| Plan Review Stops For Permit 08050665 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2008-05-29 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2008-05-29 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2008-05-29 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2008-05-29 13:40:20 | THIS PERMIT IS ATTACHED TO THE MAIN ADDRESS SINCE THE | | | WORK IS TO DIVIDE THE SPACE INTO TWO SPACES. | | | | | | QUESTIONS/COMMENTS: | | | LACRAMIOARA URSU, MA ,GISP | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] | | 2008-05-23 14:33:39 | PLEASECREATE ADDR OR UNITFOR 2ND SPACE, (WILL BE | | | RENTED OUT TO A FUTURE UNKNOWN TENANT). 1ST SPACE IS | | | ALREADY OCCUPIED BY ANOTHER TENANT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2009-06-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-06-04 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-06-04 |
Time |
09:05 |
Sent To |
E |
|
| Notes |
| 2009-06-04 09:07:25 | PROVISO - AT CONTRACTOR'S RISK (SUBJECT TO REVIEW OF | | | ENERGY CALCS, OTHER TRADES) | | | | | | ENERGY CALCS | | | | | | PANELS (4" RATHER THAN 5") | | | | | | SHEETS S.03, S.04, S.05, S.12A | | | | | | BUILDING PLANS SENT TO CONTRACTOR (@ CONTR RISK PENDING | | | REMAINING REVIEW BY OTHER TRADES, EN CALCS) | | | ENERGY CALCS ROUTED TO ELECTRIC | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2009-05-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-05-07 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-05-07 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2009-05-07 11:40:36 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. ALL CHANGES TO THE PLANS/SPECS ARE REVISIONS; PLEASE | | | PAY FEE. | | | | | | 2. HOW HAS ENERGY EFFICIENCY BEEN AFFECTED BY THIS | | | CHANGE? WEREN'T ENERGY CALCS PREPARED WHICH SPECIFIED | | | AN R VALUE BASED ON 5" THICK PANELS? | | | | | | AS DISCUSSED, THIS REVISION CAN BE ISSUED WITH PROVISOS | | | [SUBMIT REVISED ENERGY CALCS (IF NECESSARY), AT | | | CONTRACTOR'S RISK] IF THIS ISSUE IS INVESTIGATED BY DOR | | | AND DETERMINED THAT ENERGY EFFICIENCY MEETS MINIMUM | | | REQUIREMENTS OF FBC13. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2009-02-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-02-23 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-02-23 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2009-02-23 09:54:37 | REVISION, INCREASE SCOPE OF WORK (FEES ADJUSTED) | | | S00, S01, S02, S03, S04, S05, S06, S07, S08, S09, S10, | | | S11,S12,S12A, S13, S14 DATED 2/12/9 | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2009-02-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-02-19 |
Time |
06:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-02-19 |
Time |
06:56 |
Sent To |
|
|
| Notes |
| 2009-02-19 07:47:52 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. AS THIS IS A THRESHOLD BUILDING, PLEASE INCLUDE THE | | | STATEMENT REQUIRED BY FBC*109.3.6.4.4 AND | | | FS553.79(7)(D). | | | | | | 2. INCORRECT ASCE REFERENCE WAS PROVIDED ON THE | | | DECORATIVE BAHAMA SHUTTER CALCULATIONS, FBC35. PLEASE | | | EITHER REVISE OR PROVIDE A LETTER ADDRESSING THIS | | | ISSUE. THIS CAN BE A PROVISO ITEM (AT CONTRACTOR'S | | | RISK). | | | | | | 3. PLEASE NOTE THAT THE PRODUCT APPROVALS FOR THE METAL | | | DOORS (SINGLE AND DOUBLE) DO NOT PROVIDE WATER | | | INFILTRATION. THIS IS INFORMATIONAL ONLY. | | | | | | 4. THE DOUBLE DOOR PRODUCT APPROVAL SUBMITTED COMPLIES | | | WITH PRESSURES FOR ZONE 4 ONLY. THIS REVISION WILL BE | | | ISSUED WITH THE PROVISO THAT PRODUCT APPROVALS ARE | | | REQUIRED FOR DOUBLE DOORS WHICH MEET THE DP REQUIREMENT | | | OF +61.63/-80.23. | | | | | | 5. SHEET S02, ONE SET, HAS NOT BEEN SEALED. | | | | | | IF POSSIBLE, PLEASE HAVE THE EOR CONTACT ME TO MAKE AN | | | APPOINTMENT TO RESOLVE ISSUES #1 AND #5. ONCE THESE | | | STATUTORY REQUIREMENTS ARE ADDRESSED, OTHER ITEM(S) CAN | | | BE PROVISO ITEMS. THE SHEETS ARE STAMPED PENDING | | | RESOLUTION OF #1 AND #5. | | | | | | 6. THE RUSKIN (LOUVER) PRODUCT APPROVAL IS TO BE | | | APPROVED BY DESIGNER OF RECORD FBC*106. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-10-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-10-02 |
Time |
10:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-10-02 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2008-10-02 10:03:44 | REVISION, SHEETS S0, S1, S2 | | | ***PROVISO***AT RISK, STRUCTURAL ONLY | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2008-09-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-09-23 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-09-23 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2008-09-23 15:07:51 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. THE ISSUED PERMIT WAS FOR A DEMISING WALL TO | | | SEPARATE THE TWO TENANTS. THE REVISION SUBMITTED REFERS | | | TO A MEZZANINE, AND SOILS REFERS TO TWO MEZZANINES. | | | CODE COMPLIANCE FOR MEZZANINES MUST BE DEMONSTRATED | | | THROUGH FLOOR PLANS AND LIFE SAFETY PLANS, FBC CHAPTER | | | 10. NOT ENOUGH INFORMATION WAS PROVIDED TO SHOW CODE | | | COMPLIANCE. ALSO PROVIDE A CODE SUMMARY; BUILDING TYPE | | | FBC6, BUILDING HEIGHT AND AREA FBC5, SPRINKLER | | | INFORMATION, OCCUPANCY CLASSIFICATION FBC 3 AND AREA | | | PER OCCUPANCY. SHOW INFORMATION REGARDING THE PROPOSED | | | MEZZANINES ON THE PLAN, FBC CHAPTER 5, FBC CHAPTER 10, | | | FBC*106 (COMPLIANCE WITH AREA RESTRICTIONS, STRUCTURAL | | | REQUIREMENTS, EXITING PROVISIONS). | | | | | | ALTERNATIVELY, MEZZANINE STRUCTURAL DETAILS CAN BE | | | REMOVED FROM THE PLAN. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-08-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-08-22 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-08-22 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2008-11-04 10:47:36 | AT RISK PERMIT | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-07-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-07-21 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-07-21 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2008-07-21 15:50:32 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.THIS PERMIT WILL BE ISSUED AS AN AT RISK PERMIT. | | | CODE COMPLIANCE TO BE SHOWN ON THE TENANT BUILDOUT. | | | | | | 2.THE SEAL IS TO INCLUDE A DATE, FS481.PLEASE | | | INCLUDE.TO AVOID REVIEWS BY OTHER TRADES, PLEASE DATE | | | THE SHEET WHICH HAS ALREADY BEEN REVIEWED AND STAMPED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-06-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-06-02 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-06-02 |
Time |
08:52 |
Sent To |
E |
|
| Notes |
| 2008-06-02 09:23:08 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.ALL INFORMATION REQUIRED BY FAC61G1-15.23.002,003 | | | IS TO BE ON EACH SHEET (CERTIFICATE OF AUTHORIZATION). | | | | | | 2.DECLARE GOVERNING CODE, INCLUDING 2007 | | | REVISIONS/SUPPLEMENTS. | | | | | | 3.DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3. | | | | | | 4.INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6, | | | BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, | | | OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY. | | | INCLUDE EXISTING OCCUPANCY CLASSIFICATION AS WELL AS | | | PROPOSED OCCUPANCY CLASSIFICATION. | | | | | | 5.OTHER ITEMS/REVIEWS MAY BE REQUIRED (FOR EXAMPLE, | | | SEE FBC PLUMBING TABLE 403.1).CODE COMPLIANCE CANNOT | | | BE DETERMINED DUE TO INSUFFICIENT INFORMATION.PLEASE | | | PROVIDE INFORMATION REGARDING EXISTING DRINKING | | | FOUNTAINS OR WATER COOLERS, BATHROOMS, SAFETY SHOWERS, | | | ETC. | | | | | | 6.THE PLAN PROVIDED DOES NOT APPEAR TO SHOW THE | | | ENTIRE TENANT SPACE.PLEASE PROVIDE AN OVERALL PLAN. | | | | | | 7.EXITING AND EXITING REQUIREMENTS ARE NOT CLEAR. | | | PLEASE SHOW EXIT SIGNS AND MAKE NOTE OF ACCESSIBLE | | | EXITS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-08-15 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-08-15 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-08-15 |
Time |
13:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-07-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-07-08 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-07-08 |
Time |
07:42 |
Sent To |
|
|
| Notes |
