Plan Review Details - Permit 08050638
| Plan Review Stops For Permit 08050638 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-07-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-17 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-17 |
Time |
15:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-09-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-12 |
Time |
10:12 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2008-09-12 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2008-09-12 10:26:45 | BUILDING PLAN REVIEW | | | PERMIT: 08050638 | | | ADD: 901 45TH ST | | | CONT: JT ELECTRIC | | | TEL: (561) 723-5956 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SEPT.12,2008 | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B): PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, | | | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR | | | REVIEW FOR PERMIT. 106.1* /2004 SUBMITTAL DOCUMENTS | | | WEST PALM BEACH ADMINISTRATIVE CODE. | | | SITE PLAN FOR QUANTUM HOUSE PLEASE PROVIDE | | | IDENTIFICATION AS TO WHO DESIGNED SITE PLAN NAME AND | | | TELEPHONE NUMBER. 10106.1.1. | | | | | | 1C) COMPLIED. | | | | | | 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF | | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST | | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. | | | HILLMAN ENGINEERING DOES NOT PROVIDE UPDATES UNDER THE | | | 2004 FBC 2007 SUPPLEMENTS. | | | | | | 2) COMPLIED. | | | | | | 3) HILLMAN ENGINEERING PLANS ARE COPIES NOT SIGNED NOR | | | SEALED. PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING | | | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE | | | DOCUMENT. | | | FL ADMIN CODE 61G15-23.002 ENGINEERS | | | | | | 4) HILLMAN ENGINEERING PLAN INDICATES THE USE OF A | | | FEATHER LITE GENERATOR PAD PLEASE PROVIDE DOCUMENTATION | | | FOR USE FOR A GENERATOR. ADDITIONAL INFORMATION | | | REQUIRED.106.1.2. | | | 4A) PLANS DO NOT INDICATE IF THE PAD AND GENERATOR ARE | | | TO BE SHOP MOUNTED PAD OR FIELD MOUNTED PAD. | | | | | | 4B) PLANS ARE NOT HIGHLIGHTED AS TO WHICH PAD WILL BE | | | INSTALLED, NOTE KEEP IN MIND THE REQUIRED 4" EDGE | | | DISTANCE IN DETERMINING PAD SIZE. | | | | | | 5) COMPLIED. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-06-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-06-06 |
Time |
16:43 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2008-06-06 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2008-06-06 16:50:47 | BUILDING PLAN REVIEW | | | PERMIT: 08050638 | | | ADD: 901 45TH ST | | | CONT: JT ELECTRIC | | | TEL: (561) 723-5956 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, | | | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL | | | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A | | | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN | | | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED | | | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS | | | WEST PALM BEACH ADMINISTRATIVE CODE. | | | | | | 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE | | | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN | | | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO | | | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO | | | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION | | | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE | | | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR | | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | | | | 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF | | | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. | | | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS | | | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & | | | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST | | | INSPECTION. | | | | | | 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST | | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. | | | | | | 2) PLEASE CORRECT INFORMATION AS TO THE OWNER OF RECORD | | | ICOVER OF THE PERMIT APPLICATION SEE TAX ROLE. | | | | | | 3) HILLMAN ENGINEERING PLANS ARE COPIES NOT SIGNED NOR | | | SEALED. PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING | | | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE | | | DOCUMENT. | | | FL ADMIN CODE 61G15-23.002 ENGINEERS | | | | | | 4) HILLMAN ENGINEERING PLAN INDICATES THE USE OF A | | | FEATHER LITE GENERATOR PAD PLEASE PROVIDE DOCUMENTATION | | | FOR USE FOR A GENERATOR. ADDITIONAL INFORMATION | | | REQUIRED.106.1.2. | | | | | | 5) PROVIDE A SIE PLAN WHICH WILL LOCATE THE GENERATOR | | | AND A NAMED CITY STREET, MAY OR MAY NO BE LOCATED IN A | | | FLOOD ZONE WITH OUT THIS KNOWN INFORMATION, 106.1.2 | | | ADDITIONAL INFORMATION REQUIRED. | | | | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2009-07-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-17 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-17 |
Time |
15:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-09-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-15 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-15 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2008-09-15 15:03:42 | | | | ** DENIED ** | | | | | | 1) NOTE: PERMIT APPLICATION FOR PRIME CONTRACTOR NEEDS | | | TO BE REVISED FOR INSTALLATION OF THE GENERATOR. FS | | | 527.02 | | | | | | 2) NOTE: PERMIT APPLICATION STATES 35KW GENERATOR | | | HOWEVER PLANS AND SUPPORTING DOCUMENTS STATE 30KW. | | | PLEASE COORDINATE APPLICATION AND ALL DOCUMENTS. | | | NEC 2005 | | | FBC 106.1.1, 106.5 FOR COORDINATION AND CLARITY OF | | | PLANS AND RECORD PLANS. | | | | | | 3) NOTE: PLEASE KNOW AT THIS TIME THE RISER AND SCOPE | | | OF WORK IS CONFUSING TO THIS REVIEWER. THE PLANS/RISER | | | CONTAINS NOTES WHICH CALLS FOR A 35KW 3-PHASE GENERATOR | | | AND ALSO CALLS FOR A SINGLE-PHASE 30KW GENERATOR. | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-06-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-06-18 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-06-18 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2008-06-18 13:40:32 | ** DENIEDREVIEW ** | | | | | | | | | 1) NOTE: PLEASE SEE FS 527.02 AS THE PRIME CONTRACTOR | | | SHALL CONTAIN STATE REQUIRED LICENSING TO SELL, | | | INSTALLED GAS AND NATURAL GAS APPLIANCES. | | | PLEASE SUPPLY THE LICENSING UNDER THE ELECTRICAL | | | INFORMATION AS THE PRIME CONTRACTOR IS LISTED AS AN | | | ELECTRICAL CONTRACTOR WHICH MAY NOT APPLY FOR PERMIT, | | | SELLOR INSTALL THESE TYPES OF GENERATORS UNLESS | | | LICENSED. | | | PLEASE KNOW THE GAS CONTRACTOR MAY BE THE PRIME | | | CONTRACTOR IF NOT LICENSED. | | | THIS HAS BEEN CONFIRMED WITH THE LICENSING BOARD AND ON | | | RECENTPHONE AUDITS FROM A STATE LEVEL DEPARTMENT OF | | | AGRICULTURE. | | | | | | 2) NOTE: PLEASE LIST THE TYPE OF SYSTEM THIS GENERATOR | | | WILL FEED. IS THIS EMERGENCY, LEGALLY REQUIRED OR | | | STRICTLY OPTIONAL STAND-BY? | | | IF OTHER THAN OPTIONAL STAND-BY, ON-SITE FUEL IS | | | REQUIRED. | | | 700.12.B3, 701.11B3 | | | | | | 3) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | | SHEETS FOR THE PROPOSED ATS. | | | 110.3, 90.7 | | | FBC 106.1.2 FOR ADDITIONAL INFORMATION. | | | | | | 4) NOTE: PLEASE SUBMIT MINIMUM QUALITY OF PLANS WHICH | | | DOES NOT CONTAIN HAND WRITTEN PLANS IN PEN AND | | | WHITE-OUT. | | | FBC 106.1 | | | | | | 5) NOTE: PLEASE SUBMIT THE SPECS/MANUFACTURES CUT | | | SHEETS FOR THE GENERATOR WHICH COORDINATES WITH PLANS. | | | PLEAS SEE SPECS SUBMITTED IN PACKAGE FOR 45KW | | | GENERATOR. | | | SPECS NEED TO STATE MINIMUM CLEARANCES AROUND UNIT. | | | PLEASE SEE MINIMUM REQUIREMENTS FOR ZONING WAS A WALL | | | MAY BE REQUIRED. SHRUBS MAY NOT BE THE ONLY | | | REQUIREMENT. | | | THE SITE PLANS NEED MORE DETAILS FOR LOCATION, SETBACKS | | | AND DIMENSIONS OF ALL EQUIPMENT. | | | PLEASE SHOW ALL LOCATIONS OF ELECTRICAL EQUIPMENT AS | | | PROPOSED. | | | THIS WILL AFFECT ENTIRE SET OF PLANS. | | | 110.26, 225.31-225.39 ETC WHICH CAN NOT BE VERIFIED AT | | | THIS TIME. | | | | | | 6) NOTE: PLEASE SEE THE APPLIED VALUE NEEDS TO BE | | | ADJUSTED AS THE SCOPE OF ENTIRE PROJECT WILL INCREASE | | | DUE TO WALL ETC. | | | FBC 108.3 | | | | | | 7) NOTE: PLEASE SEE CHECKLIST AND SEVERAL DOCUMENTS | | | SUBMITTED ARE ACTUALLY FROM PALM BEACH COUNTY WHEN | | | PROJECT IS LOCATION IN THE CITY OF WEST PALM BEACH. | | | | | | 8) NOTE: PLEASE SEE RISER SHOWS THE NEW EMERGENCY PANEL | | | AS 125AMP RATED WITH A 150AMP BREAKER FROM THE | | | GENERATOR FEEDING THIS PANEL WHICH CONTAINS 125AMP | | | RATED LUGS ETC. | | | ALSO SHOWS #1 WHICH ARE NOT RATED FOR 150AMPS. MAY NOT | | | USE 310.15B6 AND MUST USE 310.16 FOR SIZING | | | CONDUCTORS. | | | | | | ** AS SEVERAL ITEMS ARE NOT SHOWN AT THIS TIME, REVIEW | | | FOR COMPLETE CODE COMPLIANCE CAN NOT BE DONE. | | | | | | ** IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT | | | HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2009-07-27 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-07-27 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-07-27 |
Time |
13:03 |
Sent To |
B |
|
| Notes |
| 2009-07-27 13:23:12 | *****APPROVED***** | | | | | | THE APPROPIATE PLAN SHEETS (2) WERE STAMPED, INITIALED, | | | AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-10-01 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-10-01 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-10-01 |
Time |
12:59 |
Sent To |
|
|
| Notes |
| 2008-10-01 13:06:12 | ***DENIED*** | | | | | | SOME COMMENTS ARE TAKEN DIRECTLY FROM THE FIRST FIRE | | | REVIEW: | | | | | | 1) OK | | | | | | 2) OK | | | | | | 3) OK | | | | | | 4) THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE WITH | | | NFPA 110, 2002 EDITION. | | | | | | 5) DEPENDING UPON LOCATION OF THE EQUIPMENT, SAFEGUARDS | | | AGAINST MECHANICAL DAMAGE MAY BE REQUIRED AND SHALL BE | | | ILLUSTRATED. | | | | | | 6) EQUIPMENT USING GAS AND RELATED GAS PIPING SHALL BE | | | IN ACCORDANCE WITH NFPA 54. | | | | | | | | | A RESPONSE LETTER INDICATING HOW AND WHERE ON THE PLANS | | | THE COMMENT WAS ADDRESSED WOULD HELP TO EXPEDITE THE | | | PLAN REVIEW PROCESS. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-06-30 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-06-30 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-06-30 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2008-06-30 16:29:33 | *****DENIED***** | | | | | | | | | | | | 1.PROVIDE A SITE PLAN SHOWING THE LOCATION OF | | | GENERATOR WITH RESPECT TO PROPERTY LINES, PUBLIC WAYS, | | | AND BUILDING(S) ON THE PROPERTY. | | | | | | 2.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE | | | WITH EMERGENCY RESPONSE TO THE SAID PROPERTY OR THE | | | VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE | | | LANES, ETC) . | | | | | | 3.PLEASE INDICATE THE USAGE OF THE STATIONARY | | | GENERATOR AS FOR EMERGENCY USE OR STANDBY POWER. | | | | | | 4.THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE WITH | | | NFPA 110, 2002 EDITION. | | | | | | 5.DEPENDING UPON LOCATION OF THE EQUIPMENT, | | | SAFEGUARDS AGAINST MECHANICAL DAMAGE MAY BE REQUIRED | | | AND SHALL BE ILLUSTRATED. | | | | | | 6.EQUIPMENT USING GAS AND RELATED GAS PIPING SHALL BE | | | ACCORDANCE WITH NFPA 54. | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2009-07-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-07-14 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-07-14 |
