Plan Review Details - Permit 08050543
Plan Review Stops For Permit 08050543
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-21 Cont ID  
Sent By jwitmer Date 2008-10-21 Time 15:03 Rev Time 0.77
Received By jwitmer Date 2008-10-21 Time 15:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-09-11 Cont ID  
Sent By jwitmer Date 2008-09-11 Time 08:56 Rev Time 0.77
Received By jwitmer Date 2008-09-11 Time 08:56 Sent To  
Notes
2008-09-11 08:58:34BUILDING PLAN REVIEW
 PERMIT: 08050543/ GENERATOR W/ CONCRETE PAD
 ADD: 6650 45TH ST.
 CONT: SBA NETWORK SERVICES
 TEL: (352)629-1774
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SEPTEMBERE 11,2008
 2ND REVIEW
 ACTION: DENIED
  
 1A-C) COMPLIED
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) COMPLIED
  
 1F) 2ND REQUEST, THE CITY'S ADDRESSING DEPARTMENT HAS
 DETERMINED THAT THE CURRENT ADDRESS IS OUT OF THE
 CITIES RANGE, THE NEW ADDRESS FOR THIS PCN WILL BE 6650
 45TH STREET AND SHOULD BE USED ON ALL PLANS, PERMIT
 APPLICATION AND CORRESPONDANCE.
  
 2) COMPLIED
  
 3) 2ND REQUEST, , 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 4) IN BOTH SETS OF PLANS ONLY THE COVER SHEET IS SIGNED
 AND SEALED.PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G16.003 ARCHITECTS
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-06-17 Cont ID  
Sent By jwitmer Date 2008-06-17 Time 12:26 Rev Time 2.22
Received By jwitmer Date 2008-06-17 Time 12:26 Sent To  
Notes
2008-09-11 08:55:10BUILDING PLAN REVIEW
 PERMIT: 08050543/ GENERATOR W/ CONCRETE PAD
 ADD: 6650 45TH ST.
 CONT: SBA NETWORK SERVICES
 TEL: (352)629-1774
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SEPTEMBERE 11,2008
 2ND REVIEW
 ACTION: DENIED
  
 1A-C) COMPLIED
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) COMPLIED
  
 1F) 2ND REQUEST, THE CITY'S ADDRESSING DEPARTMENT HAS
 DETERMINED THAT THE CURRENT ADDRESS IS OUT OF THE
 CITIES RANGE, THE NEW ADDRESS FOR THIS PCN WILL BE 6650
 45TH STREET AND SHOULD BE USED ON ALL PLANS, PERMIT
 APPLICATION AND CORRESPONDANCE.
  
 2) COMPLIED
  
 3) 2ND REQUEST, , 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 4) ONLY THE FIRST SHEET IN BOTH SETS OF PLANS ARE
 SIGNED AND SEALED. BUILDING PLAN REVIEW
 PERMIT: 08050543/ GENERATOR W/ CONCRETE PAD
 ADD: 6650 45TH ST.
 CONT: SBA NETWORK SERVICES
 TEL: (352)629-1774
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.PLEASE UPDATE THE
 STRUCTURAL ANALYSIS REPORT & THE STRUCTURAL SHEET S-1 &
 T-1.
  
 1F) THE CITY'S ADDRESSING DEPARTMENT HAS DETERMINED
 THAT THE CURRENT ADDRESS IS OUT OF THE CITIES RANGE,
 THE NEW ADDRESS FOR THIS PCN WILL BE 6650 45TH STREET
 AND SHOULD BE USED ON ALL PLANS, PERMIT APPLICATION AND
 CORRESPONDANCE.
  
 2) PLANS INDICATE ON SHEET T-1 130 MPH WIND ZONE PLEASE
 CORRECT TO 140 MPH SEE FIGURE 1609.
  
 3) SOILS REPORTS ARE REQUIRED, 1802.2.1 QUESTIONABLE
 SOIL. WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 4) IN BOTH SETS OF PLANS ONLY THE COVER SHEET IS SIGNED
 AND SEALED.PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT. FL ADMIN CODE 61G16.003 ARCHITECTS
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
2008-06-17 12:28:44BUILDING PLAN REVIEW
 PERMIT: 08050543/ GENERATOR W/ CONCRETE PAD
 ADD: 6650 45TH ST.
 CONT: SBA NETWORK SERVICES
 TEL: (352)629-1774
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.PLEASE UPDATE THE
 STRUCTURAL ANALYSIS REPORT & THE STRUCTURAL SHEET S-1 &
 T-1.
  
 1F) THE CITY'S ADDRESSING DEPARTMENT HAS DETERMINED
 THAT THE CURRENT ADDRESS IS OUT OF THE CITIES RANGE,
 THE NEW ADDRESS FOR THIS PCN WILL BE 6650 45TH STREET
 AND SHOULD BE USED ON ALL PLANS, PERMIT APPLICATION AND
 CORRESPONDANCE.
  
