| 2008-06-17 08:43:09 | BUILDING PLAN REVIEW |
| | PERMIT: 08050540 |
| | ADD: 6650 45TH ST. |
| | CONT: SBA NETWORK SERVICES |
| | TEL: (352)629-1774 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE |
| | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS.PLEASE UPDATE THE |
| | STRUCTURAL ANALYSIS REPORT & THE STRUCTURAL SHEET S-1 & |
| | T-1. |
| | |
| | 1F) THE CITY'S ADDRESSING DEPARTMENT HAS DETERMINED |
| | THAT THE CURRENT ADDRESS IS OUT OF THE CITIES RANGE, |
| | THE NEW ADDRESS FOR THIS PCN WILL BE 6650 45TH STREET |
| | AND SHOULD BE USED ON ALL PLANS, PERMIT APPLICATION AND |
| | CORRESPONDANCE. |
| | |
| | 2) AMERICAN TOWER ENGINEERING SERVICES -STRUCTURAL |
| | ANALYSIS REPORT DOES NOT INDICATE THERE CERTIFICATE OF |
| | AUTHORIZATION NUMBER. 481.219 F.S. CERTIFICATE OF |
| | AUTHORIZATION. THE TITLE BLOCK FOR ANY SHEET BEARING |
| | THE NAME OF AN ARCHITECT PRACTICING UNDER A FICTITIOUS |
| | NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING |
| | ARCHITECTURAL SERVICES, SHALL INCLUDE THE CERTIFICATE |
| | OF AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET. |
| | WE COULD NOT FIND YOUR COA NUMBER ON THE DEPARTMENT OF |
| | BUSSINESS & PROFESSIONAL REGULATION WEBSSITE, PLEASE |
| | PROVIDE. THIS MAY BE ADDED BY HAND. |
| | |
| | 3) ENGINEER JASON SEAVERSON - AMERICAN TOWER STRUCTURAL |
| | ANALYSIS REPORT HAS SIGNED AND SEALED THIS DOCUMENT BUT |
| | MISSING HIS PRINTED NAME AND LICENSE NUMBER, PLEASE |
| | CORRECT. |
| | 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED |
| | BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE: |
| | NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR, |
| | THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE |
| | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER |
| | IS PRACTICING (471.025 F.S. AND 471.023 F.S.). |
| | |
| | 4) ENGINEER JASON SEAVERSON - AMERICAN TOWER STRUCTURAL |
| | ANALYSIS REPORT DOES NOT INDICATE HOW MANY SHEETS ARE |
| | WITHIN THE DOCUMENT AND HAS ONLY SIGNED AND SEALED THE |
| | COVER SHEET, PLEASE CORRECT. 61G15-23.002(2) FL. ADMIN. |
| | CODE. A COVER SHEET OR INDEX SHEET FOR ENGINEERING |
| | SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE |
| | SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION & |
| | PREPARATION OF EACH SECTION OF THE ENGINEERING |
| | SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER |
| | SHEET OR INDEX. |
| | |
| | 5) STRUCTURAL ANALYSIS REPORT PAGE 1 IT APPEARS THERE |
| | MAY BE CONFLICTS WITH SECTIONS OF THE CODE: DESIGNS ARE |
| | TO ASCE 7-02, |
| | |
| | 5A) THE STRUCTURAL CLASSIFICATION OF THE STRUCTURE IS A |
| | CLASS II, PLEASE SEE ASCE 7-02 TABLE 1-1, |
| | COMMUNICATIONS TOWERS ARE LISTED AS A TYPE IV STRUCTURE |
| | , CELL PHONES ARE USED AS PART OF THE RECOVERY EFFORT |
| | FOR HIGH WIND EVENTS, PLEASE SEE TABLE 6-1 IMPORTANCE |
| | FACTOR FOR BUILDING CATEGORY IV= 1.15 NOT THE 1.0 |
| | LISTED . |
| | |
| | 5B) LOAD CASE IS INDICATED AS 1.2D+1.6W PLEASE SEE |
| | 1605.2 BASIC LOAD COMBINATIONS 0.9D+(1.6W) IS THE MORE |
| | RESTRICTIVE DESIGN WHICH SHOULD HAVE BEEN USED IN THIS |
| | CASE. 1605.2.1 WHERE STRENGTH DESIGN OR LOAD AND |
| | RESISTANCE FACTOR DESIGN IS USED, STRUCTURES AND |
| | PORTIONS THEREOF SHALL RESIST THE MOST CRITICAL EFFECTS |
| | FROM THE FOLLOWING COMBINATIONS OF FACTORED LOADS. |
| | |
| | PLEASE RUN THE LOADING CALCULATIONS WITH THESE |
| | ADJUSTMENT FACTORS TO MEET THE CURRENT WIND LOADING |
| | CRITERIA. THE CALCULATIONS MAY EXCEED THE 5% ADDITIONAL |
| | GRAVITY LOADS ALLOWED UNDER THE 2004 FBC EXISTING |
| | BUILDING CODE 903.2, EXCEPTION# 1. |
| | |
| | 6) PLANS INDICATE ON SHEET T-1 130 MPH WIND ZONE PLEASE |
| | CORRECT TO 140 MPH SEE FIGURE 1609. |
| | |
| | 7) SHEET A-3 INDICATES THE USE OF A STATE APPROVED AT&T |
| | EQUIPMENT SHELTER, PLEASE PROVIDE (2) COPIES OF THE |
| | STATE STATE APPROVED PLANS FOR MODULAR BUILDINGS 428.1, |
| | RULE 9B-1 FLORIDA ADMINISTRATIVE CODE AND CHAPTER 553 |
| | FL S S . |
| | |
| | 8) SHEET S-1: |
| | 8A) FOUNDATION NOTE# 2 INDICATES SOILS TEST ARE TO BE |
| | COMPLETED, 1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 8B) FOUNDATION NOTE # 2 INDECATES THE DESIGN TO THE |
| | 2004 FBC WITH 2006 REVISIONS, PLEASE UPDATE TO THE 2007 |
| | FBC REVISIONS, PLANS SUBMITTED AFTER JULY 1,2007 ARE TO |
| | BE DESIGNED TO THE 2007 WIND PROVISIONS. |
| | |
| | 8C) FOUNDATION NOTE# 2 PLEASE REVISE WIND INFORMATION |
| | TO 140MPH, 3 SECOND GUST ,PLEASE SEE FIGURE 1609. |
| | |
| | 8D) FOUNDATION NOTE# 2 PLEASE REVISE BUILDING CATEGORY |
| | TO A CATEGORY IV ASCE 7-02 TABLE 6-1. |
| | |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |