Plan Review Details - Permit 08050638
Plan Review Stops For Permit 08050638
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-07-17 Cont ID  
Sent By dpalmer Date 2009-07-17 Time 15:44 Rev Time 0.00
Received By dpalmer Date 2009-07-17 Time 15:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-09-12 Cont ID  
Sent By jwitmer Date 2008-09-12 Time 10:12 Rev Time 1.55
Received By jwitmer Date 2008-09-12 Time 10:12 Sent To  
Notes
2008-09-12 10:26:45BUILDING PLAN REVIEW
 PERMIT: 08050638
 ADD: 901 45TH ST
 CONT: JT ELECTRIC
 TEL: (561) 723-5956
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SEPT.12,2008
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B): PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
 SITE PLAN FOR QUANTUM HOUSE PLEASE PROVIDE
 IDENTIFICATION AS TO WHO DESIGNED SITE PLAN NAME AND
 TELEPHONE NUMBER. 10106.1.1.
  
 1C) COMPLIED.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
 HILLMAN ENGINEERING DOES NOT PROVIDE UPDATES UNDER THE
 2004 FBC 2007 SUPPLEMENTS.
  
 2) COMPLIED.
  
 3) HILLMAN ENGINEERING PLANS ARE COPIES NOT SIGNED NOR
 SEALED. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 4) HILLMAN ENGINEERING PLAN INDICATES THE USE OF A
 FEATHER LITE GENERATOR PAD PLEASE PROVIDE DOCUMENTATION
 FOR USE FOR A GENERATOR. ADDITIONAL INFORMATION
 REQUIRED.106.1.2.
 4A) PLANS DO NOT INDICATE IF THE PAD AND GENERATOR ARE
 TO BE SHOP MOUNTED PAD OR FIELD MOUNTED PAD.
  
 4B) PLANS ARE NOT HIGHLIGHTED AS TO WHICH PAD WILL BE
 INSTALLED, NOTE KEEP IN MIND THE REQUIRED 4" EDGE
 DISTANCE IN DETERMINING PAD SIZE.
  
 5) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-06 Cont ID  
Sent By jwitmer Date 2008-06-06 Time 16:43 Rev Time 1.22
Received By jwitmer Date 2008-06-06 Time 16:43 Sent To  
Notes
2008-06-06 16:50:47BUILDING PLAN REVIEW
 PERMIT: 08050638
 ADD: 901 45TH ST
 CONT: JT ELECTRIC
 TEL: (561) 723-5956
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) PLEASE CORRECT INFORMATION AS TO THE OWNER OF RECORD
 ICOVER OF THE PERMIT APPLICATION SEE TAX ROLE.
  
 3) HILLMAN ENGINEERING PLANS ARE COPIES NOT SIGNED NOR
 SEALED. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 4) HILLMAN ENGINEERING PLAN INDICATES THE USE OF A
 FEATHER LITE GENERATOR PAD PLEASE PROVIDE DOCUMENTATION
 FOR USE FOR A GENERATOR. ADDITIONAL INFORMATION
 REQUIRED.106.1.2.
  
 5) PROVIDE A SIE PLAN WHICH WILL LOCATE THE GENERATOR
 AND A NAMED CITY STREET, MAY OR MAY NO BE LOCATED IN A
 FLOOD ZONE WITH OUT THIS KNOWN INFORMATION, 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-07-17 Cont ID  
Sent By dpalmer Date 2009-07-17 Time 15:44 Rev Time 0.00
Received By dpalmer Date 2009-07-17 Time 15:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-09-15 Cont ID  
Sent By dpalmer Date 2008-09-15 Time 15:03 Rev Time 0.00
Received By dpalmer Date 2008-09-15 Time 15:03 Sent To  
Notes
2008-09-15 15:03:42 
 ** DENIED **
  
 1) NOTE: PERMIT APPLICATION FOR PRIME CONTRACTOR NEEDS
 TO BE REVISED FOR INSTALLATION OF THE GENERATOR. FS
 527.02
  
 2) NOTE: PERMIT APPLICATION STATES 35KW GENERATOR
 HOWEVER PLANS AND SUPPORTING DOCUMENTS STATE 30KW.
 PLEASE COORDINATE APPLICATION AND ALL DOCUMENTS.
 NEC 2005
 FBC 106.1.1, 106.5 FOR COORDINATION AND CLARITY OF
 PLANS AND RECORD PLANS.
  
 3) NOTE: PLEASE KNOW AT THIS TIME THE RISER AND SCOPE
 OF WORK IS CONFUSING TO THIS REVIEWER. THE PLANS/RISER
 CONTAINS NOTES WHICH CALLS FOR A 35KW 3-PHASE GENERATOR
 AND ALSO CALLS FOR A SINGLE-PHASE 30KW GENERATOR.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-18 Cont ID  
Sent By dpalmer Date 2008-06-18 Time 13:40 Rev Time 0.00
Received By dpalmer Date 2008-06-18 Time 13:40 Sent To  
Notes
2008-06-18 13:40:32** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE FS 527.02 AS THE PRIME CONTRACTOR
 SHALL CONTAIN STATE REQUIRED LICENSING TO SELL,
 INSTALLED GAS AND NATURAL GAS APPLIANCES.
 PLEASE SUPPLY THE LICENSING UNDER THE ELECTRICAL
 INFORMATION AS THE PRIME CONTRACTOR IS LISTED AS AN
 ELECTRICAL CONTRACTOR WHICH MAY NOT APPLY FOR PERMIT,
 SELLOR INSTALL THESE TYPES OF GENERATORS UNLESS
 LICENSED.
 PLEASE KNOW THE GAS CONTRACTOR MAY BE THE PRIME
 CONTRACTOR IF NOT LICENSED.
 THIS HAS BEEN CONFIRMED WITH THE LICENSING BOARD AND ON
 RECENTPHONE AUDITS FROM A STATE LEVEL DEPARTMENT OF
 AGRICULTURE.
  
 2) NOTE: PLEASE LIST THE TYPE OF SYSTEM THIS GENERATOR
 WILL FEED. IS THIS EMERGENCY, LEGALLY REQUIRED OR
 STRICTLY OPTIONAL STAND-BY?
 IF OTHER THAN OPTIONAL STAND-BY, ON-SITE FUEL IS
 REQUIRED.
 700.12.B3, 701.11B3
  
 3) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED ATS.
 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE SUBMIT MINIMUM QUALITY OF PLANS WHICH
 DOES NOT CONTAIN HAND WRITTEN PLANS IN PEN AND
 WHITE-OUT.
 FBC 106.1
  
 5) NOTE: PLEASE SUBMIT THE SPECS/MANUFACTURES CUT
 SHEETS FOR THE GENERATOR WHICH COORDINATES WITH PLANS.
 PLEAS SEE SPECS SUBMITTED IN PACKAGE FOR 45KW
 GENERATOR.
 SPECS NEED TO STATE MINIMUM CLEARANCES AROUND UNIT.
 PLEASE SEE MINIMUM REQUIREMENTS FOR ZONING WAS A WALL
 MAY BE REQUIRED. SHRUBS MAY NOT BE THE ONLY
 REQUIREMENT.
 THE SITE PLANS NEED MORE DETAILS FOR LOCATION, SETBACKS
 AND DIMENSIONS OF ALL EQUIPMENT.
 PLEASE SHOW ALL LOCATIONS OF ELECTRICAL EQUIPMENT AS
 PROPOSED.
 THIS WILL AFFECT ENTIRE SET OF PLANS.
 110.26, 225.31-225.39 ETC WHICH CAN NOT BE VERIFIED AT
 THIS TIME.
  
 6) NOTE: PLEASE SEE THE APPLIED VALUE NEEDS TO BE
 ADJUSTED AS THE SCOPE OF ENTIRE PROJECT WILL INCREASE
 DUE TO WALL ETC.
 FBC 108.3
  
 7) NOTE: PLEASE SEE CHECKLIST AND SEVERAL DOCUMENTS
 SUBMITTED ARE ACTUALLY FROM PALM BEACH COUNTY WHEN
 PROJECT IS LOCATION IN THE CITY OF WEST PALM BEACH.
  
 8) NOTE: PLEASE SEE RISER SHOWS THE NEW EMERGENCY PANEL
 AS 125AMP RATED WITH A 150AMP BREAKER FROM THE
 GENERATOR FEEDING THIS PANEL WHICH CONTAINS 125AMP
 RATED LUGS ETC.
 ALSO SHOWS #1 WHICH ARE NOT RATED FOR 150AMPS. MAY NOT
 USE 310.15B6 AND MUST USE 310.16 FOR SIZING
 CONDUCTORS.
  
 ** AS SEVERAL ITEMS ARE NOT SHOWN AT THIS TIME, REVIEW
 FOR COMPLETE CODE COMPLIANCE CAN NOT BE DONE.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-07-27 Cont ID  
Sent By mawillia Date 2009-07-27 Time 13:23 Rev Time 0.00
Received By mawillia Date 2009-07-27 Time 13:03 Sent To B
Notes
2009-07-27 13:23:12*****APPROVED*****
  
 THE APPROPIATE PLAN SHEETS (2) WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-10-01 Cont ID  
Sent By mwennerg Date 2008-10-01 Time 13:06 Rev Time 0.00
Received By mwennerg Date 2008-10-01 Time 12:59 Sent To  
Notes
2008-10-01 13:06:12***DENIED***
  
 SOME COMMENTS ARE TAKEN DIRECTLY FROM THE FIRST FIRE
 REVIEW:
  
 1) OK
  
 2) OK
  
 3) OK
  
 4) THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE WITH
 NFPA 110, 2002 EDITION.
  
 5) DEPENDING UPON LOCATION OF THE EQUIPMENT, SAFEGUARDS
 AGAINST MECHANICAL DAMAGE MAY BE REQUIRED AND SHALL BE
 ILLUSTRATED.
  
 6) EQUIPMENT USING GAS AND RELATED GAS PIPING SHALL BE
 IN ACCORDANCE WITH NFPA 54.
  
  
 A RESPONSE LETTER INDICATING HOW AND WHERE ON THE PLANS
 THE COMMENT WAS ADDRESSED WOULD HELP TO EXPEDITE THE
 PLAN REVIEW PROCESS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-30 Cont ID  
Sent By mawillia Date 2008-06-30 Time 16:33 Rev Time 0.00
Received By mawillia Date 2008-06-30 Time 16:04 Sent To  
Notes
2008-06-30 16:29:33*****DENIED*****
  
  
  
 1.PROVIDE A SITE PLAN SHOWING THE LOCATION OF
 GENERATOR WITH RESPECT TO PROPERTY LINES, PUBLIC WAYS,
 AND BUILDING(S) ON THE PROPERTY.
  
 2.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE TO THE SAID PROPERTY OR THE
 VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES, ETC) .
  
 3.PLEASE INDICATE THE USAGE OF THE STATIONARY
 GENERATOR AS FOR EMERGENCY USE OR STANDBY POWER.
  
 4.THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE WITH
 NFPA 110, 2002 EDITION.
  
 5.DEPENDING UPON LOCATION OF THE EQUIPMENT,
 SAFEGUARDS AGAINST MECHANICAL DAMAGE MAY BE REQUIRED
 AND SHALL BE ILLUSTRATED.
  
 6.EQUIPMENT USING GAS AND RELATED GAS PIPING SHALL BE
 ACCORDANCE WITH NFPA 54.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-07-14 Cont ID  
Sent By kstevens Date 2009-07-14 Time 15:14 Rev Time 0.00
Received By kstevens Date 2009-07-14 Time 15:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-09-10 Cont ID  
Sent By mperson Date 2008-09-10 Time 08:19 Rev Time 0.00
Received By mperson Date 2008-09-10 Time 08:19 Sent To  
Notes
2008-09-10 09:13:01GAS PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND
 WITH THE PREVIOUS GAS PLAN REVIEW COMMENTS AS WELL AS
 TE DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
 NEW COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS
 REVIEW COMMENTS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS. PER FBC-
 FUEL GAS CODE SECTION 401.1 SCOPE.
 NOTE: THERE WERE NO CORRESPONDING LENGTHS FOR THE CUT
 SECTIONS OF PIPE INDICATED ON GAS ISOMETRIC DRAWING.
  
 **NO COMMENT RESPONSE FROM THE DESIGNER AND THE COMMENT
 WAS NOT ADDRESSED. THE RESUBMITTED GAS ISOMETRIC STILL
 DOES NOT INDICATE CORRESPONDING LENGTHS TO ALL CUT
 SECTIONS OF PIPE. THE ONLY CUT SECTIONS OF PIPE WITH
 CORRESPONDING LENGTHS BEING INDICATED IS THE
 UNDERGROUND PE PIPING. WHAT ARE THE CORRESPONDING
 LENGTHS TO THE ABOVE GROUND PIPING? PER SECTION 401.1
 SCOPE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC- FUEL GAS
 CODE SECTION 401.1 SCOPE.
 NOTE: THE ONLY PIPING MATERIAL INDICATED WAS FOR THE
 UNDERGROUND PIPING. WHAT IS THE PIPING MATERIAL FOR THE
 ABOVE GROUND?
  
 **NO COMMENT RESPONSE FROM THE DESIGNER AND THE COMMENT
 WAS PARTIALLY ADDRESSED. WHAT IS THE TYPE AND SIZE OF
 THE PIPING MATERIAL OF THE ABOVE GROUND PIPING AT THE
 METER LOCATION? PER SECTION 401.1 SCOPE.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #1 AND COMPLY.
  
