Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-16 Cont ID  
Sent By shill Date 2008-10-16 Time 17:30 Rev Time 0.00
Received By shill Date 2008-10-16 Time 17:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-09-18 Cont ID  
Sent By shill Date 2008-09-18 Time 13:34 Rev Time 0.00
Received By shill Date 2008-09-18 Time 13:34 Sent To  
Notes
2008-09-18 13:35:15****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE PAGE 11 OF THE SHUTTER PRODUCT APPROVAL. A
 FACTOR OF .86 IS TO BE APPLIED TO THE ANCHOR SPACING
 WHEN THE EDGE DISTANCE IS 3".
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-05-29 Cont ID  
Sent By shill Date 2008-05-29 Time 09:29 Rev Time 0.00
Received By shill Date 2008-05-29 Time 09:29 Sent To  
Notes
2008-05-29 09:42:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1. THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT
 IS TO BE ON EACH SHEET, FAC61G1-16-23.002, 003.
  
 2.PROVIDE TWO COMPLETE COLLATED SETS OF PERMIT
 DOCUMENTS.ONE SET HAS TWO OF THE SHUTTER NOAS
 ATTACHED, THE OTHER HAS TWO HR WINDOW NOAS ATTACHED,
 NEITHER HAS SH WINDOW OR DOOR PRODUCT APPROVALS.
  
 3.SCOPE OF WORK APPEARS TO INCLUDE SINGLE HUNG
 WINDOWS AND DOORS. FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED, FAC9B72.
  
 4.PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 505.1.
  
 5.FOR THE SHUTTERS, COMPLETE THE ATTACHED
 INSTALLATION SCHEDULE..TWO SETS REQUIRED.
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 6.INDICATE ANY REQUIRED FIRE RESISTANCE RATINGS
 REQUIRED ON THE PLAN (STAIRS). FBC EB504.
  
 7.DECLARE OCCUPANCY, FBC CHAPTER 3.CODE COMPLIANCE
 AND REQUIREMENTS CANNOT BE DETERMINED WITHOUT THIS
 INFORMATION.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-07 Cont ID  
Sent By shill Date 2008-10-07 Time 08:52 Rev Time 0.00
Received By shill Date 2008-10-07 Time 08:52 Sent To B
Notes
2008-10-07 08:52:51TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-15 Cont ID  
Sent By adarroug Date 2008-09-15 Time 11:05 Rev Time 0.00
Received By adarroug Date 2008-09-15 Time 11:05 Sent To B
Notes
2008-09-15 11:06:13TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-05-29 Cont ID  
Sent By shill Date 2008-05-29 Time 09:42 Rev Time 0.00
Received By shill Date 2008-05-20 Time 12:00 Sent To  
Notes
2008-05-20 12:01:33TO "MISC" BOX#1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved