Plan Review Details - Permit 08050632
Plan Review Stops For Permit 08050632
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-09-17 Cont ID  
Sent By jwitmer Date 2008-09-17 Time 12:49 Rev Time 1.33
Received By jwitmer Date 2008-09-17 Time 12:21 Sent To PC
Notes
2008-09-17 13:25:46BUILDING PLAN REVIEW
 PERMIT: 08050632
 ADD: 1645 PALM BEACH LAKES SUITE# 600
 CONT: MAJOR WORKING DRAWING REVIEW
 TEL: (954)648-6068 DARLENE DE PAULA-JONES
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SEPT. 17,2008
 REVISION# 3&4
 ACTION: DENIED
  
 1) LAW OFFICE # 1 ON THE ORIGINAL PLANS STAMPED BU THE
 CITY THE INSWING DOOR DID COMPLY WITH 11-4.13.6 18" ON
 THE SWING SIDE (LATCH SIDE) OF DOOR. IF PLANS ARE GOING
 TO BE REVISED THEN
 SECTION11-4.1.6(2)(2)(A) (II) AN ACCESSIBLE ROUTE TO
 ALL AREAS. DISPROPORTIONATE COST.DUTY TO PROVIDE
 ACCESSIBLE FEATURES IN THE EVENT OF DISROPORTIONALITY.
  
 2) PARALEGAL OFFICE #33 AT TIME OF ISSUANCE THE OFFICE
 ENTRY DOOR HAD A IN SWING DOOR BUT REVISON # 3 NOW HAS
 THE DOOR AS A OUT SWING DOOR BLOCKING THE CORRIDOR, THE
 OFFICE DOOR # 1 BEING CLOSED IT WOULD MAKE IT
 IMMPOSSIBLE FOR A WHEEL CHAIR USER TO GET INTO A
 PARALELL APPROACH 11-4.13.6 & FIGURE 25(B).
  
 THE SECOND ISSUE WITH THE ENTRY DOOR TO OFFICE # 33 IS
 1005.2 DOOR ENCROACHMENT. DOORS OPENING INTO THE PATH
 OF EGRESS TRAVEL SHALL NOT REDUCE THE REQUIRED WIDTH TO
 LESS THAN ONE-HALF DURING THE COURSE OF THE SWING. WHEN
 FULLY OPEN, THE DOOR SHALL NOT PROJECT MORE THAN 7
 INCHES (178 MM) INTO THE REQUIRED WIDTH.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-27 Cont ID  
Sent By jwitmer Date 2008-08-27 Time 11:58 Rev Time 0.77
Received By jwitmer Date 2008-08-27 Time 11:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-08-11 Cont ID  
Sent By jwitmer Date 2008-08-11 Time 15:55 Rev Time 1.22
Received By jwitmer Date 2008-08-11 Time 15:55 Sent To PC
Notes
2008-08-11 15:56:20BUILDING PLAN REVIEW
 PERMIT: 08050632
 ADD: 1645 PALM BEACH LAKESSUITE# 600
 CONT:MAJOR WORKING DRAWING REVIEW
 TEL: (954)648-6068 DARLENE DE PAULA-JONES
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 08-11-08
 2NDREVIEW
 ACTION: DENIED
  
 1A-E)COMPLIEDI
  
 2) 2ND REQUEST, NULL AND VOID SINCE 2/25/05 TEWES
 DESIGN GROUP, LLC,481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ARCHITECT PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3- 6) COMPLIED.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-17 Cont ID  
Sent By jwitmer Date 2008-06-17 Time 12:59 Rev Time 2.22
Received By jwitmer Date 2008-06-17 Time 12:59 Sent To  
Notes
2008-08-11 15:55:15BUILDING PLAN REVIEW
 PERMIT: 08050632
 ADD: 1645 PALM BEACH LAKES SUITE# 600
 CONT: MAJOR WORKING DRAWING REVIEW
 TEL: (954)648-6068 DARLENE DE PAULA-JONES
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 08-11-08
 2ND REVIEW
 ACTION: DENIED
  
 1A-E) COMPLIEDI
  
 2)2ND REQUEST, NULL AND VOID SINCE 2/25/05 TEWES DESIGN
 GROUP, LLC, 481.219 F.S. CERTIFICATE OF AUTHORIZATION.
 THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3- 6) COMPLIED.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
2008-08-11 15:53:23BUILDING PLAN REVIEW
 PERMIT: 08050632
 ADD: 1645 PALM BEACH LAKESSUITE# 600
 CONT:MAJOR WORKING DRAWING REVIEW
 TEL: (954)648-6068 DARLENE DE PAULA-JONES
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 08-11-08
 2NDREVIEW
 ACTION: DENIED
  