Time |
15:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2008-09-10 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-09-10 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-09-10 |
Time |
08:19 |
Sent To |
|
|
| Notes |
| 2008-09-10 09:13:01 | GAS PLAN REVIEW: | | | DENIED **2ND TIME: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND | | | WITH THE PREVIOUS GAS PLAN REVIEW COMMENTS AS WELL AS | | | TE DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | NEW COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS | | | REVIEW COMMENTS. | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS. PER FBC- | | | FUEL GAS CODE SECTION 401.1 SCOPE. | | | NOTE: THERE WERE NO CORRESPONDING LENGTHS FOR THE CUT | | | SECTIONS OF PIPE INDICATED ON GAS ISOMETRIC DRAWING. | | | | | | **NO COMMENT RESPONSE FROM THE DESIGNER AND THE COMMENT | | | WAS NOT ADDRESSED. THE RESUBMITTED GAS ISOMETRIC STILL | | | DOES NOT INDICATE CORRESPONDING LENGTHS TO ALL CUT | | | SECTIONS OF PIPE. THE ONLY CUT SECTIONS OF PIPE WITH | | | CORRESPONDING LENGTHS BEING INDICATED IS THE | | | UNDERGROUND PE PIPING. WHAT ARE THE CORRESPONDING | | | LENGTHS TO THE ABOVE GROUND PIPING? PER SECTION 401.1 | | | SCOPE. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. PER FBC- FUEL GAS | | | CODE SECTION 401.1 SCOPE. | | | NOTE: THE ONLY PIPING MATERIAL INDICATED WAS FOR THE | | | UNDERGROUND PIPING. WHAT IS THE PIPING MATERIAL FOR THE | | | ABOVE GROUND? | | | | | | **NO COMMENT RESPONSE FROM THE DESIGNER AND THE COMMENT | | | WAS PARTIALLY ADDRESSED. WHAT IS THE TYPE AND SIZE OF | | | THE PIPING MATERIAL OF THE ABOVE GROUND PIPING AT THE | | | METER LOCATION? PER SECTION 401.1 SCOPE. | | | | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | NOTE: REFERENCE COMMENT #1 AND COMPLY. | | | | | | **NO COMMENT RESPONSE FROM THE DESIGNER AND COMMENT WAS | | | NOT ADDRESSED. PLEASE REFERENCE COMMENT #1 AND COMPLY. | | | | | | 4. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING | | | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE | | | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE | | | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER | | | SECTION *106.3.4.3. | | | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, | | | THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, | | | SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA | | | STATUTES 481 AND 471 RESPECTIVELY. | | | NOTE: SUBMITTED GAS ISOMETRIC HAS NO SIGNATURES. | | | | | | **NO COMMENT RESPONSE FROM THE DESIGNER AND COMMENT WAS | | | NOT ADDRESSED. THE RESUBMITTED GAS ISOMETRIC DRAWINGS | | | DO NOT HAVE ANYONE TAKING RESPONSIBILITY FOR THEM. THE | | | PRINTED NAME WITH THE ORIGNAL SIGNATURE OF THE PERSON | | | TAKING RESPOSIBILITY FOR THE ISOMETRIC IS STILL | | | REQUIRED. PER (W.P.B. AS AMENDED) SECTION 106.3.4.3. | | | | | | **THE FOLLOWING ARE NEW COMMENTS DUE TO THE RESUBMITTAL | | | PACKAGE AND NEW GAS ISOMETRIC. | | | | | | 5. THERE ARE TWO DIFFERENT GENERATOR MANUFACTURE | | | SPECIFICATION SHEETS MAKE AND MODEL NUMBERS WITH | | | DIFFERENT BTU LOAD CAPACITIES IN THE RESUBMITTAL. | | | PLEASE KNOW THAT THIS IS CONFUSING AND UNACCEPTABLE. A | | | GENERAC MODEL QT030 WITH A BTU CAPACITY OF 525,000 AND | | | A GAURDIAN MODEL #5219 WITH A 412,000 