROVISO ITEMS. THE SHEETS ARE STAMPED PENDING
 RESOLUTION OF #1 AND #5.
  
 6. THE RUSKIN (LOUVER) PRODUCT APPROVAL IS TO BE
 APPROVED BY DESIGNER OF RECORD FBC*106.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-10-02 Cont ID  
Sent By shill Date 2008-10-02 Time 10:02 Rev Time 0.00
Received By shill Date 2008-10-02 Time 10:02 Sent To  
Notes
2008-10-02 10:03:44REVISION, SHEETS S0, S1, S2
 ***PROVISO***AT RISK, STRUCTURAL ONLY
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-09-23 Cont ID  
Sent By shill Date 2008-09-23 Time 15:01 Rev Time 0.00
Received By shill Date 2008-09-23 Time 15:01 Sent To  
Notes
2008-09-23 15:07:51****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE ISSUED PERMIT WAS FOR A DEMISING WALL TO
 SEPARATE THE TWO TENANTS. THE REVISION SUBMITTED REFERS
 TO A MEZZANINE, AND SOILS REFERS TO TWO MEZZANINES.
 CODE COMPLIANCE FOR MEZZANINES MUST BE DEMONSTRATED
 THROUGH FLOOR PLANS AND LIFE SAFETY PLANS, FBC CHAPTER
 10. NOT ENOUGH INFORMATION WAS PROVIDED TO SHOW CODE
 COMPLIANCE. ALSO PROVIDE A CODE SUMMARY; BUILDING TYPE
 FBC6, BUILDING HEIGHT AND AREA FBC5, SPRINKLER
 INFORMATION, OCCUPANCY CLASSIFICATION FBC 3 AND AREA
 PER OCCUPANCY. SHOW INFORMATION REGARDING THE PROPOSED
 MEZZANINES ON THE PLAN, FBC CHAPTER 5, FBC CHAPTER 10,
 FBC*106 (COMPLIANCE WITH AREA RESTRICTIONS, STRUCTURAL
 REQUIREMENTS, EXITING PROVISIONS).
  
 ALTERNATIVELY, MEZZANINE STRUCTURAL DETAILS CAN BE
 REMOVED FROM THE PLAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-22 Cont ID  
Sent By shill Date 2008-08-22 Time 09:07 Rev Time 0.00
Received By shill Date 2008-08-22 Time 09:07 Sent To  
Notes
2008-11-04 10:47:36AT RISK PERMIT
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-07-21 Cont ID  
Sent By shill Date 2008-07-21 Time 15:44 Rev Time 0.00
Received By shill Date 2008-07-21 Time 15:44 Sent To  
Notes
2008-07-21 15:50:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.THIS PERMIT WILL BE ISSUED AS AN AT RISK PERMIT.
 CODE COMPLIANCE TO BE SHOWN ON THE TENANT BUILDOUT.
  
 2.THE SEAL IS TO INCLUDE A DATE, FS481.PLEASE
 INCLUDE.TO AVOID REVIEWS BY OTHER TRADES, PLEASE DATE
 THE SHEET WHICH HAS ALREADY BEEN REVIEWED AND STAMPED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-02 Cont ID  
Sent By shill Date 2008-06-02 Time 08:52 Rev Time 0.00
Received By shill Date 2008-06-02 Time 08:52 Sent To E
Notes
2008-06-02 09:23:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.ALL INFORMATION REQUIRED BY FAC61G1-15.23.002,003
 IS TO BE ON EACH SHEET (CERTIFICATE OF AUTHORIZATION).
  
 2.DECLARE GOVERNING CODE, INCLUDING 2007
 REVISIONS/SUPPLEMENTS.
  
 3.DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 4.INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6,
 BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION,
 OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY.
 INCLUDE EXISTING OCCUPANCY CLASSIFICATION AS WELL AS
 PROPOSED OCCUPANCY CLASSIFICATION.
  
 5.OTHER ITEMS/REVIEWS MAY BE REQUIRED (FOR EXAMPLE,
 SEE FBC PLUMBING TABLE 403.1).CODE COMPLIANCE CANNOT
 BE DETERMINED DUE TO INSUFFICIENT INFORMATION.PLEASE
 PROVIDE INFORMATION REGARDING EXISTING DRINKING
 FOUNTAINS OR WATER COOLERS, BATHROOMS, SAFETY SHOWERS,
 ETC.
  
 6.THE PLAN PROVIDED DOES NOT APPEAR TO SHOW THE
 ENTIRE TENANT SPACE.PLEASE PROVIDE AN OVERALL PLAN.
  
 7.EXITING AND EXITING REQUIREMENTS ARE NOT CLEAR.
 PLEASE SHOW EXIT SIGNS AND MAKE NOTE OF ACCESSIBLE
 EXITS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-08-15 Cont ID  
Sent By btrobaug Date 2008-08-15 Time 13:32 Rev Time 0.00
Received By btrobaug Date 2008-08-15 Time 13:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-07-08 Cont ID  
Sent By btrobaug Date 2008-07-08 Time 08:40 Rev Time 0.00
Received By btrobaug Date 2008-07-08 Time 07:42 Sent To  
Notes
2008-07-08 08:40:44 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW:
  
 1} 240.24(B) OCCUPANCY EACH OCCUPANT SHALL HAVE READY
 ACCESS TO ALL OVERCURRENT DEVICES PROTECTING THE
 CONDUCTORS SUPPLYING THAT OCCUPANCY.INDICATE COMPLIANCE
 WITH THIS ARTICLE**THE TENANT PANEL MUST BE IN THE
 TENANT SPACE OR A COMMON AREA. INDICATE LOCATION.
  
 5} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8
 (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE
 SAME ON PLANS.
  
 PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-03 Cont ID  
Sent By btrobaug Date 2008-06-03 Time 13:35 Rev Time 0.00
Received By btrobaug Date 2008-06-03 Time 12:27 Sent To  
Notes
2008-06-03 13:23:56THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 240.24(B) OCCUPANCY EACH OCCUPANT SHALL HAVE READY
 ACCESS TO ALL OVERCURRENT DEVICES PROTECTING THE
 CONDUCTORS SUPPLYING THAT OCCUPANCY.INDICATE COMPLIANCE
 WITH THIS ARTICLE
  
 2} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 3} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED.
  
 4} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE
 OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8).
  
 5} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8
 (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE
 SAME ON PLANS.
  
 PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-08-11 Cont ID  
Sent By mawillia Date 2008-08-11 Time 15:35 Rev Time 0.00
Received By mawillia Date 2008-08-11 Time 13:36 Sent To  
Notes
2008-08-11 15:36:17*****APPROVED*****
  
 SINGLE PLAN SHEET T.01 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-07-21 Cont ID  
Sent By mwennerg Date 2008-07-21 Time 15:10 Rev Time 0.00
Received By mwennerg Date 2008-07-21 Time 15:10 Sent To B
Notes
2008-07-21 15:12:04OK FOR CONSTRUCTION OF DEMISING WALL ONLY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-03 Cont ID  
Sent By mawillia Date 2008-06-03 Time 15:39 Rev Time 0.00
Received By mawillia Date 2008-06-03 Time 15:13 Sent To  
Notes
2008-06-03 15:39:36*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE PREMISES AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.WILL THE STRUCTURE BE OCCUPIED DURING THE SCOPE OF
 WORK?
  
 4.SHOW THE LOCATION OF THE EXIT LIGHTS AND EMERGENCY
 FOR THE NEW FLOOR PLAN.
  