 1A-E)COMPLIEDI
  
 2)2ND REQUEST, NULL AND VOID SINCE 2/25/05 TEWES DESIGN
 GROUP, LLC,481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ARCHITECT PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3- 6) COMPLIED.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
2008-06-17 13:38:45BUILDING PLAN REVIEW
 PERMIT: 08050632
 ADD: 1645 PALM BEACH LAKESSUITE# 600
 CONT:MAJOR WORKING DRAWING REVIEW
 TEL: (954)648-6068 DARLENE DE PAULA-JONES
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) : PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS PLEASE UPDATE THE
 CODE RESEARCH CRITERIA.
  
 2) TEWES DESIGN GROUP, LLC,481.219 F.S.CERTIFICATE
 OF AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET
 BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.ADD THE NUMBER TO
 EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 3) ABS ENGINEERING GROUP: 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 4)PLANS FAIL TO INDICATE THE USE OF T HE 2004 FBC
 EXISTING BUILDING CODE, PLEASE INDICATE WHAT LEVEL OF
 ALTERATION THE DESIGN PROFESSIONAL OR OWNER MUST ELECT
 ONE OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT
 TO 303,304 & 305.
  
 5) SHEET A-2.1 BREAK ROOM INDICATES THE USE OF A SINK
 BUT THERE ARE NO ELEVATIONS OF THE CABINETRY, PLEASE
 COMPLY WITH:11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED
 WITH THE COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE
 FINISH FLOOR. 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST
 27" HIGH 30" WIDE, AND 19" DEEP SHALL BE PROVIDED
 UNDERNEATH SINKS. 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD APPROACH.
 THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM)
 UNDERNEATH THE SINK.
  
 6) BUILDING PROVISO: PLANS DO NOT INDICATE SHEET A-4
 NEW DOOR SUB-BUCKS, NO COMBUSTIBLE MATERIALS SECTION
 603.1 FIRE RETARDANT TREATED WOOD SUB-BUCK AND BACKING
 ARE ALLOWED.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-09-17 Cont ID  
Sent By dpalmer Date 2008-09-17 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2008-09-17 Time 12:07 Sent To  
Notes
2008-09-17 12:07:37SEPARATE PERMITS FOR FIRE ALARM SYSTEM AND LOW VOLTAGE
 SYSTEMS INCLUDING PHONE,DATA ETC.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-08-28 Cont ID  
Sent By dpalmer Date 2008-08-28 Time 13:45 Rev Time 0.00
Received By dpalmer Date 2008-08-28 Time 13:44 Sent To B
Notes
2008-08-28 13:45:50PLANS ROUTED TO LUIS M FOR PROCESSING
2008-08-28 13:45:17 
 ** REDLINED PLANS **
  
  
  
 1) NOTE:THE FOLLOWING ITEMS WERE REDLINED AND/OR
 NOTED ON PLANS.
  
 **ALL REVISIONS SHALL BE SUBMITTED, REVIEWED, STAMPED
 AND ON-SITE FOR ELECTRICAL INSPECTOR BEFORE ROUGH
 ELECTRICAL INSPECTION.
 **ALL LOW VOLTAGE SYSTEMS INCLUDING FIRE ALARM SYSTEM
 ARE REQUIRED TO BE UNDER SEPARATE PERMITS.
 **ALL NEW LIGHTING CONTROLS SHALL MEET
 13-415.1.ABC.1.1,.1.2 AND .1.3 FOR MINIMUM PRESCRIPTIVE
 REQUIREMENTS.
 **ALL HORN AND STROBE DEVICES SHALL MEET FBC CHAPTER
 11. PLANS NOTE NFPA-72 WHICH IS ALSO CORRECT HOWEVER
 SOME REQUIREMENTS IN THE FBC ARE MORE RESTRICTIVE.
 11-4.28.1,.2 AND .3.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-08-07 Cont ID  
Sent By dpalmer Date 2008-08-07 Time 15:12 Rev Time 0.00
Received By dpalmer Date 2008-08-07 Time 15:12 Sent To  
Notes
2008-08-07 15:12:55 
 **DENIED 2ND REVIEW**
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE:PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER FOR ALL FIRMS LISTED ON TITLE
 BLOCKS. PLEASE SEE THAT THE LICENSE ON ARCHITECTURAL
 SHEETS FOR FIRM TEWES DESIGN GROUP INC IS BEING SHOWN
 ON THE STATE WEBSITE AS NULL AND VOID.
 PLEASE PROVIDE UP TO DATE ACCURATE LICENSE NUMBER FOR
 SAID FIRM. PLANS MAY BE HANDED OVER TO LEGAL COUNSEL
 FOR THE FLORIDA BOARD OF ARCHITECTS AS NO RELEVANT
 LICENSE COULD BE FOUND AS REQUIRED PER FAC 61G1-16.004
 AND FS 481.219.
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 AS
 PLANS WERE NOT REVISED TO SHOW AND INDICATE THE
 REQUIRED DEVICES FOR AUTOMATE LIGHTING CONTROLS. IN
 FACT THE PLANS CONTAIN A NOTE QUOTING THE CODE. THE
 CODE IN GENERAL OR SPECIFIC CODE REQUIREMENT SHALL NOT
 BE QUOTED IN LIEU OF MINIMUM DESIGN.
 ONE EXAMPLE ALONE WOULD BE THE FACT THE SYMBOL LEGEND
 STILL SHOWS STANDARDS SINGLE POLE DEVICES WHICH ARE NOT
 ACCEPTABLE TO MEET THE MINIMUM CODE.
  
 3) NOTE: PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2. THE
 PLANS CONTAIN SOME INFORMATION AND SEEM TO BE ON THE
 RIGHT TRACK HOWEVER AS THE FIXTURES ON PLANS AND A
 REQUIRED FIXTURE LEGEND IS NOT COMPLETE WITH ALL
 INFORMATION ON ALL FIXTURES; REVIEW FOR MINIMUM CODE
 COMPLIANCE CAN NOT BE DONE.
 PLEASE COMPLETE INFORMATION ON ALL FIXTURES.
  
 4) NOTE: PLEASE BE SURE THE NEW CIRCUITS ON PANEL
 SCHEDULES ARE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY
 FEED.
 408.4
  
 5) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE AS SOME OF THE CODE
 SECTIONS FROM THE PREVIOUS REVIEW ARE BEING REPEATED
 FOR THE SECOND REVIEW. THIS IS ONLY A NOTICE GIVEN AT
 THIS TIME.
 AS THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION
 THIS SECTION OF THE STATUTES AS NOTED WOULD APPLY TO
 ANY COMMENTS ON THE REVIEW AFTER NEXT. PLEASE BE SURE
 TO ADDRESS COMMENTS.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-19 Cont ID  
Sent By dpalmer Date 2008-06-19 Time 14:22 Rev Time 0.00
Received By dpalmer Date 2008-06-19 Time 14:22 Sent To  
Notes
2008-06-19 14:23:10** DENIEDREVIEW **
  
  
 1) NOTE:PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN
 REVIEW AND NOT FOR PERMIT. PLEASE KNOW EVEN ONCE PLANS
 ARE FOUND TO BE CODE COMPLIANT THE REVIEW WILL STILL
 REMAINED IN A FAILED STATUS UNTIL PERMIT APPLICATION IS
 MADE. LICENSING AND SEVERAL OTHER ITEMS ARE VERIFIED AT
 TIME OF APPLICATION.
  
 2) NOTE: PLEASE SEE FAC 61G1-16.004 AND FLORIDA
 STATUTES 481.219 AS THE TITLE BLOCKS ARE MISSING THE
 REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER.
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE STATED
 ON ELECTRICAL PLANS AT A MINIMUM.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101 (PLANS NOTE A 2004 NFPA-101 WHICH DOES
 NOT EXIST)
 2002 NFPA-72
  
 4) NOTE: PLEASE SEE FAC 61G15-23.002 AND FS 471.023 AS
 THE MEP TITLE BLOCKS ARE MISSING THE REQUIRED
 CERTIFICATE OF AUTHORIZATION NUMBER.
 THIS IS REQUIRED ON ALL SHEETS FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 5) NOTE: PLEASE SEE THE SEAL WHICH IS IN USE BY THE
 ENGINEER IS NO LONGER VALID IN THE STATE OF FLORIDA.
 PLEASE SEE RULING DATED FEB 2004 IN WHICH ALL SEALS FOR
 ENGINEERS WERE REQUIRED TO GO THE WORDING OF LICENSE
 HOWEVER AN EXTENSION WAS GRANTED HOWEVER ONLY TO THE
 DATE OF DECEMBER 31ST, 2005. SEAL HAS NOT BEEN VALID TO
 BE USED IN THE STATE OF FLORIDA SINCE JANUARY 1ST,
 2006.
 FAC61G15-23.001
  