BTU CAPACITY IS | | | IN THE RESUBMITTAL. PLEASE CORRELATE THE RESUBMITTAL | | | WITH ONLY ONE MAKE AND MODEL OF GENERATOR MANUFACTURE | | | SPECIFICATIONS. PER FBC-2004 FUEL GAS SECTION 401.1 | | | SCOPE. | | | | | | 6. SUBMIT TWO COPIES OF MANUFACTURE SHEETS FOR THE MP | | | REGULATORS (2ND STAGE REGULATORS) TO VERIFY COMPLIANCE | | | WITH STANDARDS NFPA 54, NFPA 58, AND THE FBC-2004 FUEL | | | GAS CODE SEC 402.2. THE MANUFACTURE SHEETS SHALL | | | CLEARLY INDICATE THE MP REGULATORS MAKE, MODEL NUMBER, | | | BTU LOAD CAPACITY, AND A LISTING FROM A NATIONALLY | | | RECOGNIZED TESTING LABORATORY (LISTING EXAMPLES= AGA, | | | CSA, UL). | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2008-06-30 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-06-30 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-06-30 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2008-06-30 09:46:35 | GAS PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS. PER FBC- | | | FUEL GAS CODE SECTION 401.1 SCOPE. | | | NOTE: THERE WERE NO CORRESPONDING LENGTHS FOR THE CUT | | | SECTIONS OF PIPE INDICATED ON GAS ISOMETRIC DRAWING. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. PER FBC- FUEL GAS | | | CODE SECTION 401.1 SCOPE. | | | NOTE: THE ONLY PIPING MATERIAL INDICATED WAS FOR THE | | | UNDERGROUND PIPING. WHAT IS THE PIPING MATERIAL FOR THE | | | ABOVE GROUND? | | | | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | NOTE: REFERENCE COMMENT #1 AND COMPLY. | | | | | | 4. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING | | | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE | | | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE | | | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER | | | SECTION *106.3.4.3. | | | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, | | | THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, | | | SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA | | | STATUTES 481 AND 471 RESPECTIVELY. | | | NOTE: SUBMITTED GAS ISOMETRIC HAS NO SIGNATURES. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE | | | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW | | | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-07-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-07-01 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-07-01 |
Time |
10:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-09-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-03 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-03 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2008-09-03 16:50:18 | TO "COMM" BD#44 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-06-30 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-06-30 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-05-22 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2008-05-29 11:25:04 | TO "COMM" BD#9 | | 2008-05-22 14:20:45 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2009-07-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-17 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2009-07-17 15:45:11 | NATURAL GAS, TO BE INSTALLED PER NFPA_37 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-09-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-09-11 |
Time |
08:58 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-09-11 |
Time |
08:58 |
Sent To |
|
|
| Notes |
| 2008-09-11 09:05:42 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | | | | 1) TWO DIFFERENT SITE PLANS WERE SUBMITTED, ONE STATING | | | THE GENERATOR WILL BE 5 FEET FROM THE BUILDING AND ONE | | | STATES 3 FEET FROM THE BUILDING. THE TWO MUST COINCIDE | | | PLEASE CORRECT. | | | | | | 2) PLEASE STATE ON PLAN WHAT THE BUILDING IN MADE OF | | | (WOOD, CONCRETE, EC.). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-06-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-06-11 |
