| 2008-05-29 09:42:40 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1. THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT |
| | IS TO BE ON EACH SHEET, FAC61G1-16-23.002, 003. |
| | |
| | 2.PROVIDE TWO COMPLETE COLLATED SETS OF PERMIT |
| | DOCUMENTS.ONE SET HAS TWO OF THE SHUTTER NOAS |
| | ATTACHED, THE OTHER HAS TWO HR WINDOW NOAS ATTACHED, |
| | NEITHER HAS SH WINDOW OR DOOR PRODUCT APPROVALS. |
| | |
| | 3.SCOPE OF WORK APPEARS TO INCLUDE SINGLE HUNG |
| | WINDOWS AND DOORS. FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVALS REQUIRED, FAC9B72. |
| | |
| | 4.PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| | SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 505.1. |
| | |
| | 5.FOR THE SHUTTERS, COMPLETE THE ATTACHED |
| | INSTALLATION SCHEDULE..TWO SETS REQUIRED. |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | 6.INDICATE ANY REQUIRED FIRE RESISTANCE RATINGS |
| | REQUIRED ON THE PLAN (STAIRS). FBC EB504. |
| | |
| | 7.DECLARE OCCUPANCY, FBC CHAPTER 3.CODE COMPLIANCE |
| | AND REQUIREMENTS CANNOT BE DETERMINED WITHOUT THIS |
| | INFORMATION. |
| | |
| | |