 6) NOTE: PLEASE SEE PLANS ARE VERY CONGESTED AND NOT
 EASILY READ. PLEASE SEE FBC 106.1.3 AS THE PLANS SHALL
 BE A MINIMUM OF 1/8 TH INCH SCALE.
 PLANS MENTIONS THE SCALE IS 1/8TH INCH HOWEVER BASED ON
 CEILING GRID FOR EXAMPLE WHICH SHOWS 2FT BY 2FT TILES,
 THESE DO NOT COORDINATE.
 PLEASE ADJUST AND SUBMIT.
  
 7) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND PLACE
 NOTES ON PLANS ACCORDINGLY.
  
 8) NOTE: PLEASE SEE 13-415.1.ABC.1.1,.1.2 AND .1.3 FOR
 NEW LIGHTING CONTROLS BEING INSTALLED.
  
 9) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1,.1.2 FOR
 MINIMUM LIGHTING PERFORMANCE CALCULATIONS COMPLIANCE.
  
 10) NOTE: PLEASE SEE 240.21, 408.36 AS THE PANEL ON THE
 SECONDARY SIDE OF THE TRANSFORMER SHALL CONTAIN OVER
 CURRENT PROTECTION.
 RISER INDICATES EXISTING MAIN CIRCUIT BREAKER YET THE
 PANEL 6L INDICATES THIS PANEL AND MAIN LUG ONLY.
  
 11) NOTE: PLEASE SEE THE MINIMUM LEVELS FOR HORN
 STROBES SHALL MEET FBC 11-4.28.1, .2 AND .3(4). THE
 LEVELS STATED ON PLANS ARE NOT CLEAR FOR ALL.
 PLEASE SEE IT IS UNCLEAR WHAT THE 15 BEFORE IS.
 IF THIS IS A HORN LEVEL, THE LEVEL IS TOO LOW.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH ARE NOT
 YET SHOWN FOR CODE COMPLIANCE, THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW.
  
 ** ONE SET OF PLANS ARE BEING RETAINED.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-09-24 Cont ID  
Sent By mwennerg Date 2008-09-24 Time 13:46 Rev Time 0.00
Received By mwennerg Date 2008-09-24 Time 13:46 Sent To  
Notes
2008-09-24 13:47:35REVISED SHEETS ME-2, ME-2A, AND ME-3 DATED 9/3/08.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-08-28 Cont ID  
Sent By mwennerg Date 2008-08-28 Time 10:32 Rev Time 0.00
Received By mwennerg Date 2008-08-28 Time 10:32 Sent To E
Notes
2008-08-28 10:33:32STAMPED SHEETS A-1, FP AND ME-3.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-08-11 Cont ID  
Sent By mawillia Date 2008-08-11 Time 13:30 Rev Time 0.00
Received By mawillia Date 2008-08-11 Time 13:10 Sent To  
Notes
2008-08-11 13:30:10*****PROVISO*****
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 BELOW COMMENT (TAKEN FROM THE PREVIOUS PLAN REVIEW) HAS
 BEEN ADDRESSED:
  
 7.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR
 THIS SCOPE OF WORK LOCATION.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-30 Cont ID  
Sent By mawillia Date 2008-06-30 Time 13:15 Rev Time 0.00
Received By mawillia Date 2008-06-30 Time 11:09 Sent To  
Notes
2008-06-30 13:14:52*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCDTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 ACCESS TO / EGRESS FROM THE OTHER FLOORS OF THE
 BUILDING.
  
 4.ON SHEET A-1, REFERENCE THE 2004 EDITION OF THE
 FLORIDA FIRE PREVENTION (NOT 2005)AND THE 2003
 EDITION OF NFPA 101 (NOT 2004) .
  
 5.ON SHEET A-2, NO LEGEND FOR THE DOOR TYPES 1 AND 2
 NOTED.
  