| 2008-07-08 08:40:44 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS | | | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | THESE COMMENTS ARE FROM THE PREVIOUS REVIEW: | | | | | | 1} 240.24(B) OCCUPANCY EACH OCCUPANT SHALL HAVE READY | | | ACCESS TO ALL OVERCURRENT DEVICES PROTECTING THE | | | CONDUCTORS SUPPLYING THAT OCCUPANCY.INDICATE COMPLIANCE | | | WITH THIS ARTICLE**THE TENANT PANEL MUST BE IN THE | | | TENANT SPACE OR A COMMON AREA. INDICATE LOCATION. | | | | | | 5} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8 | | | (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE | | | SAME ON PLANS. | | | | | | PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE | | | SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-06-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-03 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-03 |
Time |
12:27 |
Sent To |
|
|
| Notes |
| 2008-06-03 13:23:56 | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS | | | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} 240.24(B) OCCUPANCY EACH OCCUPANT SHALL HAVE READY | | | ACCESS TO ALL OVERCURRENT DEVICES PROTECTING THE | | | CONDUCTORS SUPPLYING THAT OCCUPANCY.INDICATE COMPLIANCE | | | WITH THIS ARTICLE | | | | | | 2} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN | | | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF | | | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE | | | EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE | | | PLAN. | | | | | | 3} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS | | | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES | | | FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3 | | | FBC AS AMENDED. | | | | | | 4} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE | | | OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8). | | | | | | 5} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8 | | | (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE | | | SAME ON PLANS. | | | | | | PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE | | | SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-08-11 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-08-11 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-08-11 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2008-08-11 15:36:17 | *****APPROVED***** | | | | | | SINGLE PLAN SHEET T.01 STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-07-21 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-07-21 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-07-21 |
Time |
15:10 |
Sent To |
B |
|
| Notes |
| 2008-07-21 15:12:04 | OK FOR CONSTRUCTION OF DEMISING WALL ONLY |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-06-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-06-03 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-06-03 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2008-06-03 15:39:36 | *****DENIED***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE PREMISES AT THE END OF EACH SHIFT | | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.WILL THE STRUCTURE BE OCCUPIED DURING THE SCOPE OF | | | WORK? | | | | | | 4.SHOW THE LOCATION OF THE EXIT LIGHTS AND EMERGENCY | | | FOR THE NEW FLOOR PLAN. | | | | | | 5.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 6.SPECIFY THE NEW INTERIOR WALL FINISH MATERIAL IN | | | TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2009-02-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-17 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-02-17 |
Time |
13:11 |
Sent To |
B |
|
| Notes |
| 2009-02-17 14:39:36 | TO M CRUZ DESK (NEEDS J ROACH ZONING REVIEW) | | 2009-02-17 13:23:53 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-09-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-25 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-25 |
Time |
10:59 |
Sent To |
B |
|
| Notes |
| 2008-09-25 11:01:24 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-09-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-18 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-18 |
Time |
11:09 |
Sent To |
B |
|
| Notes |