 **NO COMMENT RESPONSE FROM THE DESIGNER AND COMMENT WAS
 NOT ADDRESSED. PLEASE REFERENCE COMMENT #1 AND COMPLY.
  
 4. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
 NOTE: SUBMITTED GAS ISOMETRIC HAS NO SIGNATURES.
  
 **NO COMMENT RESPONSE FROM THE DESIGNER AND COMMENT WAS
 NOT ADDRESSED. THE RESUBMITTED GAS ISOMETRIC DRAWINGS
 DO NOT HAVE ANYONE TAKING RESPONSIBILITY FOR THEM. THE
 PRINTED NAME WITH THE ORIGNAL SIGNATURE OF THE PERSON
 TAKING RESPOSIBILITY FOR THE ISOMETRIC IS STILL
 REQUIRED. PER (W.P.B. AS AMENDED) SECTION 106.3.4.3.
  
 **THE FOLLOWING ARE NEW COMMENTS DUE TO THE RESUBMITTAL
 PACKAGE AND NEW GAS ISOMETRIC.
  
 5. THERE ARE TWO DIFFERENT GENERATOR MANUFACTURE
 SPECIFICATION SHEETS MAKE AND MODEL NUMBERS WITH
 DIFFERENT BTU LOAD CAPACITIES IN THE RESUBMITTAL.
 PLEASE KNOW THAT THIS IS CONFUSING AND UNACCEPTABLE. A
 GENERAC MODEL QT030 WITH A BTU CAPACITY OF 525,000 AND
 A GAURDIAN MODEL #5219 WITH A 412,000 BTU CAPACITY IS
 IN THE RESUBMITTAL. PLEASE CORRELATE THE RESUBMITTAL
 WITH ONLY ONE MAKE AND MODEL OF GENERATOR MANUFACTURE
 SPECIFICATIONS. PER FBC-2004 FUEL GAS SECTION 401.1
 SCOPE.
  
 6. SUBMIT TWO COPIES OF MANUFACTURE SHEETS FOR THE MP
 REGULATORS (2ND STAGE REGULATORS) TO VERIFY COMPLIANCE
 WITH STANDARDS NFPA 54, NFPA 58, AND THE FBC-2004 FUEL
 GAS CODE SEC 402.2. THE MANUFACTURE SHEETS SHALL
 CLEARLY INDICATE THE MP REGULATORS MAKE, MODEL NUMBER,
 BTU LOAD CAPACITY, AND A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY (LISTING EXAMPLES= AGA,
 CSA, UL).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-06-30 Cont ID  
Sent By mperson Date 2008-06-30 Time 09:35 Rev Time 0.00
Received By mperson Date 2008-06-30 Time 09:35 Sent To  
Notes
2008-06-30 09:46:35GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS. PER FBC-
 FUEL GAS CODE SECTION 401.1 SCOPE.
 NOTE: THERE WERE NO CORRESPONDING LENGTHS FOR THE CUT
 SECTIONS OF PIPE INDICATED ON GAS ISOMETRIC DRAWING.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC- FUEL GAS
 CODE SECTION 401.1 SCOPE.
 NOTE: THE ONLY PIPING MATERIAL INDICATED WAS FOR THE
 UNDERGROUND PIPING. WHAT IS THE PIPING MATERIAL FOR THE
 ABOVE GROUND?
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #1 AND COMPLY.
  
 4. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
 NOTE: SUBMITTED GAS ISOMETRIC HAS NO SIGNATURES.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-07-01 Cont ID  
Sent By rmcdouga Date 2009-07-01 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2009-07-01 Time 10:52 Sent To  
Notes
2009-07-01 10:53:18C17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 16:50 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 16:50 Sent To  
Notes
2008-09-03 16:50:18TO "COMM" BD#44

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-30 Cont ID  
Sent By mawillia Date 2008-06-30 Time 16:04 Rev Time 0.00
Received By mawillia Date 2008-05-22 Time 14:20 Sent To  
Notes
2008-05-29 11:25:04TO "COMM" BD#9
2008-05-22 14:20:45WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2009-07-17 Cont ID  
Sent By dpalmer Date 2009-07-17 Time 15:44 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2009-07-17 15:45:11NATURAL GAS, TO BE INSTALLED PER NFPA_37

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-09-11 Cont ID  
Sent By tgordon Date 2008-09-11 Time 08:58 Rev Time 0.30
Received By tgordon Date 2008-09-11 Time 08:58 Sent To  
Notes
2008-09-11 09:05:42PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) TWO DIFFERENT SITE PLANS WERE SUBMITTED, ONE STATING
 THE GENERATOR WILL BE 5 FEET FROM THE BUILDING AND ONE
 STATES 3 FEET FROM THE BUILDING. THE TWO MUST COINCIDE
 PLEASE CORRECT.
  