 6.ON SHEET ME-3, STROBE DEVICE V6-2-7 SHOWN AS
 RELOCATED(R) BUT LISTED AS EXISTING (E);STROBE
 DEVICE V6-2-10 SHOWN AS (E) BUT LISTED AS (R);STROBE
 DEVICE V6-2-11 SHOWN AS (E) BUT LISTED AS (R) .
  
 7.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR
 THIS SCOPE OF WORK LOCATION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-09-26 Cont ID  
Sent By adarroug Date 2008-09-26 Time 16:54 Rev Time 0.00
Received By adarroug Date 2008-09-26 Time 16:54 Sent To B
Notes
2008-09-26 16:55:12TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-10 Cont ID  
Sent By adarroug Date 2008-09-10 Time 11:45 Rev Time 0.00
Received By adarroug Date 2008-09-10 Time 11:45 Sent To  
Notes
2008-09-10 11:47:34TO "COMM" BD#7

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-05 Cont ID  
Sent By adarroug Date 2008-09-05 Time 16:25 Rev Time 0.00
Received By adarroug Date 2008-09-05 Time 16:25 Sent To  
Notes
2008-09-05 16:28:54TO "COMM" BD#12

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-08-14 Cont ID  
Sent By adarroug Date 2008-08-14 Time 09:57 Rev Time 0.00
Received By adarroug Date 2008-08-14 Time 09:57 Sent To  
Notes
2008-08-14 10:01:41TO "COMM" BD#18

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-07-21 Cont ID  
Sent By adarroug Date 2008-07-21 Time 14:29 Rev Time 0.00
Received By adarroug Date 2008-07-21 Time 14:28 Sent To  
Notes
2008-07-21 14:29:18TO "COMM" BD#34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-30 Cont ID  
Sent By mawillia Date 2008-06-30 Time 11:30 Rev Time 0.00
Received By mawillia Date 2008-05-23 Time 08:53 Sent To  
Notes
2008-05-29 11:47:38TO "COMM" BD#12
2008-05-23 08:53:38WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-09-11 Cont ID  
Sent By rregueir Date 2008-09-11 Time 11:14 Rev Time 0.00
Received By rregueir Date 2008-09-11 Time 10:53 Sent To  
Notes
2008-09-11 11:14:10REVISED PAGE ME-4 REV #3

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-08-27 Cont ID  
Sent By rregueir Date 2008-08-27 Time 13:40 Rev Time 0.00
Received By rregueir Date 2008-08-27 Time 13:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-08-08 Cont ID  
Sent By rregueir Date 2008-08-08 Time 08:27 Rev Time 0.00
Received By rregueir Date 2008-08-07 Time 16:51 Sent To  
Notes
2008-08-08 08:27:02REVIEW #: 1ST (PREVIOUS PLAN CHECK ONLY)
 ACTION: DENOED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 STAMPED. REVIEW WILL REMOAIN IN FAIL STATUS PENDING
 RESOLUTION OF THE EXPIRED ARCHITECTURE BUSINESS LICENSE
 FOR THE TEWES DESIGN GROUP. ONCE THIS IS ADDRESSED,
 PLEASE BE SURE TO RETURN THE STAMPED MECHANICAL PLANS
 FOR PERMIT ISSUANCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-20 Cont ID  
Sent By rregueir Date 2008-06-20 Time 09:35 Rev Time 0.00
Received By rregueir Date 2008-06-19 Time 13:41 Sent To  
Notes
2008-06-20 09:35:03REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE LEVEL OF ALTERATION IS NOT DECLARED ON PLANS.
 THE DESIGN PROFESSIONALMUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION IN ACCORDANCE WITH
 FBCEB 301.5.
  
 2. PROVIDE OUTSIDE AIR CALCULATIONS INCLUDING OCCUPANT
 LOAD, VENTILATION REQUIRED AND VENTILATION PROVIDED IN
 ACCORDANCE WITH FBCM TABLE 403.3. SEE ALSO FBCEB
 609.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-09-10 Cont ID  
Sent By kstevens Date 2008-09-10 Time 16:14 Rev Time 0.00
Received By kstevens Date 2008-09-10 Time 16:14 Sent To  
Notes
2008-09-10 16:15:26REVISION OK -- SHT MP-5