Time |
09:51 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-06-11 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2008-06-11 09:59:20 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) SEE ZONING REVIEW NOTES, PLEASE COMPLY. | | | | | | 2) THE NOTICE OF COMMENCEMENT SUBMITTED LINE #2 | | | DESCRIPTION OF IMPROVEMENT IS BLANK. PLEASE DESCRIBE | | | THE WORK TO BE DONE AND RE-RECORD WITH PALM BEACH | | | COUNTY, PER FS 713.13. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2009-07-16 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-07-15 |
Time |
19:41 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-07-15 |
Time |
19:41 |
Sent To |
|
|
| Notes |
| 2009-07-16 19:46:17 | PLANNING AND ZONING ("P&Z"): **** PASSED WITH PROVISO, | | | SCREENING (LANDSCAPING) FOR GENERATOR SHALL BE | | | INSTALLED PURSUANT TO PLANS SUBMITTED TO THE P&Z | | | DEPARTMENT FOR THE MINOR AMENDMENT TO THE ST. MARY'S | | | CSPD- QUANTUM HOUSE PB 1068Z **** | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2008-09-09 |
Time |
20:45 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2008-09-09 |
Time |
20:45 |
Sent To |
|
|
| Notes |
| 2008-09-09 20:46:21 | PLANNING AND ZONING **** FAILED, REPEAT COMMENT, DID | | | NOT ADDRESS**** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. THIS PROPERTY IS PART OF THE ST. MARY'S COMMUNITY | | | SERVICE PLANNED DEVELOPMENT (CSPD), AN APPLICATION FOR | | | A MINOR AMENDMENT TO THE CSPD SHOWING THE PROPOSED | | | GENERATOR WILL BE REQUIRED TO BE FILED TO THE PLANNING | | | AND ZONING DEPARTMENT AND APPROVED PRIOR TO THE | | | BUILDING PERMIT BEING APPROVED. SEE | | | HTTP://WWW.CITYOFWPB.COM/PLAN/INDEX.PHP, UNDER | | | DEVELOPMENT APPLICATION FOR REQUIREMENTS OF A MINOR PD | | | AMENDMENT. | | | | | | 3. PROVIDE ELEVATIONS AND A FLOOR PLAN OF SCREENING AND | | | LANDSCAPING DETAIL. INCLUDE WALL HEIGHT, ETC. SCREENING | | | ENCLOSURE AND LANDSCAPING SHALL MEET SECTION 94-444 OF | | | THE ZONING AND LAND DEVELOPMENT REGULATIONS. SCREENING | | | WALLS SHALL BE LADSCAPED WITH SHRUBS AND HEDGES PLANTED | | | AT TWO-FOOT INTERVALS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE | | | NUMBER BELOW. | | | | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2008-06-03 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2008-06-03 |
Time |
17:53 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2008-06-03 |
Time |
17:53 |
Sent To |
|
|
| Notes |
| 2008-06-03 18:18:02 | PLANNING AND ZONING **** FAILED **** | | | | | | 1.RESPOND TO COMMENTS IN WRITING. | | | | | | 2. THIS PROPERTY IS PART OF THE ST. MARY'S COMMUNITY | | | SERVICE PLANNED DEVELOPMENT (CSPD), AN APPLICATION FOR | | | A MINOR AMENDMENT TO THE CSPD SHOWING THE PROPOSED | | | GENERATOR WILL BE REQUIRED TO BE FILED TO THE PLANNING | | | AND ZONING DEPARTMENT AND APPROVED PRIOR TO THE | | | BUILDING PERMIT BEING APPROVED.SEE | | | HTTP://WWW.CITYOFWPB.COM/PLAN/INDEX.PHP, UNDER | | | DEVELOPMENT APPLICATION FOR REQUIREMENTS OF A MINOR PD | | | AMENDMENT. | | | | | | 3.PROVIDE ELEVATIONS AND A FLOOR PLAN OF SCREENING | | | AND LANDSCAPING DETAIL.INCLUDE WALL HEIGHT, ETC. | | | SCREENING ENCLOSURE AND LANDSCAPING SHALL MEET SECTION | | | 94-444 OF THE ZONING AND LAND DEVELOPMENT REGULATIONS. | | | SCREENING WALLS SHALL BE LADSCAPED WITH SHRUBS AND | | | HEDGES PLANTED AT TWO-FOOT INTERVALS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE | | | NUMBER BELOW. | | | | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | | | | |
|
|
|