| 2008-09-18 11:09:34 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-07-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-28 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-28 |
Time |
12:48 |
Sent To |
|
|
| Notes |
| 2008-08-07 16:56:32 | TO "BOB"#4 | | 2008-07-28 14:14:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-07-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-01 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-01 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2008-07-01 14:23:10 | TO "BOB"#4 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-06-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-06 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-03 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2008-06-03 13:35:24 | TO BOB BOARD #8 PER R.B../WRT. | | 2008-05-23 15:53:26 | TO "MISC" BOX#1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2008-07-02 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-07-02 |
Time |
09:46 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2008-07-02 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2008-07-02 09:47:29 | DEMISING WALL ONLY. NO MECHANICAL PLANS SUBMITTED, AND | | | NO MECHANICAL PERMIT NUMBER APPLIED FOR AT THIS TIME. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-06-03 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-06-03 |
Time |
14:30 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2008-06-03 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2008-06-03 14:38:18 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLEASE SHOW HOW THE SPACES ARE MEETING THE | | | VENTILATION REQUIREMENTS OF 2004 FBC/M 401.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2008-07-03 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-07-03 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-07-03 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2008-07-03 11:41:30 | DEMISING WALL ONLY. NO PLUMBING PLANS SUBMITTED, AND NO | | | PLUMBING PERMIT NUMBER APPLIED FOR AT THIS TIME. PER | | | COMMENT RESPONE FROM DESIGN PROFESSIONAL "FUTURE TENANT | | | PLANS WILL PROVIDE ALL THIS INFORMATION". |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-06-05 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-06-05 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-06-05 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2008-06-05 08:44:57 | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. ALL INFORMATION REQUIRED BY FAC61G1-15.23.002, 003 | | | IS REQUIRED TO BE ON EACH SHEET (PRINTED NAME AND | | | LICENSE NUMBER OF THE PERSON WHO SIGNED AND SEALED PLAN | | | SHEETS AND THE ARCHITECTURAL FIRMS CERTIFICATE OF | | | AUTHORIZATION) | | | | | | 2. DECLARE GOVERNING CODE. (FBC-2004 WITH 2007 | | | REVISIONS) | | | | | | 3. DECLARE LEVEL OF ALTERATION. PER FBC-2004 EXISTING | | | BUILDING CHAPTER 3. | | | | | | 4. NOTE: SHEET T.01 DOES NOT INDICATE EXISTING OR | | | PROPOSED PLUMBING FIXTURES. PLEASE CLARIFY THIS ON THE | | | RESUBMITTAL PER FBC-2004 TABLE PLUMBING, TABLE 403.1 | | | MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES FOR A | | | WAREHOUSE (S-1 OR S-2 OCCUPANCY) ARE AS FOLLOWS. | | | | | | WATER CLOSETS MALE/FEMALE = 1 PER 100. | | | | | | LAVATORIES MALE/FEMALE = 1 PER 100. | | | | | | BATHTUBS/SHOWERS = SEE SECTION 411. (EMERGENCY SHOWER | | | AND EYEWASH STATIONS) WHAT TYPES OF MATERIALS ARE IN | | | THE WAREHOUSE? THIS MAY REQUIRE A EMERGENCY SHOWER AND | | | EYEWASH STATION. PLEASE CLARIFY THIS ON THE | | | RESUBMITTAL. | | | | | | DRINKING FOUNTAINS = 1 PER 1000. | | | | | | SERVICE SINK = 1. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2009-02-17 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2009-02-17 |
Time |
18:52 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2009-02-17 |
Time |
18:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2008-06-06 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-06-06 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-06-06 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2008-06-06 13:44:09 | *ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE | | | VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE | | | IMPROVEMENT VALUE. |
|
|