 2) PLEASE STATE ON PLAN WHAT THE BUILDING IN MADE OF
 (WOOD, CONCRETE, EC.).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-11 Cont ID  
Sent By tgordon Date 2008-06-11 Time 09:51 Rev Time 0.30
Received By tgordon Date 2008-06-11 Time 09:51 Sent To  
Notes
2008-06-11 09:59:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE COMPLY.
  
 2) THE NOTICE OF COMMENCEMENT SUBMITTED LINE #2
 DESCRIPTION OF IMPROVEMENT IS BLANK. PLEASE DESCRIBE
 THE WORK TO BE DONE AND RE-RECORD WITH PALM BEACH
 COUNTY, PER FS 713.13.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2009-07-16 Cont ID  
Sent By lfranco Date 2009-07-15 Time 19:41 Rev Time 0.00
Received By lfranco Date 2009-07-15 Time 19:41 Sent To  
Notes
2009-07-16 19:46:17PLANNING AND ZONING ("P&Z"): **** PASSED WITH PROVISO,
 SCREENING (LANDSCAPING) FOR GENERATOR SHALL BE
 INSTALLED PURSUANT TO PLANS SUBMITTED TO THE P&Z
 DEPARTMENT FOR THE MINOR AMENDMENT TO THE ST. MARY'S
 CSPD- QUANTUM HOUSE PB 1068Z ****
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2008-09-09 Cont ID  
Sent By lfranco Date 2008-09-09 Time 20:45 Rev Time 0.00
Received By lfranco Date 2008-09-09 Time 20:45 Sent To  
Notes
2008-09-09 20:46:21PLANNING AND ZONING **** FAILED, REPEAT COMMENT, DID
 NOT ADDRESS****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THIS PROPERTY IS PART OF THE ST. MARY'S COMMUNITY
 SERVICE PLANNED DEVELOPMENT (CSPD), AN APPLICATION FOR
 A MINOR AMENDMENT TO THE CSPD SHOWING THE PROPOSED
 GENERATOR WILL BE REQUIRED TO BE FILED TO THE PLANNING
 AND ZONING DEPARTMENT AND APPROVED PRIOR TO THE
 BUILDING PERMIT BEING APPROVED. SEE
 HTTP://WWW.CITYOFWPB.COM/PLAN/INDEX.PHP, UNDER
 DEVELOPMENT APPLICATION FOR REQUIREMENTS OF A MINOR PD
 AMENDMENT.
  
 3. PROVIDE ELEVATIONS AND A FLOOR PLAN OF SCREENING AND
 LANDSCAPING DETAIL. INCLUDE WALL HEIGHT, ETC. SCREENING
 ENCLOSURE AND LANDSCAPING SHALL MEET SECTION 94-444 OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS. SCREENING
 WALLS SHALL BE LADSCAPED WITH SHRUBS AND HEDGES PLANTED
 AT TWO-FOOT INTERVALS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-03 Cont ID  
Sent By lfranco Date 2008-06-03 Time 17:53 Rev Time 0.00
Received By lfranco Date 2008-06-03 Time 17:53 Sent To  
Notes
2008-06-03 18:18:02PLANNING AND ZONING **** FAILED ****
  
 1.RESPOND TO COMMENTS IN WRITING.
  
 2. THIS PROPERTY IS PART OF THE ST. MARY'S COMMUNITY
 SERVICE PLANNED DEVELOPMENT (CSPD), AN APPLICATION FOR
 A MINOR AMENDMENT TO THE CSPD SHOWING THE PROPOSED
 GENERATOR WILL BE REQUIRED TO BE FILED TO THE PLANNING
 AND ZONING DEPARTMENT AND APPROVED PRIOR TO THE
 BUILDING PERMIT BEING APPROVED.SEE
 HTTP://WWW.CITYOFWPB.COM/PLAN/INDEX.PHP, UNDER
 DEVELOPMENT APPLICATION FOR REQUIREMENTS OF A MINOR PD
 AMENDMENT.
  
 3.PROVIDE ELEVATIONS AND A FLOOR PLAN OF SCREENING
 AND LANDSCAPING DETAIL.INCLUDE WALL HEIGHT, ETC.
 SCREENING ENCLOSURE AND LANDSCAPING SHALL MEET SECTION
 94-444 OF THE ZONING AND LAND DEVELOPMENT REGULATIONS.
 SCREENING WALLS SHALL BE LADSCAPED WITH SHRUBS AND
 HEDGES PLANTED AT TWO-FOOT INTERVALS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  