Plan Review Details - Permit 08050570
Plan Review Stops For Permit 08050570
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-06-11 Cont ID  
Sent By shill Date 2008-06-11 Time 09:53 Rev Time 0.00
Received By shill Date 2008-06-11 Time 09:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-06-27 Cont ID  
Sent By dpalmer Date 2008-06-27 Time 10:21 Rev Time 0.00
Received By dpalmer Date 2008-06-27 Time 10:21 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-05-28 Cont ID  
Sent By dpalmer Date 2008-05-28 Time 10:35 Rev Time 0.00
Received By dpalmer Date 2008-05-28 Time 10:35 Sent To G
Notes
2008-05-28 10:35:58** DENIED **
  
 1) NOTE:PLEASE KNOW PER FS 527.02 THE PRIMARY
 GENERATOR PERMIT SHALL BE APPLIED FOR UNDER LICENSES AS
 REQUIRED. MAY NO LONGER USE THE U-# ASSOCIATED WITH THE
 ELECTRICAL CONTRACTOR. THE ELECTRICAL LICENSE NUMBER
 STILL MAY BE USED FOR THE ELECTRICAL SUB-PERMIT. THIS
 HAS BEEN RECENTLY CONFIRMED WITH THE STATE OF FLORIDA
 DEPARTMENT OF AGRICULTURE AND CONTRACTORS LICENSING
 BOARD.
  
 ** PLEASE KNOW FOR INFORMATIONAL PURPOSE, THE GENERATOR
 CHECK LIST FROM 2006 IS NO LONGER ACCURATE. SOME ITEMS
 ARE CURRENTLY BEING REVISED.
  
 2) NOTE: PLEASE COORDINATE PAPERWORK AS SUBMITTED.
 PLEASE SEE MANUFACTURES SPECS/CURT SHEETS FROM GENERAC
 ATTACHED CLEARLY SHOWS A SEPARATE TRANSFER PANEL WITH
 SUB BRANCH CIRCUITS HOWEVER THERE IS ALSO THE SHEETS
 FOR A NEW DOUBLE POLE/DOUBLE THROW SAFETY SWITCH.
 110.3, 90.7, 702.6 ETC
  
 3) NOTE: PLEASE SHOW A LAYOUT ON PLANS THE LOCATION OF
 ALL ELECTRICAL EQUIPMENT. THE RISER DOES NOT INDICATE
 WHICH EQUIPMENT IS INSIDE, OUTSIDE, IN ROOMS, ETC.
 SEVERAL ITEMS CAN NOT BE VERIFIED AT THIS TIME FOR CODE
 COMPLIANCE.
 110.26, 240.24, 408.17 ETC
 FBC 106.1.2
  
 4) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW SERVICE
 MAINS AND EQUIPMENT.
 110.9
 FBC 106.3.5.4, 106.1.2
  
 5) NOTE: PLEASE SHOW THE GROUNDING ELECTRODE SYSTEM PER
 250.50. THE CWP MAY NOT BE THE ONLY ATTACHMENT.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-06-30 Cont ID  
Sent By mperson Date 2008-06-30 Time 14:03 Rev Time 0.00
Received By mperson Date 2008-06-30 Time 14:03 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-06-04 Cont ID  
Sent By mperson Date 2008-06-04 Time 13:12 Rev Time 0.00
Received By mperson Date 2008-06-04 Time 13:12 Sent To M
Notes
2008-06-04 13:32:49GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 NOTE: THE SUBMITTED ISOMETRIC IS ONLY INDICATING THE
 CORRESPONDING LENGTH TO THE UNDERGROUND PE. CLEARLY
 INDICATE THE CORRESPONDING LENGTHS TO ALL CUT SECTIONS
 OF PIPE. WHAT ARE THE ABOVE GROUND CORRESPONDING
 LENGTHS TO THE CUT SECTIONS OF PIPE?
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC-2004 FUEL
 GAS SECTION 401.1 SCOPE.
 NOTE: THE ONLY PIPING MATERIAL INDICATED ON THE
 DRAWING IS PE. THE PLANS ARE INDICATING FINAL CONNECT
 PER FBC 411.1, HOWEVER THAT SECTION IS VAUGE. WHAT ARE
 THE ABOVE GROUND PIPING MATERIAL AND SIZES? CLEARLY
 INDICATE ALL PIPING MATERIALS AND SIZES FOR THE
 PROPOSED GENERATOR.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #1.
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: PLEASE SUBMIT THE 2ND STAGE REGULATOR
 MANUFACTURER'S SPECIFICATIONS SHEETS CLEARLY INDICATING
 THE MAKE, MODEL NUMBER, BTU LOAD CAPACITIES, AND A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
  
 5. A GAS PERMIT CAN NOT BE ISSUED UNTIL
 THE GEN/RES PERMIT APPLICATION HAS BEEN
 APPROVED BY ZONING FOR THE GENERATOR LOCATION.
 NOTE: CLEARLY INDICATE THE PROPOSED GENERATORS
 LOCATION FROM PROPERTY LINE AND ADJACENT STRUCTURES.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-06-18 Cont ID  
Sent By adarroug Date 2008-06-18 Time 11:39 Rev Time 0.00
Received By adarroug Date 2008-06-18 Time 11:39 Sent To Z
Notes
2008-06-18 11:39:29TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-11 Cont ID  
Sent By shill Date 2008-06-11 Time 09:53 Rev Time 0.00
Received By shill Date 2008-05-21 Time 09:15 Sent To  
Notes
2008-05-21 09:15:50TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-06-27 Cont ID  
Sent By tgordon Date 2008-06-27 Time 10:56 Rev Time 0.30
Received By tgordon Date 2008-06-27 Time 10:56 Sent To G
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-06-04 Cont ID  
Sent By tgordon Date 2008-06-04 Time 15:31 Rev Time 0.20
Received By tgordon Date 2008-06-04 Time 15:31 Sent To B
Notes
2008-06-04 15:33:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ZONING REVIEW NOTE #1, PLEASE COMPLY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-06-19 Cont ID  
Sent By choops Date 2008-06-19 Time 08:44 Rev Time 0.00
Received By choops Date 2008-06-19 Time 08:44 Sent To E
Notes
2008-06-19 08:44:31***APPROVED - RESUB #1***
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 1 Status F Date 2008-05-28 Cont ID  
Sent By choops Date 2008-05-28 Time 09:51 Rev Time 0.00
Received By choops Date 2008-05-28 Time 09:51 Sent To E
Notes
2008-05-28 09:53:46***FAILED***
  
  
 1)PROVIDE BEAR ISLAND ACC (ARCHITECTURAL CONTROL
 COMMITTEE) APPROVAL.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED
 GENERATOR EQUIPMENT TO ALL PROPERTY LINES.AS PER
 SECTION 94-305(B)(4) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - GENRES BOX