 5.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 6.SPECIFY THE NEW INTERIOR WALL FINISH MATERIAL IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-02-17 Cont ID  
Sent By adarroug Date 2009-02-17 Time 13:11 Rev Time 0.00
Received By shill Date 2009-02-17 Time 13:11 Sent To B
Notes
2009-02-17 14:39:36TO M CRUZ DESK (NEEDS J ROACH ZONING REVIEW)
2009-02-17 13:23:53TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-25 Cont ID  
Sent By adarroug Date 2008-09-25 Time 10:59 Rev Time 0.00
Received By adarroug Date 2008-09-25 Time 10:59 Sent To B
Notes
2008-09-25 11:01:24TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-18 Cont ID  
Sent By adarroug Date 2008-09-18 Time 11:09 Rev Time 0.00
Received By adarroug Date 2008-09-18 Time 11:09 Sent To B
Notes
2008-09-18 11:09:34TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-28 Cont ID  
Sent By adarroug Date 2008-07-28 Time 14:13 Rev Time 0.00
Received By adarroug Date 2008-07-28 Time 12:48 Sent To  
Notes
2008-08-07 16:56:32TO "BOB"#4
2008-07-28 14:14:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-01 Cont ID  
Sent By adarroug Date 2008-07-01 Time 14:19 Rev Time 0.00
Received By adarroug Date 2008-07-01 Time 14:19 Sent To  
Notes
2008-07-01 14:23:10TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-06 Cont ID  
Sent By adarroug Date 2008-06-06 Time 09:15 Rev Time 0.00
Received By adarroug Date 2008-06-03 Time 13:34 Sent To  
Notes
2008-06-03 13:35:24TO BOB BOARD #8 PER R.B../WRT.
2008-05-23 15:53:26TO "MISC" BOX#1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-07-02 Cont ID  
Sent By tgordon Date 2008-07-02 Time 09:46 Rev Time 0.20
Received By tgordon Date 2008-07-02 Time 09:46 Sent To  
Notes
2008-07-02 09:47:29DEMISING WALL ONLY. NO MECHANICAL PLANS SUBMITTED, AND
 NO MECHANICAL PERMIT NUMBER APPLIED FOR AT THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-03 Cont ID  
Sent By tgordon Date 2008-06-03 Time 14:30 Rev Time 0.25
Received By tgordon Date 2008-06-03 Time 14:30 Sent To  
Notes
2008-06-03 14:38:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SHOW HOW THE SPACES ARE MEETING THE
 VENTILATION REQUIREMENTS OF 2004 FBC/M 401.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status N Date 2008-07-03 Cont ID  
Sent By mperson Date 2008-07-03 Time 11:37 Rev Time 0.00
Received By mperson Date 2008-07-03 Time 11:37 Sent To  
Notes
2008-07-03 11:41:30DEMISING WALL ONLY. NO PLUMBING PLANS SUBMITTED, AND NO
 PLUMBING PERMIT NUMBER APPLIED FOR AT THIS TIME. PER
 COMMENT RESPONE FROM DESIGN PROFESSIONAL "FUTURE TENANT
 PLANS WILL PROVIDE ALL THIS INFORMATION".

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-06-05 Cont ID  
Sent By mperson Date 2008-06-05 Time 08:09 Rev Time 0.00
Received By mperson Date 2008-06-05 Time 08:09 Sent To  
Notes
2008-06-05 08:44:57PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. ALL INFORMATION REQUIRED BY FAC61G1-15.23.002, 003
 IS REQUIRED TO BE ON EACH SHEET (PRINTED NAME AND
 LICENSE NUMBER OF THE PERSON WHO SIGNED AND SEALED PLAN
 SHEETS AND THE ARCHITECTURAL FIRMS CERTIFICATE OF
 AUTHORIZATION)
  
 2. DECLARE GOVERNING CODE. (FBC-2004 WITH 2007
 REVISIONS)
  
 3. DECLARE LEVEL OF ALTERATION. PER FBC-2004 EXISTING
 BUILDING CHAPTER 3.
  
 4. NOTE: SHEET T.01 DOES NOT INDICATE EXISTING OR
 PROPOSED PLUMBING FIXTURES. PLEASE CLARIFY THIS ON THE
 RESUBMITTAL PER FBC-2004 TABLE PLUMBING, TABLE 403.1
 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES FOR A
 WAREHOUSE (S-1 OR S-2 OCCUPANCY) ARE AS FOLLOWS.
  
 WATER CLOSETS MALE/FEMALE = 1 PER 100.
  
 LAVATORIES MALE/FEMALE = 1 PER 100.
  
 BATHTUBS/SHOWERS = SEE SECTION 411. (EMERGENCY SHOWER
 AND EYEWASH STATIONS) WHAT TYPES OF MATERIALS ARE IN
 THE WAREHOUSE? THIS MAY REQUIRE A EMERGENCY SHOWER AND
 EYEWASH STATION. PLEASE CLARIFY THIS ON THE
 RESUBMITTAL.
  
 DRINKING FOUNTAINS = 1 PER 1000.
  
 SERVICE SINK = 1.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2009-02-17 Cont ID  
Sent By jroach Date 2009-02-17 Time 18:52 Rev Time 0.00
Received By jroach Date 2009-02-17 Time 18:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2008-06-06 Cont ID  
Sent By choops Date 2008-06-06 Time 13:43 Rev Time 0.00
Received By choops Date 2008-06-06 Time 13:43 Sent To  
Notes
2008-06-06 13:44:09*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.