 2) PLANS INDICATE ON SHEET T-1 130 MPH WIND ZONE PLEASE
 CORRECT TO 140 MPH SEE FIGURE 1609.
  
 3) SHEET S-1:
 3A) FOUNDATION NOTE# 2 INDICATES SOILS TEST ARE TO BE
 COMPLETED, 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 3B) FOUNDATION NOTE # 2 INDECATES THE DESIGN TO THE
 2004 FBC WITH 2006 REVISIONS, PLEASE UPDATE TO THE 2007
 FBC REVISIONS, PLANS SUBMITTED AFTER JULY 1,2007 ARE TO
 BE DESIGNED TO THE 2007 WIND PROVISIONS.
  
 3C) FOUNDATION NOTE# 2 PLEASE REVISE WIND INFORMATION
 TO 140MPH, 3 SECOND GUST ,PLEASE SEE FIGURE 1609.
  
 3D) FOUNDATION NOTE# 2 PLEASE REVISE BUILDING CATEGORY
 TO A CATEGORY IV ASCE 7-02 TABLE 6-1.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-10-21 Cont ID  
Sent By dpalmer Date 2008-10-21 Time 11:58 Rev Time 0.00
Received By dpalmer Date 2008-10-21 Time 11:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-09-11 Cont ID  
Sent By dpalmer Date 2008-09-11 Time 11:52 Rev Time 0.00
Received By dpalmer Date 2008-09-11 Time 11:52 Sent To  
Notes
2008-09-11 11:52:11 
  
  
  
 ** DENIED REVIEW **
  
  
  
 1) NOTE: PLANS ARE NOT SEALED WITH RAISED SEAL AS
 REQUIRED PER FS 471.025, FAC 61G15-23.002.
  
 ** THIS IS ALSO REQUIRED FOR ALL OTHER SHEETS AND
 TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWERS
  
 2) NOTE: BASED ON RESPONSE COMMENT FOR VALUE FOR
 COMPLETE SCOPE OF WORK. THE VALUE WAS INCREASED ON
 PERMITS 08050540 TO $238,000 AND 08050543 TO $55,000.
 FEES DUE BEFORE PERMITS CAN BE ISSUED.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-06-18 Cont ID  
Sent By dpalmer Date 2008-06-18 Time 15:38 Rev Time 0.00
Received By dpalmer Date 2008-06-18 Time 15:38 Sent To  
Notes
2008-06-18 15:38:47** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE VALUE FOR THE COMPLETE SCOPE OF
 WORK INCLUDING ALL EQUIPMENT, DESIGN COST ETC SHALL BE
 INCLUDED EVEN IF ANY EQUIPMENT SUCH AS THE BUILDING,
 GENERATOR ETC IS OWNER SUPPLIED.
 FBC 108.3
  
 2) NOTE: PLEASE BE SURE TO SUBMIT THE MANUFACTURES
 SPECS/CUT SHEETS WHICH ACTUALLY STATE THE MINIMUM
 CLEARANCES. AS REQUIREMENTS FOR OTHER TRADES SUCH AS
 ZONING MAY REQUIRE A WALL OF SOME KIND. THE SET BACKS
 NEED TO BE SHOWN.
 NEED TO ALSO SHOW THE ACTUAL SET BACK FROM PROPERTY
 LINE AS THE MINIMUM WILL ALSO BE REQUIRED FROM PROPERTY
 LINE.
 90.7, 110.3. ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 3) NOTE: PLEASE SHOW HOW ANY TRANSFER OF POWER FROM THE
 RECEPTACLE SHOWN ON PLANS TO EQUIPMENT MEETS 701.7.
  
 4) NOTE: PLEASE STATE ON PLANS THE MINIMUM RUN TIMES
 PER FEDERAL CODE OF REGULATIONS TITLE 47, PART 12.2
  
 5) NOTE: PLEASE BE SURE TO DATE PLANS WHEN SIGNING AND
 SEALING PER FS 471.025, 481.221
  
 6) NOTE: PLEASE SHOW HOW THE BREAKER ON THE GENERATOR
 MEETS 701.11B5 FOR THE EXCEPTION OF THE REQUIRED
 DISCONNECT PER 225.361-225.39 FOR FEEDERS.
  
 7) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED ATS. 90.7,110.3, 701.7.
 PLEASE SEE COMMENT #3 ABOVE WHICH WILL ALSO NEED
 SPECS/CUT SHEETS.
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-10-21 Cont ID  
Sent By mawillia Date 2008-10-21 Time 12:46 Rev Time 0.00
Received By mawillia Date 2008-10-21 Time 12:34 Sent To  
Notes
2008-10-21 12:46:44*****APPROVED*****
  
  
 PLAN SHEET A-3 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-09-23 Cont ID  
Sent By mwennerg Date 2008-09-23 Time 12:18 Rev Time 0.00
Received By mwennerg Date 2008-09-23 Time 12:18 Sent To  
Notes
2008-09-23 12:19:03***DENIED***
  
 1) PLANS HAVE BEEN REVISED TO ILLUSTRATE THE CORRECT
 ADDRESS. PLEASE CORRECT PERMIT APPLICATION AND ALL
 SUPPORTING DOCUMENTS TO CORRELATE INFORMATION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-06-25 Cont ID  
Sent By mawillia Date 2008-06-25 Time 16:47 Rev Time 0.00
Received By mawillia Date 2008-06-25 Time 16:01 Sent To  
Notes
2008-06-25 16:08:21*****DENIED*****
  
  
  
 1.THE ACTUAL SCOPE OF WORK ADDRESS SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.SEE BLDG
 EXAMINER'S COMMET # 1F
  
 2.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE TO THE SAID PROPERTY OR THE
 VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES, ETC) .
  
 3.PLEASE INDICATE THE USAGE OF THE STATIONARY
 GENERATOR AS FOR EMERGENCY USE OR STANDBY POWER.
  
 4.THE GENERATOR SHALL BE INSTALLED IN ACCORDANCE WITH
 NFPA 110, 2002 EDITION.
  
 5.DEPENDING UPON LOCATION OF THE EQUIPMENT,
 SAFEGUARDS AGAINST MECHANICAL DAMAGE MAY BE REQUIRED
 AND SHALL BE ILLUSTRATED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 3 Status P Date 2008-10-07 Cont ID  
Sent By tgordon Date 2008-10-07 Time 14:26 Rev Time 0.20
Received By tgordon Date 2008-10-07 Time 14:26 Sent To  
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status F Date 2008-09-03 Cont ID  
Sent By tgordon Date 2008-09-03 Time 08:33 Rev Time 0.45
Received By tgordon Date 2008-09-03 Time 08:33 Sent To  
Notes
2008-09-03 08:36:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SITE PLANS NEED TO BE SEALED BY THE ARCHITECT
 (ROBERT J. LARA), PER FAC 61G1-16.003.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2008-06-09 Cont ID  
Sent By tgordon Date 2008-06-09 Time 16:25 Rev Time 0.00
Received By tgordon Date 2008-06-09 Time 16:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-06 Cont ID  
Sent By adarroug Date 2008-10-06 Time 10:59 Rev Time 0.00
Received By adarroug Date 2008-10-06 Time 10:59 Sent To  
Notes
2008-10-06 11:23:51TO "COMM" BD#24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 15:55 Rev Time 0.00
Received By tgordon Date 2008-08-26 Time 15:55 Sent To  
Notes
2008-08-26 15:56:14TO "COMM" BD #11.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-06-25 Cont ID  
Sent By mawillia Date 2008-06-25 Time 16:48 Rev Time 0.00
Received By mawillia Date 2008-05-20 Time 16:23 Sent To  
Notes
2008-05-20 16:24:06WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-10-07 Cont ID  
Sent By tgordon Date 2008-10-07 Time 14:26 Rev Time 0.20
Received By tgordon Date 2008-10-07 Time 14:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-06-09 Cont ID  
Sent By tgordon Date 2008-06-09 Time 16:24 Rev Time 0.15
Received By tgordon Date 2008-06-09 Time 16:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2008-06-06 Cont ID  
Sent By kstevens Date 2008-06-06 Time 10:55 Rev Time 0.00
Received By kstevens Date 2008-06-06 Time 10:55 Sent To  
Notes
2008-06-06 10:56:33GENERATOR IS INDICATED AS A DIESEL GENERATOR

Review Stop Z ZONING
Rev No 2 Status P Date 2008-09-02 Cont ID  
Sent By kdfreema Date 2008-09-02 Time 11:54 Rev Time 0.00
Received By kdfreema Date 2008-09-02 Time 11:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-02 Cont ID  
Sent By kdfreema Date 2008-06-02 Time 14:27 Rev Time 0.00
Received By kdfreema Date 2008-06-02 Time 14:27 Sent To  
Notes
2008-06-02 16:02:10***FAILED***
  
 PER SEC. 94-444(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS, THE GENERATOR SHALL BE SCREENED WITH A
 HEDGE.
  
 IT IS RECOMMENDED TO PLANT THE HEDGES ON THE OUTSIDE OF
 THE FENCE SURROUNDING THE TOWER. WE RECOMMEND EITHER
 PODOCARPUS MACROPHYLLA PLANTED AT 30 INCHES ON CENTER
 OR BOUGAINVILLEA SPP AT 48 INCHES ON CENTER. ONLY THE
 WEST, SOUTH, AND EAST SIDES OF THE FENCE NEED TO BE
 PLANTED. ANY GATES MAY BE LEFT UNPLANTED AS WELL.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT
 [email protected] OR 561-822-1435 WITH QUESTIONS.