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-08-15 Cont ID  
Sent By kstevens Date 2008-08-15 Time 13:13 Rev Time 0.00
Received By kstevens Date 2008-08-14 Time 14:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-08-04 Cont ID  
Sent By kstevens Date 2008-08-04 Time 11:45 Rev Time 0.00
Received By kstevens Date 2008-08-04 Time 11:45 Sent To  
Notes
2008-08-04 12:02:12DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. ALL SHEETS WITH ARCHITECTURAL TITLE BLOCKS. THE
 BUSINESS LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED ON EACH SHEET. THE STATE OF
 FLORIDA DEPT OF PROFESSIONAL REGULATION, (DBPR),
 INDICATES THE BUSINESS NUMBER IS NULL AND VOID SINCE
 2/28/2005. THIS NUMBER IS REQUIRED PER FAC
 61G1-16.004(1) & FS 481.219. (SEE ATTACHED SHEET).
 ****NO WRITTEN RESPONSE FROM ARCHITECT, BUT THE
 CERTIFICATE OF AUTHORIZATION IS ADDED TO THE
 ARCHITECTURAL SHEETS BUT NOT THE ME SHEETS WHERE TEWES
 DESIGN GROUP LLC IS IN THE TITLE BLOCKS. ALSO THE
 CERTIFICATE OF AUTHORIZATION IS STILL IN A NULL & VOID
 STATUS. THE STATUS WILL HAVE TO BE ACTIVATED PRIOR TO
 APPROVAL OF PLANS.
  
 2. OK
  
 3. SHT A-2 ELEVATION "A" SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. OK
 B. 11-4.24.4 SINK DEPTH
 ****NO RESPONSE COMMENT NOT ADDRESSED.
 C. 11-4.24.5 CLEAR FLOOR SPACE. (FORWARD APPROACH
 REQD. CABINET DOORS NOT APPROVED).
 ****NO RESPONSE COMMENT NOT ADDRESSED. CLEAR FLOOR
 SPACE NOT SHOWN ON THE FLOOR PLAN AND CABINET DOORS ARE
 STILL SHOWN ON ELEVATION.
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 ****NO RESPONSE COMMENT NOT ADDRESSED.
 E. 11-4.24.7 FAUCETS
 ****NO RESPONSE COMMENT NOT ADDRESSED.
  
 4. OK
  
 5. SHT ME-1 SHOWS SINKS THAT WERE DELETED ON THE
 ARCHITECTURAL FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT THE SINKS ARE STILL SHOWN.
 CORRELATE WITH SHEET A-2 (NEW FLOOR PLAN).
  
 6. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-06-16 Cont ID  
Sent By kstevens Date 2008-06-16 Time 11:18 Rev Time 0.00
Received By kstevens Date 2008-06-11 Time 18:29 Sent To  
Notes
2008-06-16 11:39:58DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH ARCHITECTURAL TITLE BLOCKS. THE
 BUSINESS LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED ON EACH SHEET. THE STATE OF
 FLORIDA DEPT OF PROFESSIONAL REGULATION, (DBPR),
 INDICATES THE BUSINESS NUMBER IS NULL AND VOID SINCE
 2/28/2005. THIS NUMBER IS REQUIRED PER FAC
 61G1-16.004(1) & FS 481.219. (SEE ATTACHED SHEET).
  
 2. SHTS A-1.1 & ME-5 IN THE REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD SHALL BE PROHIBITED. SECTION
 704.5. ALL DEMO'D/CAPPED PIPING SHALL NOT BE COVERED
 PRIOR TO FIELD INSPECTORS INSPECTION &APPROVAL.
  
 3. SHT A-2 ELEVATION "A" SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE. (FORWARD APPROACH
 REQD. CABINET DOORS NOT APPROVED).
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 4. ALL ME SHEETS. THE CERTIFICATE OF AUTHORIZATION
 NUMBER IS REQUIRED ON EACH SHEET. FAC 61G15-23.002(2) &
 FS 471.025. (SEE ATTACHED SHEET).
  
 5. SHT ME-1 SHOWS SINKS THAT WERE DELETED ON THE
 ARCHITECTURAL FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 6. SHT ME-5 THE WATER HAMMER ARRESTOR SHALL BE LOCATED
 NEAR THE FIXTURE, (REF),IN AN "EFFECTIVE RANGE", NOT
 IN THE CEILING AS SHOWN. PDI-WH 201. SECTION 604.9.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-10-03 Cont ID  
Sent By mcruz Date 2008-10-03 Time 12:22 Rev Time 0.00
Received By mcruz Date 2008-10-03 Time 12:22 Sent To  
Notes
***NONE***